1. Introduction
Climate change is primarily caused by greenhouse gas emissions, especially carbon dioxide (CO2). Power generation contributes most significantly to carbon release. In 2018, as documented by the U.S. Energy Information Agency (EIA), residential and commercial building sectors’ combined consumption represented 40% of total U.S. energy consumption. The residential sector accounts for 55% of this amount. According to the EIA 2015 Residential Energy Consumption Survey (RECS), air conditioning and space heating account for 17% and 15% of residential electricity consumption, respectively. It is evident that minimizing heating, ventilation, and air condition (HVAC) energy consumption can reduce residential energy consumption and greenhouse gas emissions both nationally and worldwide.
Since 2015, there has been a marked evolution of implemented utility-related energy efficiency programs. Pilot programs managed by utility providers throughout the U.S. have documented the energy-saving potential of smart thermostats, ranging from negative to 20% savings [
1]. A 2018 report on smart thermostat market characterization, prepared by a Bonneville Power Administration (BPA) research team, concluded that only “smart advanced thermostats”, which include occupancy sensing and self-learning algorithms, yield savings. One of the studies in their research effort showed an annual saving of 745–955 kWh per thermostat [
2].
The well-known saving mechanism applied by smart thermostats is to maintain a high cooling temperature set-point and a low heating temperature set-point during occupied periods, with even larger increases/decreases (depending upon the season) in unoccupied periods. The former means that users must, to some extent, sacrifice their comfort to achieve energy savings [
3]. However, compromising indoor thermal comfort can lead to significant negative impacts on occupant health and productivity [
4,
5].
2. Background
The question is, therefore, how do systems simultaneously save energy and ensure thermal comfort? It is first important to understand the factors that contribute to thermal comfort. Zonal dry-bulb air temperature alone does not reflect the actual thermal sensation of occupants. In particular, the temperature measurement afforded by a thermostat only represents the indoor room temperature of the space where the thermostat is located. Three additional general factors affect thermal comfort, including (i) other internal environmental factors (room relative humidity, air velocity, and mean radiant temperature (MRT); (ii) residential factors associated with occupant age, gender, clothing ensemble, and level of activity or metabolic rate; and (iii) occupant controls, such as the opening and closing of windows and blinds. Ideally, thermostat set-points should account for most of the factors affecting thermal comfort to generate set-points that are able to establish thermal comfort at any time for the actual conditions existing in a residence.
Fanger’s predicted mean vote (PMV) has generally been used to characterize thermal comfort in buildings. This model was developed by testing multiple subjects under steady-state moderated indoor environments in the 1970s. The PMV index is based upon a heat balance of the human thermoregulatory system [
6]. Thermal equilibrium is achieved when heat losses to the ambient environment are equal to the heat produced by the human body.
The American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) proposed that the PMV index predicts the average vote of a large group of people on a defined thermal sensation scale [
7]. This seven-point scale ranges from −3 to +3 and effectively accounts for the perceived comfort of a majority of people. The lower and upper ends of the scale are associated with most people feeling cold and warm, respectively, as shown in
Table 1.
The PMV index is calculated using six parameters. Four of these are environmental thermal parameters: air temperature (Ta), relative humidity (RH), mean radiant temperature (MRT), and air velocity (m/s). Two are occupant factors: clothing insulation (Clo) and activity level (MET) are related to the human metabolic rate. A comfort range, given by −0.5 < PMV < +0.5, provides reasonable comfort for 90% of people.
Of these, a smart WiFi thermostat assesses only room temperature and humidity. Proposed herein is a new approach to measure the MRT. In general, the other parameters cannot be known without additional sensors or input from the residents themselves. Thus, the following assumptions were made.
- (1)
Activity level (MET). The MET generally ranges from 1.0 to 1.7. A conservative MET value can be estimated depending upon the physical task (e.g., 1.0 for reading or writing while sitting, 1.7 for walking about).
