Next Article in Journal
Enhancing the Rice Seedlings Growth Promotion Abilities of Azoarcus sp. CIB by Heterologous Expression of ACC Deaminase to Improve Performance of Plants Exposed to Cadmium Stress
Next Article in Special Issue
Evaluation of Recommended Water Sample Collection Methods and the Impact of Holding Time on Legionella Recovery and Variability from Healthcare Building Water Systems
Previous Article in Journal
Syngas as Electron Donor for Sulfate and Thiosulfate Reducing Haloalkaliphilic Microorganisms in a Gas-Lift Bioreactor
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Chlorine Disinfection of Legionella spp., L. pneumophila, and Acanthamoeba under Warm Water Premise Plumbing Conditions

1
Department of Civil and Environmental Engineering, Virginia Military Institute, Lexington, VA 24450, USA
2
Internal Medicine Residency Program, University of Virginia, Charlottesville, VA 22904, USA
3
Department of Environmental and Ecological Engineering, Department of Civil Engineering, Department of Materials Engineering, Department of Biomedical Engineering, Purdue University, West Lafayette, IN 47907, USA
4
Charles E. Via, Jr. Department of Civil and Environmental Engineering, Virginia Tech, Blacksburg, VA 24450, USA
*
Author to whom correspondence should be addressed.
Microorganisms 2020, 8(9), 1452; https://doi.org/10.3390/microorganisms8091452
Submission received: 22 August 2020 / Revised: 16 September 2020 / Accepted: 19 September 2020 / Published: 22 September 2020

Abstract

:
Premise plumbing conditions can contribute to low chlorine or chloramine disinfectant residuals and reactions that encourage opportunistic pathogen growth and create risk of Legionnaires’ Disease outbreaks. This bench-scale study investigated the growth of Legionella spp. and Acanthamoeba in direct contact with premise plumbing materials—glass-only control, cross-linked polyethylene (PEX) pipe, magnesium anode rods, iron pipe, iron oxide, pH 10, or a combination of factors. Simulated glass water heaters (SGWHs) were colonized by Legionella pneumophila and exposed to a sequence of 0, 0.1, 0.25, and 0.5 mg/L chlorine or chloramine, at two levels of total organic carbon (TOC), over 8 weeks. Legionella pneumophila thrived in the presence of the magnesium anode by itself and or combination with other factors. In most cases, 0.5 mg/L Cl2 caused a significant rapid reduction of L. pneumophila, Legionella spp., or total bacteria (16S rRNA) gene copy numbers, but at higher TOC (>1.0 mg C/L), a chlorine residual of 0.5 mg/L Cl2 was not effective. Notably, Acanthamoeba was not significantly reduced by the 0.5 mg/L chlorine dose.

1. Introduction

Legionella is the primary cause of waterborne disease outbreaks in the United States (USA), with more than 5000 cases of Legionnaires’ Disease (LD) reported annually and approximately 5000–45,000 unreported cases per year [1,2,3], costing nearly a half billion dollars in annual hospitalization costs in the United States [4]. Legionella pneumophila is identified as the causative agent in 90 percent (%) of LD, but other members of the genus also cause LD, even though their association is less commonly diagnosed [5]. Another opportunistic pathogen capable of growth in premise plumbing (OPPP) is Acanthamoeba, which can cause eye infection/meningitis, as well as acting as a host organism for Legionella proliferation [6,7,8,9]. While traditional LD risk is managed at the building-scale, the potential responsibility of water utilities to deliver at least some chlorine residual (≈0.5 mg/L) via the municipal distribution system has recently been gaining attention in the wake of a major LD outbreak that occurred in Flint, MI, in which case chlorine residuals were frequently absent [10,11,12]. Thus, there is need to complement existing research on supplemental disinfection in buildings by systematically assessing the effects of building point-of-entry chlorine levels on growth of OPPPs, such as Legionella and Acanthamoeba [7,13].
Free chlorine or chloramine (chlorine with ammonia) disinfectant residuals are traditionally applied with the intention of inactivating fecal contaminants, but a comprehensive understanding of the efficacy of such disinfectants for controlling OPPPs in the diverse downstream micro-environments characteristic of premise plumbing is emerging [14,15]. The U.S. Environmental Protection Agency’s (EPA’s) existing chlorine regulations attempt to balance risks from fecal pathogens and disinfection by-products by requiring that 95% of distributed water samples collected from representative monitoring sites in flushed water from mains have detectable (often >0.1 or 0.2 mg/L) residual chlorine [16]. The World Health Organization has suggested a requirement for higher levels of disinfectant at the building point of entry, predicting that higher disinfectant residual thresholds of 0.3–0.5 mg/L would be needed to limit Legionella spp. growth [17].
A key challenge is that, as distributed water travels through mains, service lines, and premise plumbing, the chlorine or chloramine disinfectant residual is often lost or otherwise rendered ineffective due to a range of biological and chemical reactions [7,10,18,19,20,21]. Deficiencies within the premise plumbing system have been associated with 85% of LD outbreaks between 2000–2014, including a lack of adequate disinfectant residual (70%) and water storage in the optimal temperature range for Legionella growth (52%) [1]. These findings are consistent with other LD outbreak investigations, in which problems were traced to stagnant water tanks with disinfectant residuals levels <0.05 mg/L [22,23,24] or lack of consistent chlorine residual throughout the distribution system [10,11,12]. The losses of chlorine within premise plumbing are of particular interest, because copper and iron pipe corrosion and nitrification can remove disinfectant [25,26,27] and allow Legionella to thrive [28,29,30,31]. If disinfection is disrupted or reduced, Legionella and other OPPPs can return to pre-disinfection levels within five days [32] or re-establish from a viable but nonculturable (VBNC) state [33].
While it is widely accepted that increased water temperature accelerates chlorine and chloramine decay rates in water mains [26,34,35,36,37,38], relatively little is known about how temperature influences chlorine decay in the warm water characteristic of building plumbing systems [26,28,39]. Storage >30 °C is predicted to increase rates of chlorine removal [40,41] and one study of a model plumbing system determined that increasing the temperature of water from 25 °C to 43 °C roughly doubled the dose of chlorine required to maintain a residual of 4 mg/L as Cl2 [42]. Additionally, disinfection is understood to be more effective when the residual is maintained with regular additions of chlorine, compared to a single large dose [42].
Higher organic carbon content also increases the rate of chlorine decay in distributed cold bulk water [34,43,44,45] and can serve as a nutrient source for microbial re-growth in plumbing [46,47,48,49,50,51]. For instance, when Flint, MI switched to distributing treated local river water with higher organic carbon, the chlorine demand required to maintain residuals was much higher, which in turn caused exceedances of trihalomethane disinfection by-product regulations [10,52]. Legionella has been shown to sometimes correlate with organic carbon in water, but it can also thrive when the carbon content is low [51,53,54,55,56,57].
The role of pH is also expected to be important and complex, given that lower pH tends to increase the disinfection effectiveness of free chlorine, even as it tends to hasten the rate of chlorine disappearance [58,59]. pH may also have a direct effect on Legionella, which is known to be generally acid-tolerant (at a pH of 3 and 5) but loses culturability above pH 11 [60]. A study examining a pure culture of L. pneumophila observed growth occurring up to a pH of 9.5, with a loss of culturability at pH 10.5 [61], whereas a field study correlated pH with L. pneumophila in a cooling tower, with a decrease to less than 1 colony-forming unit (CFU)/mL observed at pH > 8.2 [62].
Here we systematically assessed the effects of a disinfectant residual on representative OPPPs, including Legionella spp., L. pneumophila, and Acanthamoeba, while under possible protection of several premise plumbing conditions known to cause chlorine loss or alter pH. Specifically, it was hypothesized that warm temperatures, higher pH, and higher organic carbon concentrations would tend to increase OPPP and total bacterial gene copies, due to decreased effectiveness of chlorine or chloramine disinfectant residuals. The tests were conducted in replicated simulated glass water heaters (SGWHs), each with premise plumbing materials/conditions of interest (Figure 1), including pH 10, iron, iron oxide, magnesium, and a combination of magnesium and iron, with sequential increase in chlorine or chloramine disinfectant dose. A temperature of 37 °C was selected to represent “worst case” portions of warm water plumbing at risk of OPPP growth, including mixing valves and convectively-mixed distal taps [63]. The goal of this study was to examine chlorine stability and disinfection effectiveness, in the warmer temperatures and conditions found in the presence of a wide range of premise plumbing conditions.

