Correction

Correction: Melgaard et al. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366

by
Simon P. Melgaard
*,
Kamilla H. Andersen
,
Anna Marszal-Pomianowska
,
Rasmus L. Jensen
and
Per K. Heiselberg
Department of the Built Environment, Aalborg University, Thomas Manns Vej 23, 9220 Aalborg Ø, Denmark
*
Author to whom correspondence should be addressed.
Energies 2024, 17(21), 5407; https://doi.org/10.3390/en17215407
Submission received: 23 September 2022 / Accepted: 27 September 2022 / Published: 30 October 2024
(This article belongs to the Section G: Energy and Buildings)
Error in Table
In the original publication [1], Table 10 was difficult to read and has therefore been modified to make distinguishing between the classes easier. The updated Table 10 can be seen below. Besides these, there was a mistake in Table 11 as published. Due to a miscommunication, the table did not indicate the different types of references, as written in the table caption. The corrected Table 11, along with an updated table caption, appears below.
Text Correction
Due to the corrections made to Table 11, some corrections have been made to Section 5.2.2. Performance Evaluation Metrics.
The previous text was:
The performance evaluation metric with an underscore is the name suggested for future application to avoid confusion. The references in bold specified precisely how the metric was calculated and the name of the metric. The references without bold text only stated the name of the metric, and not the numerical calculation.
The new text is:
The performance evaluation metrics with an underscore are the names suggested for future applications. The references in the column “Specified name of the metric and equation” specify precisely how the metric was calculated and the name used for the metric. The references in the column “Specified name of the metric but not the equation” only state the metric’s name but not the equation applied to calculate it.
The authors state that the scientific conclusions are unaffected. This correction was approved by the Academic Editor. The original publication has also been updated.

