1. Introduction
The growing importance of electricity generation and environmental sustainability necessitates robust, efficient, and resilient electrical power systems. The North American Blackout of 2003 [
1] highlighted the importance of distributed control in large-scale interconnected power systems, with a specific focus on the ability to withstand physical and network communication challenges as well as the ability to recover and reorganize autonomously. The European interconnected grid also exemplifies how interconnected power systems can meet these challenges by facilitating efficient distribution and sharing of electrical power [
2]. Moreover, these interconnected grids achieve energy security and sustainability by balancing loads and integrating renewable energy sources to satisfy increasing energy demands. This dual approach benefits all stakeholders and improves power reliability for residents, ensuring reliable energy supply, enhancing environmental protection, and enabling energy trade and communication between nations [
3].
In connection with the operation and control of power systems, providing a sufficient reliable supply of high-quality electricity with high standards is a priority. Achieving this target depends critically on load frequency control (LFC). There are several control areas in an interconnected power system where all generators constitute a cohesive unit [
4]. During steady-state operation, variations in load demand lead to changes in kinetic energy stored within generator prime movers. Consequently, these changes affect speed and frequency. Hence, effective control of load frequency becomes indispensable for the secure operation of the power system [
5,
6,
7,
8,
9,
10]. LFC is a technique that adjusts the power output of controlled generators in a particular area in response to fluctuations in system frequency, tie-line, or their interaction. The goal is to maintain the scheduled system frequency and establish interchange with additional areas within predetermined limits [
11,
12,
13,
14]. An optimal control method that ensures frequency stability and the intended tie-line power flow as well as zero steady-state error and accidental interchange is sought. The conventional Proportional–Integral (PI) controller stands out as the most widely used among the array of load frequency controllers available [
15,
16]. Recent advancements in control strategies for power systems have focused on predictive control methods and reinforcement learning techniques to enhance system performance and stability. For instance, learning-based predictive control can improve the dynamic response and robustness of power converters [
17,
18] and voltage source inverters [
19] in a power system. However, their effectiveness diminishes as system complexity increases due to load fluctuations and boiler dynamics [
20]. Hence, there is a need for controllers capable of addressing these challenges. Artificial intelligence (AI) controllers, such as the Neural Network Control approach, prove more fitting in this context [
21]. These techniques possess the advantage of providing model-free control descriptions, eliminating the need for model identification. Employing an Advanced Adaptive Control setup like the ANN controller is particularly beneficial, as it offers swifter control than other methods [
22]. To enhance the performance of conventional controllers (PI and PID) and neural controllers, a proposal is made for an Artificial Neural Network (ANN) controller within a two-area interconnected hydro–thermal and thermal–thermal power plant scenario. Including a neural controller sliding surface is motivated by variable structure control (VSC). This concept involves utilizing a sliding surface that leads to robust control systems, often resulting in invariant systems. Invariance implies that the system remains unaffected mainly by parametric uncertainty and external disturbances [
23,
24]. However, traditional PID algorithms offer simplicity, reliability, low computational demands, fast response, less expensive, and ease of practical implementation and tuning, making them superior to AI controllers in straightforward, well-defined control systems [
25,
26,
27].
The investigation of an LFC conflict in a nonlinear power generation network is conducted by implementing an innovative hybrid GSA-tuned optimized controller [
28]. A PSO-PID controller and a PID controller based on the flower pollination algorithm (FPA) were developed to analyze the frequency regulation of nuclear power facilities integrated with networks of thermal, gas, hydro, and PV power systems to address LFC conflicts [
29]. These techniques provide premature convergence and do not convert the global optima; also, early convergence becomes caught in local optima when used for complex problems. The GWO algorithm was employed in [
30,
31] to modify the controller parameters. The simulation results demonstrated that the GWO algorithm could rapidly suppress the power system frequency and power oscillations. However, as the algorithm progresses, the lead wolf’s weight increases unsustainably, making it simple to enter the local optimum. The gray wolf algorithm was employed in [
32,
33] to optimize and regulate the frequency of multi-area loads. At the same time, it encountered the convergence issue. In a later phase, the proportion of the lead wolf grew excessively high, resulting in local optima. The gray wolf optimization algorithm was implemented in [
34] to optimize the time-delayed load frequency control problem. The gray wolf algorithm with fixed weight demonstrated a more favorable outcome in the domain of optimal frequency control [
35]. The method cannot exist for local search due to slow convergence speed at the later part of the iteration; however, it resulted in slow convergence and poor precision and accuracy.