2. Materials and Methods

2.1. Chlorine Dosing and Residual Experiments

Chlorine demand tests were performed to determine the dose of chlorine needed to achieve the desired initial disinfectant residual in the influent water to the SGWHs. These tests were carried out at room temperature (21 °C) in acid-washed, baked (at 550 °C) 500 mL glass beakers containing water that was homogenized using magnetic stirrers. Chlorine was titrated from a stock sodium hypochlorite solution until a stable free chlorine residual of 0.5 mg/L was achieved. Chlorine concentrations were determined by taking ten milliliter aliquots from the chlorinated samples to determine free or total chlorine using a HACH DR 5700 (HACH, Loveland, CO, USA) via standard method 4500-Cl G.
Subsequent chlorine decay at 37 °C in the SGWHs with “glass-only” premise plumbing conditions (Cl control, chloramine, pH 10) was tracked by measuring the free and total chlorine concentration in the SGWH at 5 min, 1 h, and 24 h, via ten milliliter aliquots pipetted from the center of homogenized SGWHs. Chlorine demand or chlorine loss was calculated as the difference between chlorine concentration added to the SGWH and the chlorine concentration measured in the SGWH. Because these chlorine measurements were taken from unfiltered samples using a colorimetric method, chlorine measurements in SGWHs containing iron plumbing materials were inaccurate due to interference from iron particles with the measurements. In these conditions, the routine chlorine measurement could be inflated by as much as 0.50 mg/L Cl2, depending on the level of mixing that occurred prior to sampling of the SGWH.

2.2. Simulated Glass Water Heaters (SGWHs)

SGWHs were used in this experiment to test a range of materials and ecological niches of interest in premise plumbing (Table 1). The SGWHs were established in 2009 [49,51] and operated for just over five years prior to this experiment [54,57] establishing complex mature biofilms in each SGWH. L. pneumophila had been established in the SGWHs for three years prior to the start of this experiment. For each of the nine conditions (rows in Table 1) stored at 37 °C, six SGWHs were maintained—triplicate low total organic carbon (TOC) SGWHs and triplicate high TOC SGWHs (Table 1). In order to facilitate establishment of a similar microbial baseline for the experiment in week 0, the effluents from each of the low TOC, high TOC, or pH 10 SGWHs were combined and one milliliter of the combination was used to cross-inoculate each group of SGWHs (low TOC, high TOC, and pH 10) prior to the subsequent water change. Standard water changes (weeks 1–9) were completed three times a week with 80% of the water volume (100 mL) being exchanged for new influent water. To simulate the quiescent conditions typical at the bottom of electric water heaters, water changes were conducted by gently pouring the effluent from the top 80% of the SGWHs, with only slight incidental stirring of the SGWHs during decanting and transport from the incubator to a biosafety cabinet. The influent was completely mixed prior to its addition to the SGWH to ensure complete mixing and even distribution of the disinfectant. A series of control SGWHs with only glass beads were maintained that included no chlorine (No Cl), no chlorine pH 10 (pH 10), free chlorine control (Cl Control), and chloramine control (ClNH2) (Table 1).

2.3. Water Preparation Method, Sequential Disinfection Addition, and Sampling Schedule

SGWH water changes were made with modified Blacksburg tap water (Figure 2). Tap water was collected after the faucet had been flushed at full flow for ten minutes to minimize the influence of building premise plumbing materials. The water was breakpoint chlorinated and then pasteurized at 90 °C for ten minutes which also removed chlorine. Once cooled, the low TOC water was created by recirculation through a biologically-active granular-activated carbon (GAC) filter for at least 12 h. Both low (average 0.52 mg/L C) and high (average 1.0 mg/L C) TOC water was then filtered through a 0.45 μm polyvinylidene fluoride (PVDF) filter to remove biomass and particulate matter, and adjusted to targets of either pH 7.5 ± 0.1 (using 1 M HCl) or a pH of 10 ± 0.1 (using 1 M NaOH).
In the previous five years of exposure to a synthesized oligotrophic tap water or a breakpoint chlorinated local tap water, the SGWHs had never been exposed to a chlorine residual [51,57,63]. The chlorine concentration in the influent water was increased in sequence from 0 to 0.1 mg/L (week 3) to 0.25 mg/L Cl2 (week 5) to 0.5 mg/L Cl2 (week 7) to examine dosed versus actual residual disinfectant. To create the chloramine, ammonium sulfate was added to the designated SGWHs at 1 mg/L free NH3-N and well mixed just prior to the addition of the chlorinated influent water to the SGWHs.

2.4. Sampling Methods

Effluent samples for microbial analysis were collected from the 100 mL water removed from the SGWHs during a water change every other week (weeks 1, 3, 5, 7, 9). Samples for microbiological analysis presented here were collected in week 1 (initial data with no chlorine addition) and week 9 (final) after the two-week acclimation period at the 0.5 mg/L Cl2 dose. The microbes were captured on sterile 47 mm diameter, 0.22 μm pore size, mixed-cellulose ester filters (Millipore, Billerica, MA, USA) using vacuum filtration, torn and then consistently folded using sterile tweezers, and placed into a FastDNA® SPIN Kit Lysing Matrix A tube (MP Biomedicals, Solon, OH, USA) to extract the DNA according to the manufacturer’s instructions. The extracted sample was stored in screw-cap tubes at −20 °C until analysis.
Quantitative polymerase chain reaction (qPCR) was performed on the samples to quantify the genes specific to L. pneumophila, Acanthamoeba, Legionella spp., and total bacterial 16S rRNA genes. All qPCR assays used to quantify these organisms were described and validated previously [64]. qPCR was run on Bio-Rad CFX96™ real time system (Bio-Rad, Hercules, CA, USA). Each sample was run in triplicate with a no template control and calibration curve on each plate. The calibration curve consisted of at least six standard concentration points for each organism. Culturing of Legionella was completed using a 0.1 mL aliquot of the SGWH effluent. The aliquot was heated to 50 °C and spread directly onto buffered charcoal yeast extract (BCYE) agar (Remel Inc., Shawnee Mission, KS, USA) containing l-cysteine. Samples suspected of containing L. pneumophila were also spread directly onto BCYE plates without l-cysteine. The culturing results were used to verify that live Legionella was present in the SGWHs but were not used in a quantitative manner.
Metals (copper, iron, zinc, magnesium) in the SGWHs were analyzed via inductively-coupled plasma mass spectrometry (ICP-MS). Ten milliliter samples from the SGWHs were collected and transferred to sterile culture tubes. The samples were acidified with 2% nitric acid to the test tube and left at room temperature 24 h prior to analysis. Standards, positive controls, and negative controls were run alongside the samples to provided appropriate quality control and assurance.
TOC was measured using a Sievers 5310 Laboratory TOC-MS Analyzer (Suez Water Technologies, Trevose, PA, USA). Samples were pooled by condition combining ten milliliter volumes from each triplicate SGWH. The combined sample was acidified using 85% phosphoric acid. Nitrogen gas was bubbled through each sample at 10 pounds per square inch (psi) for three minutes before analysis.