Reference

  1. Melgaard, S.P.; Andersen, K.H.; Marszal-Pomianowska, A.; Jensen, R.L.; Heiselberg, P.K. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366. [Google Scholar] [CrossRef]
Table 10. Proposed generalized definition template for confusion matrix of FDD (multiple faulty and one nonfaulty class).
Table 10. Proposed generalized definition template for confusion matrix of FDD (multiple faulty and one nonfaulty class).
Predicted   Class   N P
Negative
(Non-Faulty)
N P , N
Positive
(Fault 1)
N P , P , c p
Positive
(Fault n−1) N P , P , c p
Positive
(Fault n) N P , P , c p
True class N T Negative
(Nonfaulty)
N T , N
T N (No alarm) F P , c p (False alarm)
Positive (Fault 1)
N T , P , c t
F N , c t (Missed alarm) T P , c t = T P , 1 (Alarm)
T P , c t (Alarm) F P , c t , c p (Misdiagnosed alarm)
Positive (Fault n − 1)
N T , P , c t
F P , c t , c p (Misdiagnosed alarm) T P , c t = T P , n 1 (Alarm)
Positive (Fault n)
N T , P , c t
T P , c t = T P , n (Alarm)
Table 11. The performance evaluation metrics with an underscore are the names suggested for future applications. The references in the column “Specified name of the metric and equation” specify precisely how the metric is calculated and the name used for the metric. The references in the column “Specified name of the metric but not the equation” only state the metric’s name but not the equation applied to calculate it.
Table 11. The performance evaluation metrics with an underscore are the names suggested for future applications. The references in the column “Specified name of the metric and equation” specify precisely how the metric is calculated and the name used for the metric. The references in the column “Specified name of the metric but not the equation” only state the metric’s name but not the equation applied to calculate it.
Specified Name of the Metric and EquationSpecified Name of the Metric but Not the EquationPerformance Evaluation MetricEquation
[96,104,105,111,150,155,156,158,160,161,163,168,170] Confusion matrix-
Used in FD (1 nonfault class and 1 fault class)
Global[104,105] Correct rate (CR) T P + T N N
[104] Misclassification rate (MisCR) 1 T P + T N N = F P + F N N
Local[153][57,164,168,171]Fault-detection rate (FDR) T P T P + F N = T P N T , P
[154]Correct rate
[84][70]Detection accuracy
[101]Classification accuracy
[104,105] Hit rate
[104] Recall
[104] True-positive rate
[153] False-alarm rate F P F P + T P = F P N P , P
[84,104,105,154][57,111,168,171]False-alarm rate (FAR) F P F P + T N = F P N T , N
Used in FDD (1 nonfault class and multiple fault classes)
Global[56,57,94,95,151,152,155,156,158][161,163,166]Accuracy T N + T P , c t N
[150][96,104,105]Correct rate (CR)
[165,169,190][159,160]Correct diagnosis rate
[101]Classification accuracy
[162]Diagnosis rate
[165,169,190][159]False-diagnosis rate (FaDR) 1 T N + T P , c t N
[94] Macro-F1 (MF1) [191] c = 1 N c 1 F 1 N c
[95] Matthew’s correlation coefficient (MCC) T N T P , c t N T , N N T , P , c t N P , N N P , P , c p
[95] G-mean P R E C
Local[155,161] False-alarm rate F P , c p + F P , c t , c p F P , c p + F P , c t , c p + T P , c t = F P , c p + F P , c t , c p N P , P , c p
[56,104,105][167]False-alarm rate (FAR) F P , c p F P , c p + T N = F P , c p N T , N  
[155] Fake-alarm rate (FaAR) F P , c p F P , c p + F P , c t , c p + T P , c t = F P , c p N P , P , c p
[155,156] Misdiagnosed-alarm rate (MisR) F P , c t , c p F P , c p + F P , c t , c p + T P , c t = F P , c t , c p N P , P , c p
[155] Missed-detection rate (MDR) F N , c t F P , c p + F P , c t , c p + T P , c t = F N , c t N P , P , c p
[156] Misdiagnosed normal rate (MisNR) 1 T N T N + F P , c p = 1 T N N T , N
Local (calculated per class)[95,156] Precision (PREC) T P , c t N P , P , c p   o r   T N N P , N
[157,167,170] Diagnosis ratio
[104,156] Recall (REC)   T P , c t N T , P , c t   o r   T N N T , N
[59] Sensitivity index
[95] Sensitivity
[111] Successful diagnosed ratio
[104,105] Hit rate
[157,167,170] Detection ratio
[156] F1-score (F1) 2     P R E C     R E C P R E C + R E C
[95] F-measure
[56] False-negative rate (FNR) F N , c t F N , c t + c p = 1 N c 1 F P , c t , c p + T P , c t = F N , c t N T , P , c t
[56] False-positive rate (FPR) c p = 1 N c 1 F P , c t , c p F N , c t + c p = 1 N c 1 F P , c t , c p + T P , c t = c p = 1 N c 1 F P , c t , c p N T , P , c t
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Melgaard, S.P.; Andersen, K.H.; Marszal-Pomianowska, A.; Jensen, R.L.; Heiselberg, P.K. Correction: Melgaard et al. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366. Energies 2024, 17, 5407. https://doi.org/10.3390/en17215407

AMA Style

Melgaard SP, Andersen KH, Marszal-Pomianowska A, Jensen RL, Heiselberg PK. Correction: Melgaard et al. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366. Energies. 2024; 17(21):5407. https://doi.org/10.3390/en17215407

Chicago/Turabian Style

Melgaard, Simon P., Kamilla H. Andersen, Anna Marszal-Pomianowska, Rasmus L. Jensen, and Per K. Heiselberg. 2024. "Correction: Melgaard et al. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366" Energies 17, no. 21: 5407. https://doi.org/10.3390/en17215407

APA Style

Melgaard, S. P., Andersen, K. H., Marszal-Pomianowska, A., Jensen, R. L., & Heiselberg, P. K. (2024). Correction: Melgaard et al. Fault Detection and Diagnosis Encyclopedia for Building Systems: A Systematic Review. Energies 2022, 15, 4366. Energies, 17(21), 5407. https://doi.org/10.3390/en17215407

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.