- (2)
Clothing level (Clo). An indoor clothing assembly of between 0.36–0.57 and 0.61–1.01 for, respectively, summer and winter conditions is typically employed. For a minimum energy perspective, we assumed a clothing level reflective of a desire to save energy; thus, a Clo for, respectively, summer and winter conditions of 0.36 and 1.01 was used herein.
- (3)
Relative air velocity/air flow (v
ar). According to ASHRAE 55, the indoor air velocity should not exceed 0.2 m/s (39 fpm) to achieve a minimum livable condition [
8]. Also, in order to reduce draft risk at any temperatures below 22.5 °C (72.5 °F), airspeed due to the HVAC system must be 0.15 m/s (30 fpm) or below [
9]. Therefore, the relative air velocity was assumed to be 0.1 m/s (19.7 fpm).
A number of researchers have investigated various active thermal comfort control approaches in residences based upon the PMV. In these studies, control methodologies have included fuzzy logic (FLC) [
10] and neural network (NN) [
11] based predictive controllers. Prior researchers have succeeded in simultaneously maintaining thermal comfort and reducing energy consumption. In [
10], the authors utilized a complicated hierarchical FLC with a 3D fuzzy set to represent thermal comfort based upon the PMV indicator, indoor illumination, and CO
2 level. Its membership function constraints were tuned by a genetic algorithm (GA). The authors noted a roughly 8% energy increase in order to satisfy more occupants. In [
11], a discrete model-based predictive controller was developed. A cost function to optimize the controller by minimizing energy consumption and maintaining thermal comfort was developed. Energy savings in relation to a standard constant temperature setpoint control l, ranging from 41% - 77%, were realized.
Table 2 summarizes the research conducted in this arena. Included in this table are descriptions of the MRT determination, the thermal comfort assessment, the assumed factor values in calculating the PMV, the control techniques employed, the energy savings derived, and the sensors and other hardware employed. The latter is particularly important. The requirement of sensors not available in systems already present in residences poses a substantial barrier to market penetration.
There is no evidence of thermal comfort control having been implemented at scale. Most approaches have been tested in laboratories or at small-scales, and have utilized sensors not commonly present in residences to improve the estimation of the PMV. Only the research of Zheng et al. [
14], which relies only on smart thermostat measurements (room temperature and humidity), has the potential for rapid market scalability. However, their approach calculated the real-time PMV value by assuming an MRT equal to room temperature. This assumption is generally poor, especially in poorly-insulated residences and in rooms with significant exterior exposure [
7]. No prior study has leveraged the thermostat collected data to improve estimation of the MRT and the PMV. The approach posed, because it relies only upon smart WiFi thermostat information, has potential for rapid scalability.
Here, prior research of Alanezi et al. [
17], where wall, window, and ceiling R-values are estimated using a combination of smart WiFi thermostat, weather, energy consumption, residential building geometry, and occupancy data, was leveraged. With the exterior R-values, interior temperature, and known exterior temperature, the interior surface temperature of the envelope elements can be estimated from a steady-state heat transfer analysis, yielding a more accurate MRT, and therefore PMV assessment. With the PMV known, the thermostat setpoint can be reset if needed to achieve the desired PMV level. The posed approach requires no additional sensors other than those provided by a smart WiFi thermostat. Thus, thermal comfort control can be achieved at no extra cost.
Additionally, assuming the presence of a home automation system, where a resident could “set up” their home by defining the dimensions of each room and identifying the presence of exterior connected surfaces in each room, room level MRT, and PMV calculations are possible. Further, because a home automation system can know where the people in the home are located, a worst-case thermal comfort control condition can be established for the entire residence based upon where people are present. The thermostat setpoint can be adjusted in order to achieve this comfort condition.
The following describes the data leveraged for this research, presents the methodology employed to estimate the MRT using smart WiFi thermostat data, and describes the simulation used to assess the potential of minimum thermal comfort control in different types of residences to achieve energy savings. It then presents results from the cases considered in terms of the energy savings derived and the improvement of the MRT and thus the comfort estimation from the approach we employ. It also discusses the implications of the results. It concludes with a statement about future research required.