2.5. Statistical Analyses

R version 3.4.3 was used to conduct all statistical analyses. The distribution of the chlorine decay data was normally distributed (based on the results of a Shapiro test of the residuals as well as the QQ plot), thus parametric tests were applied to calculate the linear regressions. The distribution of the qPCR, metals, and carbon data were not normally distributed even when a logarithmic transformation was applied, so non-parametric tests were used for analyses of these data. Spearman’s correlation coefficients were determined for relationships between the average (of triplicate SGWHs) of each qPCR gene target, magnesium, copper, zinc, iron, and effluent carbon. An alpha value of 0.05 was used to determine the significance of the p values comparing the correlation coefficients. One-sided paired Wilcox rank sum tests were used to determine significant differences between gene targets, magnesium, and iron with a 0 mg/L chlorine dose or a 0.5 mg/L chlorine dose.

3. Results

3.1. Instantaneous Residual Demand and Decay Without Premise Plumbing Materials at Room Temperature

Chlorine demand was quantified in four influent waters with two levels of pH (low = pH 7.5 and high = pH 10) and two levels of organic carbon (low = 0.52 mg/L and high = 1.00 mg/L). An illustrative Cl2 dose response curve was developed (Figure 3) for each influent water, by plotting the chlorine residual as a function of total chlorine dosed to each SGWH and determining the residual yield (mg Cl2 residual per milligram total chlorine dosed). At pH 7.5, the low TOC condition had a yield of 0.99 mg/L residual per 1 mg/L Cl2 dosed, whereas the high TOC condition only had a yield of 0.67, confirming the expected role of higher TOC in creating chlorine demand at this pH. At pH 10, the yield in the low TOC condition decreased to 0.75. For the higher TOC water at pH 10, yield increased slightly to 0.72. This information was used to achieve the target Cl2 dose of 0.1, 0.25, or 0.5 mg/L. In one case, the water was converted to a chloramine residual by adding ammonia.

3.2. Residual Decay Without Premise Plumbing Materials at 37 °C

The rate of chlorine decay was monitored in SGWHs without any premise plumbing materials. At pH 10 and low TOC, 90% and 14% of the initial residual remained at 1 and 24 h, respectively (Table 2). However, in the comparable condition at pH 10 and high TOC, only 3% remained by the 24 h time period. In all tested low TOC conditions, the chlorine decay was more consistent, with decay percentages ranging from 86–93%. Contrary to expectations, the high TOC condition had the most residual chlorine at 24 h, with 42% of the residual remaining (Table 2). After 24 h of contact time, the chloramine conditions actually had lower total chlorine residuals compared to the conditions with free chlorine, for both high and low TOC. Based on experience at room temperature, chloramine is expected to be more stable than free chlorine, in the absence of nitrification [65]. Thus, these experiments in warm water importantly demonstrated that disinfectant residual behavior can be contrary to prior experience in cold water.

3.3. Effects of Premise Plumbing Materials and Conditions at Warm Temperatures

3.3.1. Accounting for Background Variation in the No Chlorine Control Condition

Two control conditions, without Cl2 added, were established to determine the possible background effects of time and water changes on the microbial targets in the SGWHs. Only a slight decrease in total bacterial gene copies (i.e., 6% in low TOC, 10% in high TOC) was observed over the course of the experiment in these two controls. Similar slight decreases in gene copy numbers were observed for L. pneumophila, Legionella spp., and Acanthamoeba) (Figure 4). The exceptional case was Acanthamoeba in the high TOC No Cl condition, which decreased by about 2 logarithms (logs) over the duration of the experiment (Figure 4). We assumed that any changes in gene copies greater than these control replicates could be attributed to the addition of a disinfectant, rather than temporal variation in the SGWHs.

3.3.2. Chloramine versus Chlorine in the SGWHs

A reduction in gene copies exceeding that of the No Chlorine control was observed in at least one replicate SGWH for each target organism in the low TOC conditions (Figure 4). In the chloramine conditions, there was no indication of any disinfection of the target organisms. To the contrary, gene copy numbers (with the exception of Acanthamoeba) actually increased by 2 logs (Figure 4). The lack of disinfection with chloramine is not surprising, given the lack of residual (Table 2). Nonetheless, at a low TOC concentration, chlorine was more effective at decreasing L. pneumophila gene copies than chloramine, which is consistent with the relative persistence patterns of the disinfectant residuals (Table 2).
In the high TOC conditions, the addition of chlorine did not have an effect on L. pneumophila or Legionella compared to the control conditions without disinfectant, but it did decrease Acanthamoeba and total bacterial gene copies by 3–4 logs. Chloramine also decreased L. pneumophila in the high TOC SGWHs, but this promising effect was not observed for the other organisms (Figure 4). Thus, it seems that, at higher TOC, chloramine was more effective than chlorine in preventing L. pneumophila growth, even though it did not persist as long in this warm water condition in the control glass SGWHs (Table 2).

3.3.3. Effect of pH in the SGWHs Without Plumbing Materials

In the low TOC SGWHs where the pH was increased to 10, the target organism gene copies decreased by 97–100% (Figure 4). This result aligns well with the above-noted and counterintuitive higher persistence of chlorine at 37 °C and pH 10 (Table 2). The pH 10 high TOC conditions showed little to no change in Legionella spp. and total bacterial gene copies but did exhibit a 4-log (100%) decrease in Acanthamoeba. In fact, the L. pneumophila concentration in the high TOC pH 10 condition actually increased in two out of the three SGWHs when chlorine was added (Figure 4), suggesting that higher pH and higher TOC condition might be a selector for L. pneumophila versus Legionella spp. This result was surprising in light of the results of the chlorine decay experiments (Table 2, Figure 3), but indicates that the high pH and high TOC condition might be an ideal scenario for L. pneumophila to circumvent effects of disinfection, possibly due to the relative ineffectiveness of OCl- ion favored at high pH versus the more effective HOCl favored at lower pH.

3.3.4. Plumbing Material Effects on Target Microorganisms

Total Bacteria: When considering plumbing modifications to the SGWHs, effect of chlorination varied among the target organisms, as was also the case for the glass-only controls (Figure 4). For total bacterial gene copies, the premise plumbing materials tended to reduce the effect of the chlorine dose, with only slight decreases in gene copy concentration in some SGWHs (all less than 20% average decreases in concentration). In other words, results confirm that virtually all of the premise plumbing materials tended to protect total bacteria from chlorine when compared to the control.
The PEX high TOC condition was least protective of total bacteria from disinfection in this test, with a decrease of 19% versus the 6% in the control. Chloramine was completely ineffective in the situation with a combination of plumbing materials (chloramine combo), such that total bacteria actually increased 12–14% at both levels of TOC, perhaps due to the addition of ammonia as a nitrogen source. The effect of plumbing material was dominant over the effect of TOC, since the level of TOC did not have an apparent effect on the disinfection of total bacteria, possibly due to the presence of disinfectant-resistant bacteria in the mature biofilms in each SGWH.
L. pneumophila: The effect of chlorine disinfection and plumbing conditions on L. pneumophila gene copies was a strong function of TOC level. The high TOC levels sporadically hindered disinfection in the three iron oxide replicates (1%, 10%, and 100% decreases) and the chloramine combo condition (greater than 50% increase in 2/3 SGWHs) (Figure 4). Efficacy of disinfection also varied in the iron and magnesium rod conditions, with one SGWH in the high TOC condition never having a detectable concentration of L. pneumophila, the second SGWH having increasing levels of L. pneumophila, and the third SGWH having decreasing L. pneumophila gene copies. Neither the high nor low TOC iron condition indicated significant disinfection of L. pneumophila, suggesting that iron was almost completely protective (Figure 4). In contrast, the PEX conditions showed decreases in gene copy concentration of 49% in the high TOC and 28% in the low TOC conditions, confirming that, unlike iron, PEX did not interfere with chlorine disinfection. This is expected because iron metal has a higher chlorine demand and PEX has a low chlorine demand.
Legionella spp.: Legionella spp. concentrations decreased with time and increasing disinfectant dose in all of the low TOC plumbing conditions, regardless of the material present, but did not decrease in all the high TOC conditions. TOC had a negative effect on disinfection in the chloramine combo condition, where Legionella gene copy numbers actually increased by at least 9% in each high TOC replicate (Figure 4). This result was notably consistent, especially compared to the variable changes in L. pneumophila concentration under the same conditions, demonstrating the need for future studies to examine more closely the effects of disinfection and plumbing conditions on specific species and serogroups of Legionella, particularly the most virulent forms. Legionella spp. decreased by an average of 63% in all other high TOC conditions, compared to an average decrease of 77% in the low TOC conditions.
Acanthamoeba: Acanthamoeba resistance to chlorine varied, as gene copy numbers remained near the quantification limit. The gene copy numbers in magnesium and iron SGWHs dropped below the quantification limit after disinfection, regardless of TOC concentration. Conversely, in the iron oxide conditions the Acanthamoeba concentrations actually increased in two out of the three SGWHs (Figure 4). The gene copy numbers increased in the PEX condition at a high TOC concentration but not in the SGWHs at the low TOC concentration.