Stabilizing load frequency in interconnected power systems is a research area that has seen various algorithms proposed to enhance the performance of Proportional–Integral–Derivative (PID) controllers. El-Hameed and El-Fergany [
36] pioneered the integration of the Water Cycle Algorithm (WCA) with PID controllers, addressing nonlinearity in interconnected power systems. This approach exhibits delayed convergence and limited exploration and exploitation. The technique demonstrates a frequency response that requires more time to settle. Guha et al. [
37] advanced this domain by implementing the Backtracking Search Algorithm (BSA) in the LFC of a multi-area interconnected power system, demonstrating improved system stability and robustness. BSA generally exhibits a slow convergence rate during its early stages due to its disregard for the significance of the optimal individual, which challenges its ability to attain a satisfactory outcome. This is the reason the frequency response requires more time to settle down. Yeboah et al. [
38] employed the Gravitational Search Algorithm (GSA) to address LFC challenges in multi-area power systems, offering a novel approach to system optimization by mimicking the law of gravity and mass interactions. GSA suffers from premature convergence due to rapid reduction in diversity. Frequency response requires more time to settle down. Comparative studies by Hakimuddin et al. [
39] explored the efficacy of Genetic Algorithms (GAs), Bacteria Foraging Algorithms (BFAs), Particle Swarm Optimization (PSO) [
40], and Mayfly Algorithm (MA) [
41] in multi-source power plants, highlighting the competitive nature of these algorithms and also highlighting the need for more comprehensive comparative frameworks. This technique converges quickly, gets stuck in the local optimal solution, and takes more time to settle. Mohanty et al. [
42] introduced the Moth Flame Optimization Algorithm (MFOA), demonstrating the potential of bio-inspired algorithms in achieving fine-tuned control over LFC in power systems. This technique provides limited population variety and falls into local optima and premature convergence. The outcomes were less time-settled than other techniques, but overall performance was low. Acharyulu et al. [
43] and Jagatheesan et al. [
44] proposed using Green Anaconda Optimization and gray wolf optimization algorithms, focusing on renewable energy and diverse power generation systems. These techniques are frequency response, and more time is required for stability. However, in this research, paperwork is a benchmark for the proposed pelican optimization algorithm (POA)-PID controller, aiming to further reduce frequency deviations and the cost function ITAE in a complex four-area power system. The proposed POA technique outperforms existing techniques by effectively balancing exploration and exploitation, achieving superior and more competitive performance [
45,
46,
47]. It classifies a population-based approach that converges to a nearly optimal solution through an iterative procedure. The proposed technique, LFC, rapidly resolved the issue of time to settle.
The above comprehensive literature review underscores the extensive exploration of various optimization algorithms to fine-tune auxiliary controller gains for implementing LFC in multi-area interconnected power systems. In this paper, the POA is proposed for optimizing the gain values of PID controllers under a 1% step load perturbation across a mixed thermal–hydro–gas turbine power plant. Given the prevalence of thermal power generation due to its scalability and accessibility, its environmental impact remains a significant drawback. This study aims to mitigate such drawbacks by integrating conventional thermal, reheat thermal power plants, gas turbine power plants, and hydropower plants, enhancing the power generation mix’s efficiency and sustainability. The effectiveness of the newly optimized regulation technique is assessed by comparing it against the performance metrics of PID controllers tuned via gray wolf optimization (GWO), Harris Hawks Optimization (HHO), Particle Swarm Optimization (PSO), and Moth Flame Optimization Algorithm (MFOA). Additionally, the robustness and adaptability of the proposed POA-PID controller are evaluated under varying load disturbances, and parameter changes ±25% and ±50% of their nominal values, highlighting its superior performance and efficiency in maintaining system stability and operational efficiency.
The main contributions of this paper are as follows:
Interconnected power systems with and without pollution-free generating sources are modeled for ith area. Further, based on the modeled ith area power systems network, a four-area power network is developed for testing and validation purposes.
Introduced a secondary controller for LFC that utilizes POA-based PID controller tuning parameters to maintain stability during unexpected load changes.
Conducted comprehensive robustness analysis under varying load conditions and variations in parameters, confirming the effectiveness of the POA-PID controller.
Proposed POA-based optimization technique performance is compared against established methods like GWO, PSO, MFOA, and HHO to set new benchmarks for load frequency and tie-line power flow control efficiency, showing significant improvements in ITAE and system stability.
The article is arranged as follows:
Section 2 is the mathematical modeling of the proposed four-area interconnected power system.
Section 3 shows the structure of the controller and optimization technique.
Section 4 shows the analysis investigated between the proposed controller POA-PID and other algorithms, including GWO, MFOA, PSO, and HHO-PID controller. Finally, the conclusion about optimization techniques is in
Section 5.
5. Conclusions
This study introduces an LFC mechanism for an ith area interconnected power network using a PID controller enhanced through the POA. The POA technique is utilized to optimize the gain parameters of the PID controller, ensuring the system output power is maintained without damping oscillations during unpredicted load-varying conditions in the tie-line between interconnected areas. The proposed POA-PID controller significantly improves control efficacy in a complex, four-area power grid, reducing the ITAE value to 0.084346. Compared to conventional optimization techniques, GWO, MFOA, PSO, and HHO, the POA-PID controller shows enhanced efficiency by margins of 7.01%, 7.31%, 45.97%, and 50.57%, respectively, in a diverse-generation unit power network. This underscores the robust optimization capability of the POA, setting new benchmarks for load frequency and tie-line power flow control efficiency by an average of 45.56% and 42.79%, respectively. The POA-PID controller demonstrated remarkable resilience despite load variations, maintaining performance parameters and system frequency stability, with a maximum deviation of 11 s under severe disturbances.
The findings highlight the efficacy of the POA-PID controller in managing interconnected power systems. The POA addresses key technical challenges, including managing dynamic load changes, handling the complexities of multi-area systems, and minimizing frequency deviations. It provides adaptive tuning of PID controller parameters, enhancing system responsiveness to sudden load variations and achieving quicker stabilization and improved overall stability but acknowledges limitations such as implementing the POA requires substantial computational resources and expertise. Its scalability in larger systems needs further testing, and real-time optimization presents challenges demanding advanced computational capabilities. Ensuring consistent performance across diverse scenarios and integrating POA with existing infrastructure may require system modifications.
Future work aims to extend the applicability and robustness of the POA-based PID controller by testing in a broader array of power system configurations, incorporating a more comprehensive range of load disturbances, developing hybrid optimization techniques, and implementing the controller in more realistic environments.