3. Methodology
3.1. Data Collection and Preprocessing
Data used for this study are mainly from 700+ university student residences (450 stand-alone detached residences, and the rest, apartment residences) in the Midwest USA. This data consists of historical smart WiFi thermostat readings (cooling/heating setpoint, indoor air temperature, and relative humidity, and cool/heat/fan status), monthly energy consumption, weather, and building geometry data. The historical weather data was obtained from NOAA’s Climate Data Online resource [
18].
All data was synched and merged, and then normalized (scaled from −1.0 to 1.0).
3.2. Estimating the MRT
Alanezi et al. [
17] developed and validated a method to automatically audit the energy effectiveness of any stand-alone residence using a combination of archived smart WiFi thermostats, weather, metered energy consumption, and building geometry data. Occupancy data has been shown to improve their evaluation. These data would be available to a WiFi thermostat manager providing service to a utility. A single model, valid for any stand-alone residence, can be developed by combining synched and merged data for all residences into a single dataset. The training data includes the most important HVAC energy characteristics for a residence, namely the wall insulation thickness, window type, ceiling insulation thickness, water heater fuel type and efficiency, and heating/cooling system efficiency. This data would be available within utility districts which have completed energy audits on many houses. Supervised-learning machine learning models (distributed random forest, global boosting, deep learning neural network) can be developed to accurately predict each individual energy characteristic based on a training set of residences. The models developed have been proven to be capable of predicting the R-values of the envelope components in other residences. This approach serves as the basis for developing an improved estimation of the MRT, as follows.
In order to estimate the MRT of a space, the interior temperature of all surfaces enclosing a space is needed. Non-exterior connected surfaces can be estimated to be equal in temperature to the room temperature, which is assumed to be adequately reflected by the measured smart WiFi thermostat temperature. The interior surfaces connected to exterior walls, ceiling, or basement/crawlspace are estimated from knowledge of the real-time room and exterior temperatures and envelope R-values. These temperatures are obtained using a steady-state heat transfer analysis. Application of an energy balance on each exterior connected surface under this assumption, and assuming that the solar gain on any of the surfaces is small, requires that the heat flow through the envelope component be equal to the heat flow from the interior surface of the envelope to the indoor air, as given by Equation (1) and shown in
Figure 1.
where
Rho = convective thermal resistance on exterior surface, typically 0.03 m2—C°/W.
Rhi = convective thermal resistance on interior surface, typically 0.12 m2—C°/W.
Re = conductive thermal resistance through envelope component.
Te,in = interior surface temperature of envelope component.
Rearranging yields the following interior surface temperature of wall, given by
With all surface area information available through a home automation setup by the resident, and with estimates of the exterior envelope component interior surface temperatures, the MRT can be calculated using an area weighted average given by Equation (3).
3.3. Applying Thermal Comfort Control to WiFi Thermostats
A feedback control scenario based upon Fanger’s
PMV equation [
6], shown in Equation (4) below, was used to control the thermal comfort to be set as the minimum thermal comfort range for cooling. At each sampled time, the
PMV was calculated based upon thermostat measurements (room temperature and humidity), and inferred thermostat measurement (MRT) and minimum thermal comfort values for other parameters in Fanger’s equation for the room air velocity, clothing level (
Clo), and metabolic rate (
MET).
Then the measured
PMV was compared to the desired
PMV and adjustments were made to the thermostat setpoint level if needed. The control logic was as follows. The thermostat setpoint value was increased/decreased by 1 degree if the
PMV value was above 0.5 (minimum cooling thermal comfort condition) and less than 0; otherwise, the setpoint temperature was maintained.
This same logic would apply to a heating situation, except instead, the PMV would be maintained between −0.5 and 0 for minimum thermal comfort.
3.4. Smart Home Automation Assistant to Define Actual Minimum Thermal Comfort in A Residence
This research also considers the idea that the minimum comfort within a residence depends upon where the residents are. For example, if a resident is in a room with a large number of windows and with exposure to two or three exterior connected surfaces, the MRT could be much closer to the outdoor temperature than were a resident or residents in a room with little or no exposure to exterior walls, windows or attic walls. Thus, the determination of the minimum thermal comfort condition in a house should take into account where the residents are within a residence.