3.4. Correlation of Target Microbes with Each Other and with Chemical Measurements

Total bacterial, L. pneumophila, and Legionella spp. gene copies were significantly and positively correlated with each other, but the Acanthamoeba gene copies were only correlated with total bacteria (p = 0.03) (Figure 5). Iron concentration was only significantly positively correlated with magnesium concentration (p = 0.007) (Figure 5), and decreased significantly with chlorine concentration (Wilcox rank sum, p = 0.02, n0 mg/L Cl = n0.5 mg/L = 18). Magnesium concentration served as a surrogate measure of anode rod corrosion and was positively correlated with total bacteria (p = 4.0 × 10−4), Legionella (p = 3.7 × 10−5), and L. pneumophila (p = 5.0 × 10−3). The addition of chlorine also decreased the magnesium released from the water heater anode (Wilcox rank sum, p = 0.001, n0 mg/L = n0.5 mg/L = 18). The addition of chlorine to the SGWHs significantly reduced total bacteria (Wilcox rank sum, p = 0.002), Legionella (Wilcox rank sum, p = 1.37 × 10−5, n0 mg/L = n0.5 mg/L = 18), and L. pneumophila (Wilcox rank sum, p = 0.04, n0 mg/L = n0.5 mg/L = 18), but not Acanthamoeba (Wilcox rank sum, p = 0.08, n0 mg/L = n0.5 mg/L = 18).

4. Discussion

In order to better design plumbing systems to reduce risk of Legionella proliferation in building systems and to consider the important role of the water utility in delivering a residual to buildings, we examined the decay of chlorine at room temperature and 37 °C, and the disinfection effects of 0.5 mg/L as Cl2 residual concentration chlorine at high and low TOC concentrations and in the presence of various premise plumbing factors hypothesized to protect pathogens from disinfectant [17].
The loss of chlorine as water flows through a distribution system and premise plumbing contributes to the regrowth of pathogens, including L. pneumophila. In this study, we find that this problem is exacerbated in warm water, for which relatively little research has been done to determine decay rates. When chlorine was applied to a low TOC water at a warm temperature (37 °C), only 11% of the initial residual remained after 24 h without any plumbing or biofilm interactions (Table 2). Chlorine decayed more rapidly at warm temperature in glass containers [7,37,38,42] and had little disinfecting effect in the presence of iron [10,26,45], a magnesium anode, high TOC [10,11,52], or the combination of all three. The findings here are consistent with field studies where chlorine was ineffective in the presence of similar factors. Depletion of disinfectant by iron and TOC was consistent with expectation, but the increased L. pneumophila gene copy numbers in the presence of magnesium was an unexpected finding that should be examined further as a potential factor contributing to Legionella proliferation in building plumbing. For example, increased Mg in water may be associated with increased release of H2 as an electron donor enable fixation of organic carbon in the system via autotrophy, or Mg may simply act by elevating pH.
Low levels of chlorine (less than 0.5 mg/L Cl2) measured in distribution systems are sometimes reported to have no significant effect on L. pneumophila concentration. The results of this experiment (Figure 5) demonstrate that, although the effect of chlorine on bacteria and Legionella spp. is stronger than its effect on L. pneumophila, a significant negative correlation between L. pneumophila and this low dose of chlorine was still evident even after only 2 weeks at the 0.5 mg/L dose. Although drops in L. pneumophila concentration were observed in some of the SGWHs at a chlorine concentration of 0.5 mg/L Cl2, this effect was not consistent among triplicates nor between the plumbing conditions. This sporadic efficacy of the disinfectant residual could be a result of low concentration, but also might be due to a rapid loss of the residual in warm water and its consumption in reactions with the plumbing materials leaving the system vulnerable to growth in a majority of the 48 h stagnation events [32].
Although iron is known to be a required nutrient for Legionella [66,67], iron concentration was not significantly correlated with Legionella nor L. pneumophila. However, prior field surveys of Legionella in potable hot water systems identified increased Legionella growth with increased iron [68,69]. In addition to direct nutritional requirements, iron has a strong effect of removing chlorine disinfectant due to corrosion [10,70], while the resulting rusts can end up in water heaters and further protect biofilms. Neither chloramine nor chlorine were effective disinfectants for Legionella or L. pneumophila in the conditions with iron (Figure 4).
The lower extent of L. pneumophila and Legionella gene copy number decreases in high versus low TOC conditions observed in this experiment demonstrate that higher TOC waters may be more difficult to disinfect. However, further investigation is needed to determine if the influence of TOC is primarily due to its role as a microbial growth substrate or removal of disinfectant [31,48,71]. Note that Legionella can only use amino acids as a growth substrate, thus, effects of TOC would be indirect, by stimulating growth of complex heterotrophic biofilms and the free-living amoebae that feed on them and serve as hosts for Legionella amplification. Successful limitation of the growth of L. pneumophila has been indicated in unchlorinated distribution systems with an assimilable organic carbon (AOC) concentration as low as 5 μg/L, whereas L. pneumophila has been detected to be present in systems with greater than 10 μg/L AOC [72]. Plastic plumbing components have also been shown to increase the AOC and TOC content of drinking water [49,50], providing a possible explanation for less effective reduction of L. pneumophila in the low TOC SGWHs containing PEX. However, other experiments have indicated that higher TOC concentration in a bench-scale cold drinking water distribution system resulted in more rapid decay of the chloramine residual [45] and that chlorinated systems contained even higher AOC than chloramine systems [49]. Thus, there is a need for further studies on the mechanisms by which organic carbon in warm water plumbing systems affect L. pneumophila, by increasing microbial growth or by degrading the disinfectant.
In regard to metal components of plumbing systems, Legionella was significantly, positively correlated with magnesium in the water that was derived from anode rod corrosion. Magnesium ions might have a direct positive effect on Legionella. In a study conducted in Pittsburg, there was no correlation between Legionella positivity and magnesium concentration [73], whereas another study determined that low concentrations of magnesium (up to 43 mg/L) in culture media consistently enhanced growth [74]. Previous studies using these SGWHs measured an increase in pH in the conditions containing magnesium (both low and high TOC magnesium and chloramine combo conditions) from 7.5 in the influent to an average of 8.5–9.5 in the effluent of the SGWHs [49]. It is possible that this high pH at the anode surface, along with H2 gas released during anode rod corrosion, helped encourage the sustained Legionella and L. pneumophila concentrations in these two SGWH conditions. H2 gas is an energetically-favorable electron donor and could have stimulated organic carbon fixation and biofilm formation by autotrophic organisms, in turn providing an environment favorable to Legionella.
Even though monochloramine is considered to generally be more persistent than chlorine [36,39], this is based on experiences in cold water mains and was not found to translate to the warm water SGWHs with plumbing deficiencies. Monochloramine at a concentration of 0.8 mg/L Cl2 was more effective against L. pneumophila than chlorine (residual of 1 mg/L Cl2 after one contact hour) in a prior pure culture experiment with up to sixty minutes of exposure at 30 °C [36]. Previous research in our laboratory has shown that chlorine is more effective than chloramine in reducing concentrations of Legionella and Acanthamoeba in simulated drinking water distribution systems that also had high rates of chloramine decay due to nitrification [75]. The results from this experiment at higher temperature show that chlorine is more effective at disinfecting Legionella, while raising additional questions given the fact that chloramine apparently enhanced Acanthamoeba growth in this study. Thus, the assumption that chloramine is more effective than chlorine for Legionella control in premise plumbing systems needs to be carefully re-examined, particularly under warm water conditions with various deficiencies at play.

5. Conclusions

This study highlights the complexities influencing the efficacy of Legionella disinfection in premise plumbing system. Chlorine decay is altered by changes in temperature (21 °C to 37 °C), increases in organic carbon, or extreme increases in pH (pH 10). Changes in pH, temperature, carbon concentration, and disinfectant type all have an effect on the efficacy of the disinfectant on Legionella spp., L. pneumophila, and Acanthamoeba. The presence of a magnesium anode had the greatest effect on L. pneumophila when TOC was at 1 mg/L C. The chloramine residual was less effective than chlorine at reducing total bacteria, Acanthamoeba, and Legionella spp. in low and high TOC conditions and least effective at reducing L. pneumophila when combined with plumbing materials in the SGWH chloramine combo condition. Disinfection techniques, which are largely developed under the scenario of cold or room temperature water in water mains, must be re-examined in the context of potable water entering the warm or hot water, biofilm-laden environment of premise plumbing.

Author Contributions

Conceptualization, R.L.M., C.R.P., A.M., K.W., M.A.E., and A.P.; methodology, R.L.M., K.H., C.R.P., M.E., and A.P.; validation, R.L.M. and K.H..; formal analysis, R.M.; investigation, R.L.M. and K.H..; resources, R.L.M. and C.R.P.; data curation, R.L.M.; writing—original draft preparation, R.M.; writing—review and editing, R.L.M., K.H., A.M., K.W., M.A.E., and A.P.; visualization, R.L.M.; supervision, M.A.E. and A.P.; project administration, M.A.E. and A.P..; funding acquisition, M.A.E. All authors have read and agreed to the published version of the manuscript.

Funding

This material is based on work supported by the National Science Foundation under grant number 1336650 and the Alfred P. Sloan Foundation Microbiology of the Built Environment Program, as well as the Water Research Foundation Project 4251.