In a smart home automation era, it is feasible to know where people are in the residence. All a resident would need to do is say “John is in the living room” or “Sarah is in the dining room” to enable the automation system to know where they are located. Moreover, we could readily imagine an app that helps residents “set-up” their houses. They could identify for each room the following: the room dimensions, which walls are exterior walls, if the room is exposed to the attic space or roof, the number and size of windows in the room, and if the room’s floor is exposed to an unheated/uncooled space beneath.
Moreover, residents could even say what they are doing in each room, whether they are sitting, sleeping, exercising, or other things. Thus it would be feasible to more accurately estimate the metabolic level (MET). Lastly, they could also identify what clothing they are wearing and if they have an open window or a floor or ceiling fan. Thus, the CLO and vair parameters could theoretically be estimated with greater accuracy.
It will thus be possible to estimate the MRT and PMV real-time in each room. Knowledge of where occupants are will enable estimation of a worst-case PMV for the residence. The thermostat setpoint for a single zoned residence could then be adjusted to maintain a minimum comfort PMV in the worst-case occupied zone.
3.5. Assessing the Energy Savings Impact of Minimum Thermal Comfort Control Via Simulation
In this section, we describe a dynamic data-based model used to evaluate the energy-savings impact of the thermal comfort control strategy described in
Section 3.3. The developed dynamic model leverages thermostat data for an individual residence, synched with simultaneous weather data. The thermostat data include human times, cool/heat/fan status, cooling/heating setpoint, indoor air temperature, and relative humidity, and outdoor weather conditions.
With the dynamic model developed for a residence, new setpoint targets based upon real-time PMV comfort assurance can be tested, and the resulting cooling (and heating) energy savings can be estimated.
The dynamic model was developed based on a nonlinear autoregressive network with exogenous inputs (NARX) neural network.
Figure 2 depicts this approach. The NARX was created in MATLAB 2019a, with 20 hidden neurons and the Levenberg–Marquardt as the training function.
Model validation was achieved by applying the model to data not used for the model training. The validation data inputs were outdoor temperature and humidity and interior thermostat setpoint data. The model was applied to predict indoor temperature and humidity. The predictions for these were compared to the measured values for those inputs in order to assess the efficacy of the developed model. R-squared and RMSE metrics were used to evaluate the quality of the validation.
5. Conclusions
Implementation of a thermal comfort control which relies on a smart WiFi thermostat alone has been demonstrated. In this approach, an improved means to estimate the MRT, based upon prior estimation of exterior wall and ceiling RSI values obtained from smart WiFi thermostat information, was posed. The modified MRT estimation was shown to be particularly valuable in poorly insulated residences, especially if a space has a significant exterior connection.
Additionally, we demonstrated the ability to leverage a dynamic machine learning-based predictive model of the residential temperature and humidity measured by a smart WiFi thermostat using historical thermostat and outdoor weather data to estimate savings with thermal comfort control. Such models are derivable for any smart WiFi-equipped residence. Thus, we have demonstrated the ability to estimate thermal comfort control savings in any residence. This information could be communicated to occupants to enable them to choose to control for comfort rather than temperature alone.
Lastly, through simulated implementation of thermal comfort control using the developed dynamic models in both high- and low-efficiency residences, we have shown potential cooling savings for these types of residences to be, respectively, in the order of 85% and 95%. These results show the promise of smart WiFi thermostats enable thermal comfort control for achieving large scale savings from cooling. This research also reveals the opportunity to leverage home automation systems to permit thermal comfort control based upon the room or rooms where people are present.
The limitation of this research is that these conclusions have been drawn via simulations leveraging developed dynamic models of internal temperature and humidity in residences in order to assess the impact of thermal comfort control using a smart WiFi thermostat controller. Future research is needed to experimentally validate the savings from thermal comfort control in a variety of residences. As well, future research should explore the potential for integrating this type of control into home automation systems to enable room by room estimations of thermal comfort.