Acknowledgments

We would like to thank the National Science Foundation for their support of this project, as well as Jeffrey Parks, Kim Hughes, and Christine Pankow for their technical expertise and laboratory assistance. Any opinions, findings, and conclusions or recommendations expressed in this material are those of the author(s) and do not necessarily reflect the views of the National Science Foundation.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Garrison, L.E.; Kunz, J.M.; Cooley, L.A.; Moore, M.R.; Lucas, C.; Schrag, S.; Sarisky, J.; Whitney, C.G. Vital Signs: Deficiencies in Environmental Control Identified in Outbreaks of Legionnaires’ Disease—North America, 2000–2014. Morb. Mortal. Wkly. Rep. 2016, 16, 3049–3058. [Google Scholar]
  2. OSHA. Legionnaires’ Disease: Facts and Frequently Asked Questions. Available online: https://www.osha.gov/dts/osta/otm/legionnaires/faq.html (accessed on 14 January 2020).
  3. CDC. Legionella Fast Facts. Available online: https://www.cdc.gov/legionella/fastfacts.html (accessed on 21 September 2020).
  4. Collier, S.A.; Stockman, L.J.; Hicks, L.A.; Garrison, L.E.; Zhou, F.J.; Beach, M.J. Direct healthcare costs of selected diseases primarily or partially transmitted by water. Epidemiol. Infect. 2012, 140, 2003–2013. [Google Scholar] [CrossRef] [Green Version]
  5. Vaccaro, L.; Izquierdo, F.; Magnet, A.; Hurtado, C.; Salinas, M.A.; Gomes, T.S.; Angulo, S.; Salso, S.; Pelaez, J.; Tejeda, M.I.; et al. First Case of Legionnaire’s Disease Caused by Legionella anisa in Spain and the Limitations on the Diagnosis of Legionella non-pneumophila Infections. PLoS ONE 2016, 11, e0159726. [Google Scholar] [CrossRef]
  6. Fields, B.S.; Sanden, G.N.; Barbaree, J.M.; Morrill, W.E.; Wadowsky, R.M.; White, E.H.; Feeley, J.C. Intracellular multiplication ofLegionella pneumophila in amoebae isolated from hospital hot water tanks. Curr. Microbiol. 1989, 18, 131–137. [Google Scholar] [CrossRef]
  7. National Academies of Sciences, Engineering, and Medicine. Management of Legionella in Water Systems; The National Academies Press: Washington, DC, USA, 2019; p. 304. [Google Scholar] [CrossRef]
  8. Hsu, B.-M. Surveillance and Evaluation of the Infection Risk of Free-Living Amoebae—Acanthamoeba in Aquatic Environments. Int. J. Environ. Sci. Dev. 2016, 7, 445–448. [Google Scholar] [CrossRef] [Green Version]
  9. Hsu, B.-M.; Huang, C.-C.; Chen, J.-S.; Chen, N.-H.; Huang, J.-T. Comparison of potentially pathogenic free-living amoeba hosts by Legionella spp. in substrate-associated biofilms and floating biofilms from spring environments. Water Res. 2011, 45, 5171–5183. [Google Scholar] [CrossRef] [PubMed]
  10. Rhoads, W.J.; Garner, E.; Ji, P.; Zhu, N.; Parks, J.; Schwake, D.O.; Pruden, A.; Edwards, M.A. Distribution System Operational Deficiencies Coincide with Reported Legionnaires’ Disease Clusters in Flint, Michigan. Environ. Sci. Technol. 2017, 51, 11986–11995. [Google Scholar] [CrossRef]
  11. Zahran, S.; McElmurry, S.P.; Kilgore, P.E.; Mushinski, D.; Press, J.; Love, N.G.; Sadler, R.C.; Swanson, M.S. Assessment of the Legionnaires’ disease outbreak in Flint, Michigan. Proc. Natl. Acad. Sci. USA 2018, 115, E1730–E1739. [Google Scholar] [CrossRef] [Green Version]
  12. Schwake, D.O.; Garner, E.; Strom, O.R.; Pruden, A.; Edwards, M.A. Legionella DNA Markers in Tap Water Coincident with a Spike in Legionnaires’ Disease in Flint, MI. Environ. Sci. Technol. Lett. 2016. [Google Scholar] [CrossRef] [Green Version]
  13. EPA. Draft-Technologies for Legionella Control: Scientific Literature Reviewed; EPA Office of Water: Washington, DC, USA, 2016. [Google Scholar]
  14. Falkinham, J.O.; Pruden, A.; Edwards, M. Opportunistic Premise Plumbing Pathogens: Increasingly Important Pathogens in Drinking Water. Pathogens 2015, 4, 373. [Google Scholar] [CrossRef] [Green Version]
  15. Schoenen, D. Role of disinfection in suppressing the spread of pathogens with drinking water: Possibilities and limitations. Water Res. 2002, 36, 3874–3888. [Google Scholar] [CrossRef]
  16. Wahman, D.G.; Pressman, J.G. Distribution System Residuals—Is “Detectable” Still Acceptable for Chloramines? J. Awwa 2015, 107, 53–63. [Google Scholar] [CrossRef]
  17. WHO. Legionella and the Prevention of Legionellosis; WHO: Geneva, Switzerland, 2007. [Google Scholar]
  18. Lehtola, M.J.; Lehtola, M.J.; Miettinen, I.T.; Lampola, T.; Hirvonen, A. Pipeline materials modify the effectiveness of disinfectants in drinking water distribution systems. Water Res. 2005, 39, 1962–1971. [Google Scholar] [CrossRef]
  19. Lehtola, M.J.; Miettinen, I.T.; Keinänen, M.M.; Kekki, T.K.; Laine, O.; Hirvonen, A.; Vartiainen, T.; Martikainen, P.J. Microbiology, chemistry and biofilm development in a pilot drinking water distribution system with copper and plastic pipes. Water Res. 2004, 38, 3769–3779. [Google Scholar] [CrossRef] [PubMed]
  20. Clark, R.M. Chlorine fate and transport in drinking water distribution systems: Results from experimental and modeling studies. Front. Earth Sci. 2011, 5, 334–340. [Google Scholar] [CrossRef]
  21. Rhoads, W.J.; Pruden, A.; Edwards, M.K. Interactive Effects of Corrosion, Copper, and Chloramines on Legionella and Mycobacteria in Hot Water Plumbing. Environ. Sci. Technol. 2017, 51, 7065–7075. [Google Scholar] [CrossRef] [PubMed]
  22. Cohn, P.D.; Gleason, J.A.; Rudowski, E.; Tsai, S.M.; Genese, C.A.; Fagliano, J.A. Community outbreak of legionellosis and an environmental investigation into a community water system. Epidemiol. Infect. 2015, 143, 1322–1331. [Google Scholar] [CrossRef] [Green Version]
  23. Rodríguez-Martínez, S.; Rodriguez-Martinez, S.; Sharaby, Y.; Pecellin, M.; Brettar, I. Spatial distribution of Legionella pneumophila MLVA-genotypes in a drinking water system. Water Res. 2015, 77, 119–132. [Google Scholar] [CrossRef]
  24. Sánchez-Busó, L.; Olmos, M.P.; Camaró, M.L.; Adrián, F.; Calafat, J.M.; González-Candelas, F. Phylogenetic analysis of environmental Legionella pneumophila isolates from an endemic area (Alcoy, Spain). Infect. Genet. Evol. 2015, 30, 45–54. [Google Scholar] [CrossRef]
  25. Nguyen, C.; Elfland, C.; Edwards, M. Impact of advanced water conservation features and new copper pipe on rapid chloramine decay and microbial regrowth. Water Res. 2012, 46, 611–621. [Google Scholar] [CrossRef]
  26. Zhang, Y.; Edwards, M. Accelerated chloramine decay and microbial growth by nitrification in premise plumbing. Am. Water Work. Assoc. J. 2009, 101, 51. [Google Scholar] [CrossRef]
  27. LeChevallier, M.W.; Lowry, C.D.; Lee, R.G.; Gibbon, D.L. Examining the relationship between iron corrosion and the disinfection of biofilm bacteria. J. Am. Water Work. Assoc. 1993, 85, 111–123. [Google Scholar] [CrossRef]
  28. Wang, H.; Masters, S.; Hong, Y.; Stallings, J.; Falkinham, J.O.; Edwards, M.A.; Pruden, A. Effect of Disinfectant, Water Age, and Pipe Material on Occurrence and Persistence of Legionella, mycobacteria, Pseudomonas aeruginosa, and Two Amoebas. Environ. Sci. Technol. 2012, 46, 11566–11574. [Google Scholar] [CrossRef] [PubMed]
  29. Zhang, Y.; Griffin, A.; Edwards, M. Nitrification in premise plumbing: Role of phosphate, pH and pipe corrosion. Environ. Sci. Technol. 2008, 42, 4280–4284. [Google Scholar] [CrossRef] [PubMed]
  30. Långmark, J.; Storey, M.V.; Ashbolt, N.J.; Stenström, T.-A. The effects of UV disinfection on distribution pipe biofilm growth and pathogen incidence within the greater Stockholm area, Sweden. Water Res. 2007, 41, 3327–3336. [Google Scholar] [CrossRef] [PubMed]
  31. Weinrich, L.A.; Weinrich, L.A.; Jjemba, P.K.; Giraldo, E.; LeChevallier, M.W. Implications of organic carbon in the deterioration of water quality in reclaimed water distribution systems. Water Res. 2010, 44, 5367–5375. [Google Scholar] [CrossRef] [PubMed]
  32. Thomas, V.; Bouchez, T.; Nicolas, V.; Robert, S.; Loret, J.F.; Lévi, Y. Amoebae in domestic water systems: Resistance to disinfection treatments and implication in Legionella persistence. J. Appl. Microbiol. 2004, 97, 950–963. [Google Scholar] [CrossRef]
  33. Mustapha, P.; Epalle, T.; Allegra, S.; Girardot, F. Monitoring of Legionella pneumophila viability after chlorine dioxide treatment using flow cytometry. Res. Microbiol. 2015, 166, 215–219. [Google Scholar] [CrossRef]
  34. Singer, P.C. Control of disinfection by-products in drinking water. J. Environ. Eng. 1994, 120, 727–744. [Google Scholar] [CrossRef] [Green Version]
  35. Hua, G.; Reckhow, D.A. DBP formation during chlorination and chloramination: Effect of reaction time, pH, dosage, and temperature. J. Am. Water Work. Assoc. 2008, 100, 82–95. [Google Scholar] [CrossRef]
  36. Dupuy, M.; Mazoua, S.; Berne, F.; Bodet, C.; Garrec, N.; Herbelin, P.; Menard-Szczebara, F.; Oberti, S.; Rodier, M.-H.; Soreau, S.; et al. Efficiency of water disinfectants against Legionella pneumophila and Acanthamoeba. Water Res. 2011, 45, 1087–1094. [Google Scholar] [CrossRef] [PubMed]
  37. Fisher, I.; Kastl, G.; Sathasivan, A. A suitable model of combined effects of temperature and initial condition on chlorine bulk decay in water distribution systems. Water Res. 2012, 46, 3293–3303. [Google Scholar] [CrossRef] [PubMed]
  38. Monteiro, L.; Viegas, R.; Covas, D.I.; Menaia, J. Modelling chlorine residual decay as influenced by temperature. Water Environ. J. 2015, 29, 331–337. [Google Scholar] [CrossRef]
  39. Coniglio, M.A.; Melada, S.; Yassin, M.H. Monochloramine for controlling Legionella in biofilms: How much we know? J. Nat. Sci. 2015, 1, 44. [Google Scholar]
  40. Pioneer. Sodium Hypochlorite Handbook. Available online: http://www.forceflow.com/hypochlorite/PioneerHypo.pdf (accessed on 27 June 2017).
  41. Olin Corporation. Sodium Hypochlorite Manual. Available online: https://olinchloralkali.com/wp-content/uploads/2016/11/Olin_NaClO_Handbook.pdf (accessed on 21 June 2016).
  42. Muraca, P.; Stout, J.E.; Yu, V.L. Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system. Appl. Environ. Microbiol. 1987, 53, 447–453. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  43. Garner, E.; Zhu, N.; Strom, L.; Edwards, M.; Pruden, A. A human exposome framework for guiding risk management and holistic assessment of recycled water quality. Environ. Sci. Water Res. Technol. 2016. [Google Scholar] [CrossRef] [Green Version]
  44. Bond, T.; Goslan, E.H.; Parsons, S.A.; Jefferson, B. Treatment of disinfection by-product precursors. Environ. Technol. 2011, 32, 1–25. [Google Scholar] [CrossRef]
  45. Zhang, Y.; Zhou, L.; Zeng, G.; Deng, H.; Li, G. Impact of total organic carbon and chlorine to ammonia ratio on nitrification in a bench-scale drinking water distribution system. Front. Environ. Sci. Eng. China 2010, 4, 430–437. [Google Scholar] [CrossRef]
  46. Liu, W.; Wu, H.; Wang, Z.; Ong, S.L.; Hu, J.Y.; Ng, W.J. Investigation of assimilable organic carbon (AOC) and bacterial regrowth in drinking water distribution system. Water Res. 2002, 36, 891–898. [Google Scholar] [CrossRef]
  47. Liu, X.; Wang, J.; Liu, T.; Kong, W.; He, X.; Jin, Y.; Zhang, B. Effects of assimilable organic carbon and free chlorine on bacterial growth in drinking water. PLoS ONE 2015, 10, e0128825. [Google Scholar] [CrossRef] [Green Version]
  48. van der Kooij, D.; Veenendaal, H.R.; Scheffer, W.J.H. Biofilm formation and multiplication of Legionella in a model warm water system with pipes of copper, stainless steel and cross-linked polyethylene. Water Res. 2005, 39, 2789–2798. [Google Scholar] [CrossRef] [PubMed]
  49. Martin, A.K. Organic Carbon Generation Mechanisms in Main and Premise Distribution Systems. Masters’ Thesis, Virginia Tech, Blacksburg, VA, USA, 2012. [Google Scholar]
  50. Connell, M.; Stenson, A.; Weinrich, L.; LeChevallier, M.; Boyd, S.L.; Ghosal, R.R.; Dey, R.; Whelton, A.J. PEX and PP Water Pipes: Assimilable Carbon, Chemicals, and Odors. J. Am. Water Work. Assoc. 2016, 108, E192–E204. [Google Scholar] [CrossRef] [Green Version]
  51. Williams, K.; Pruden, A.; Falkinham, J.O.; Edwards, M. Relationship between Organic Carbon and Opportunistic Pathogens in Simulated Glass Water Heaters. Pathogens 2015, 4, 355–372. [Google Scholar] [CrossRef] [Green Version]
  52. Masten, S.J.; Davies, S.H.; Mcelmurry, S.P. Flint Water Crisis: What Happened and Why? J. Am. Water Work. Assoc. 2016, 108, 22–34. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  53. van der Kooij, D.; Veenendaal, H.R.; Italiaander, R.; van der Mark, E.J.; Dignum, M. Primary-Colonizing Betaproteobacteriales Play a Key Role in Growth of Legionella Pneumophila in Biofilms on Surfaces Exposed to Drinking Water Treated By Slow Sand Filtration. Appl. Environ. Microbiol. 2018, 84. [Google Scholar] [CrossRef] [Green Version]
  54. Dai, D.; Proctor, C.R.; Williams, K.; Edwards, M.A.; Pruden, A. Mediation of effects of biofiltration on bacterial regrowth, Legionella pneumophila, and the microbial community structure under hot water plumbing conditions. Environ. Sci. Water Res. Technol. 2018, 4, 183–194. [Google Scholar] [CrossRef]
  55. Van der Kooij, D.; van der Wielen, P.W.; Rosso, D.; Shaw, A.; Borchardt, D.; Ibisch, R.; Apgar, D.; Witherspoon, J.; Di Toro, D.M.; Paquin, P.R. Microbial Growth in Drinking Water Supplies; Iwa Publishing: London, UK, 2013. [Google Scholar]
  56. Wullings, B.A.; Bakker, G.; van der Kooij, D. Concentration and Diversity of Uncultured Legionella spp. in Two Unchlorinated Drinking Water Supplies with Different Concentrations of Natural Organic Matter. Appl. Environ. Microbiol. 2011, 77, 634–641. [Google Scholar] [CrossRef] [Green Version]
  57. Proctor, C.R.; Dai, D.; Edwards, M.A.; Pruden, A. Interactive effects of temperature, organic carbon, and pipe material on microbiota composition and Legionella pneumophila in hot water plumbing systems. Microbiome 2017, 5, 130. [Google Scholar] [CrossRef]
  58. Chang, S.L. Modern concept of disinfection. J. Sanit. Eng. Div. 1971, 97, 689–707. [Google Scholar]
  59. Ward, N.R.; Wolfe, R.; Olson, B.H. Effect of pH, application technique, and chlorine-to-nitrogen ratio on disinfectant activity of inorganic chloramines with pure culture bacteria. Appl. Environ. Microbiol. 1984, 48, 508–514. [Google Scholar] [CrossRef] [Green Version]
  60. Vatansever, C.; Irfan, T. Survival of Biofilm-Associated Legionella pneumophila Exposed to Various Stressors. Water Environ. Res. 2015, 87, 227. [Google Scholar] [CrossRef] [PubMed]
  61. Wadowsky, R.M.; Wolford, R.; McNamara, A.; Yee, R.B. Effect of temperature, pH, and oxygen level on the multiplication of naturally occurring Legionella pneumophila in potable water. Appl. Environ. Microbiol. 1985, 49, 1197–1205. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  62. States, S.J.; Conley, L.F.; Towner, S.G.; Wolford, R.S.; Stephenson, T.E.; McNamara, A.M.; Wadowsky, R.M.; Yee, R.B. An alkaline approach to treating cooling towers for control of Legionella pneumophila. Appl. Environ. Microbiol. 1987, 53, 1775–1779. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  63. Rhoads, W.J.; Pruden, A.; Edwards, M.A. Convective mixing in distal pipes exacerbates Legionella pneumophila growth in hot water plumbing. Pathogens 2016, 5, 29. [Google Scholar] [CrossRef] [Green Version]
  64. Wang, H.; Edwards, M.; Falkinham, J.O., III; Pruden, A. Molecular Survey of the Occurrence of Legionella spp., Mycobacterium spp., Pseudomonas aeruginosa, and Amoeba Hosts in Two Chloraminated Drinking Water Distribution Systems. Appl. Environ. Microbiol. 2012, 78, 6285–6294. [Google Scholar] [CrossRef] [Green Version]
  65. Masters, S.; Wang, H.; Pruden, A.; Edwards, M.A. Redox gradients in distribution systems influence water quality, corrosion, and microbial ecology. Water Res. 2015, 68, 140–149. [Google Scholar] [CrossRef]
  66. Feeley, J.; Gorman, G.; Weaver, R.; Mackel, D.C.; Smith, H. Primary isolation media for Legionnaires disease bacterium. J. Clin. Microbiol. 1978, 8, 320–325. [Google Scholar]
  67. Warren, W.J.; Miller, R.D. Growth of Legionnaires disease bacterium (Legionella pneumophila) in chemically defined medium. J. Clin. Microbiol. 1979, 10, 50–55. [Google Scholar] [CrossRef] [Green Version]
  68. Rakić, A.; Štambuk-Giljanović, N. Physical and chemical parameter correlations with technical and technological characteristics of heating systems and the presence of Legionella spp. in the hot water supply. Environ. Monit. Assess. 2016, 188, 1–12. [Google Scholar] [CrossRef]
  69. Bargellini, A.; Marchesi, I.; Righi, E.; Ferrari, A.; Cencetti, S.; Borella, P.; Rovesti, S. Parameters predictive of Legionella contamination in hot water systems: Association with trace elements and heterotrophic plate counts. Water Res. 2011, 45, 2315–2321. [Google Scholar] [CrossRef]
  70. Pieper, K.J.; Tang, M.; Edwards, M.A. Flint Water Crisis Caused By Interrupted Corrosion Control: Investigating “Ground Zero” Home. Environ. Sci. Technol. 2017, 51, 2007–2014. [Google Scholar] [CrossRef]
  71. Ramseier, M.K.; Ramseier, M.K.; Peter, A.; Traber, J.; von Gunten, U. Formation of assimilable organic carbon during oxidation of natural waters with ozone, chlorine dioxide, chlorine, permanganate, and ferrate. Water Res. 2011, 45, 2002–2010. [Google Scholar] [CrossRef] [PubMed]
  72. van der Wielen, P.W.; van der Kooij, D. Nontuberculous mycobacteria, fungi, and opportunistic pathogens in unchlorinated drinking water in The Netherlands. Appl. Environ. Microbiol. 2013, 79, 825–834. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  73. Stout, J.E.; Yu, V.L.; Yee, Y.C.; Vaccarello, S.; Diven, W.; Lee, T.C. Legionella pneumophila in residential water supplies: Environmental surveillance with clinical assessment for Legionnaires’ disease. Epidemiol. Infect. 1992, 109, 49–57. [Google Scholar]
  74. Reeves, M.; Pine, L.; Hutner, S.; George, J.; Harrell, W. Metal requirements of Legionella pneumophila. J. Clin. Microbiol. 1981, 13, 688–695. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  75. Wang, H.; Proctor, C.R.; Edwards, M.A.; Pryor, M.; Santo Domingo, J.W.; Ryu, H.; Camper, A.K.; Olson, A.; Pruden, A. Microbial community response to chlorine conversion in a chloraminated drinking water distribution system. Environ. Sci. Technol. 2014, 48, 10624–10633. [Google Scholar] [CrossRef]
Figure 1. Simulated glass water heaters (SGWHs) identified by their premise plumbing condition. No Cl control not pictured, but identical to Cl Control.
Figure 1. Simulated glass water heaters (SGWHs) identified by their premise plumbing condition. No Cl control not pictured, but identical to Cl Control.
Microorganisms 08 01452 g001
Figure 2. Water preparation method for high and low total organic carbon (TOC) granular-activated carbon (GAC) treated waters. These waters were used as simulated glass water heater (SGWH) influent after adjusting chlorine and pH. Town of Blacksburg tap water is a chloraminated water source.
Figure 2. Water preparation method for high and low total organic carbon (TOC) granular-activated carbon (GAC) treated waters. These waters were used as simulated glass water heater (SGWH) influent after adjusting chlorine and pH. Town of Blacksburg tap water is a chloraminated water source.
Microorganisms 08 01452 g002
Figure 3. Cumulative chlorine added to the influent water conditions. Solid line is the 1:1 correlation between added and measured Cl2. Dashed red lines are the best fit linear regression results.
Figure 3. Cumulative chlorine added to the influent water conditions. Solid line is the 1:1 correlation between added and measured Cl2. Dashed red lines are the best fit linear regression results.
Microorganisms 08 01452 g003
Figure 4. The change in log gene copy numbers of target organisms, enumerated by qPCR, in simulated glass water heaters (SGWHs) dosed with 0.5 mg/L disinfectant (week 9) versus no disinfectant (week 1) at two total organic carbon (TOC) concentrations. Each point represents the difference in the week 9 and week 1 measurements for one SGWH, with negative values indicating lower levels of organisms due to time or the impact of chlorine. The black dotted line at zero indicates no change in gene copies per milliliter in each SGWH, whereas the dashed red line indicates the median decrease observed in the No Cl (No chlorine) control due to a temporal effect. Shaded areas indicate “glass-only” SGWHs (no plumbing condition or pH change present) control conditions with either no disinfectant added (No Cl) or disinfectant added as indicated (Cl control, chloramine).
Figure 4. The change in log gene copy numbers of target organisms, enumerated by qPCR, in simulated glass water heaters (SGWHs) dosed with 0.5 mg/L disinfectant (week 9) versus no disinfectant (week 1) at two total organic carbon (TOC) concentrations. Each point represents the difference in the week 9 and week 1 measurements for one SGWH, with negative values indicating lower levels of organisms due to time or the impact of chlorine. The black dotted line at zero indicates no change in gene copies per milliliter in each SGWH, whereas the dashed red line indicates the median decrease observed in the No Cl (No chlorine) control due to a temporal effect. Shaded areas indicate “glass-only” SGWHs (no plumbing condition or pH change present) control conditions with either no disinfectant added (No Cl) or disinfectant added as indicated (Cl control, chloramine).
Microorganisms 08 01452 g004
Figure 5. Spearman correlation coefficients (ρ) of comparing gene copy numbers of various target microorganisms, iron concentration, and magnesium concentration. Color scale indicates the direction and magnitude of the correlation coefficient (ρ). Gray marks indicate correlations that are not significant at the 0.05 level.
Figure 5. Spearman correlation coefficients (ρ) of comparing gene copy numbers of various target microorganisms, iron concentration, and magnesium concentration. Color scale indicates the direction and magnitude of the correlation coefficient (ρ). Gray marks indicate correlations that are not significant at the 0.05 level.
Microorganisms 08 01452 g005
Table 1. Simulated glass water heater (SGWH) experimental set up.
Table 1. Simulated glass water heater (SGWH) experimental set up.
SGWH Condition 1Premise Plumbing MaterialGlass Beads?Cl Added?NH3 AddedpH of Influent 2
No ClNoneNoNoNo7.5 ± 0.1
Cl controlNoneNoYesNo7.5 ± 0.1
ClNH2NoneYesYesYes7.5 ± 0.1
ClNH2 comboIron and Magnesium anode rodYesYesYes7.5 ± 0.1
Iron metalIron couponYesYesNo7.5 ± 0.1
Iron oxideFe(OH)3 (rust)YesYesNo7.5 ± 0.1
MgMagnesium anode rodYesYesNo7.5 ± 0.1
PEXPEX couponsYesYesNo7.5 ± 0.1
pH 10NoneYesYesNo10 ± 0.1
1 Independent triplicate SGWHs were established for each condition, with a low and high level of total organic carbon (TOC), resulting in 54 SGWHs total. 2 pH values shown are targeted influent values for each condition.
Table 2. Average percent chlorine decay measured in effluent of triplicate “glass-only” SGWHs, without premise plumbing materials.
Table 2. Average percent chlorine decay measured in effluent of triplicate “glass-only” SGWHs, without premise plumbing materials.
Microorganisms 08 01452 i001

Share and Cite

MDPI and ACS Style

Martin, R.L.; Harrison, K.; Proctor, C.R.; Martin, A.; Williams, K.; Pruden, A.; Edwards, M.A. Chlorine Disinfection of Legionella spp., L. pneumophila, and Acanthamoeba under Warm Water Premise Plumbing Conditions. Microorganisms 2020, 8, 1452. https://doi.org/10.3390/microorganisms8091452

AMA Style

Martin RL, Harrison K, Proctor CR, Martin A, Williams K, Pruden A, Edwards MA. Chlorine Disinfection of Legionella spp., L. pneumophila, and Acanthamoeba under Warm Water Premise Plumbing Conditions. Microorganisms. 2020; 8(9):1452. https://doi.org/10.3390/microorganisms8091452

Chicago/Turabian Style

Martin, Rebekah L., Kara Harrison, Caitlin R. Proctor, Amanda Martin, Krista Williams, Amy Pruden, and Marc A. Edwards. 2020. "Chlorine Disinfection of Legionella spp., L. pneumophila, and Acanthamoeba under Warm Water Premise Plumbing Conditions" Microorganisms 8, no. 9: 1452. https://doi.org/10.3390/microorganisms8091452

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop