1. Introduction
Modern society is becoming increasingly interconnected, and the electric power grid is providing, besides energy from the sources to the loads, a main path for communication systems. Although, in many applications, separate lines are used for power delivery and data communication, in recent installations they have been merged by resorting to Power Line Communication (PLC) technology [
1,
2,
3]. Transmitting power and data through a single interconnect is highly desirable in all those fields in which reduction of cost, mass, and weight is the target. Therefore, PLC is attracting increasing interest in different applications, e.g., Smart Grid (SG), Advanced Meter Infrastructure, home automation, and electric vehicles [
4,
5,
6,
7].
G3-PLC is a widespread communication protocol in many PLC applications, such as in the SG framework. However, recent research results put in evidence that it may suffer from potential coexistence issues associated with the power converter modulation scheme being used. In particular, alternative Pulse Width Modulation (PWM) schemes such as Random Pulse Width Modulation (RPWM), which are largely adopted as a cost-effective alternative to traditional EMI filters to reduce the Conducted Emissions (CE) from power converters, have been found to interfere with the PLC [
8,
9,
10,
11].
The effects of power converter modulation schemes on PLC systems are an open research area, and enough research has not yet been conducted. There are contributions discussing the comparison between conventional PWM and RPWM effects on the PLC system. For instance, in [
12], the comparison between the deterministic and random modulation effects on the narrow-band G3-PLC performance in terms of Frame Error Rate (FER) is presented. In that work, only one type of RPWM scheme, i.e., Random Frequency Modulation (RFM), was considered, and it was found that the RFM results in a higher FER than the deterministic modulation in a specific switching frequency range (50–75 kHz) near the center frequency of the G3-PLC (63 kHz). In [
13], the influence of deterministic and random modulation on the transmission errors of a serial communication systems is compared using a mathematical model, where no significant differences between the two modulation schemes were observed. Additionally, the influence of a random frequency modulated SiC-based buck converter on the G3-PLC Channel Capacity and Channel Capacity Loss is investigated in [
14], where it is shown that RFM impairs the G3-PLC channel performance.
In other contributions, the interference between randomly modulated converters and other communication protocols is studied. For instance, in [
15], the effects of random frequency modulated power converters on the low frequency digital communication systems were studied, and it was proven that RPWM does not have a significant effect on digital communication systems. In general, only specific random modulation schemes (mainly RFM) were investigated in the literature, and further investigations on other random modulation strategies are required. More recently, the effects of Random Pulse Position (RPPM) on the PLC system are compared with conventional PWM in [
16]. However, the analysis was carried out based on simulations only, and experimental verification is needed to draw general conclusions.
Additional investigations are required to determine which random modulation scheme is most suitable for power converters in applications involving PLC. Furthermore, there are also many parameters that influence random modulation schemes, such as the switching frequency of the RPWM, the modulation index, and the Random Number Update Rate (RNUR). Hence, more analysis is required to identify constraints on these parameters, assuring coexistence with PLC. For instance, the switching frequency of the randomly modulated power converter is not constant, i.e., it depends on the specific application, and it is very difficult to draw general conclusions about coexistence by considering specific switching frequencies only. Furthermore, the modulation index specifies by how much the pulse position of the RPPM should vary, and it surely plays a significant role on the coexistence. The RNUR determines how fast the pulse position of RPPM should change, and it obviously also affects the operation of the RPPM.
In line with these objectives, this work is aimed at investigating the effects of the RPPM on the G3-PLC system and at comparing the results with previous experimental findings obtained with other modulation strategies (such as the RFM) to understand which modulation scheme could better assure coexistence. To this end, an experimental test campaign aimed at examining the effects of the main parameters that affect the RPPM, such as the switching frequency, modulation index, and the RNUR, on the performance of G3-PLC is carried out. The performance of the G3-PLC is assessed by considering the FER, the Channel Capacity, and the Channel Capacity Loss.
The remaining part of the manuscript is organized as follows.
Section 2 introduces the details of Random Modulation. The description of the G3-PLC and the experimental test setup is presented in
Section 3 and
Section 4, respectively. The obtained results are then presented and discussed in
Section 5. Finally, in
Section 6, some conclusions are drawn.
2. Random Pulse Position Modulation
In RPWM, one of the switching parameters of the PWM signal, such as switching period, pulse position, and pulse width, are varied randomly in order to spread the noise exiting power converters. Therefore, RPWM can be classified as Random Frequency Modulation (RFM), Random Pulse Position Modulation (RPPM), and Random Duty-Cycle Modulation (RDCM), depending on the parameter, which is made random [
17].
Figure 1 shows the RPWM signal, where ‘T’ is switching period, ‘∆’ is the pulse position, and ‘d’ denotes pulse width.
In order to investigate the properties of RPWM, it is important to consider the Power Spectral Density (PSD) (in particular for RPPM). For conventional PWM, the PSD can be directly determined from the Fourier Series expansion of the PWM signal (1).
or indirectly, by using the autocorrelation/PSD relationship [
18,
19,
20]:
where
S(
f) is the PSD of the PWM signal,
is the magnitude of the Fourier Series coefficients,
is the switching frequency, and
is the autocorrelation of the switching signal, respectively.
However, it is not straightforward to apply the above formulas to find the PSD of RPWM signals, because they are random and can be described only by a probabilistic level using the theory of stochastic processes such as Wide-Sense Stationary (WSS) random processes.
The PSD of a RPPM is derived in [
20] by assuming the constant switching period and pulse width of the RPWM shown in
Figure 1.
where
U (
f;
d) is the Fourier transform of the sampling pulse
u(
t):
E{e−jωΔ} is the expectation of the probability density function of the random pulse position, which depends on the distribution of the random number, and = 2πf.
As an example, the PSD of RPPM with 5 kHz switching frequency and 0.5 duty ratio is shown in
Figure 2. In this case, a uniformly distributed random number is used to vary the random pulse position. Of course, the shape of the spectrum may change if the distribution of the random number changes, e.g., if a normal distribution is used. However, the spectrum always exhibits both the density and the harmonic part, unlike other modulation schemes. For instance, the RFM spectrum only exhibits the density part [
20]. This makes RPPM less effective compared to RFM in minimizing the CE of power converters. Nevertheless, this property will play a significant role in making RPPM more compatible than RFM with communications systems.
5. Results and Discussion
The performance of the G3-PLC is assessed by considering the FER, the Channel Capacity, and the Channel Capacity Loss metrics. The
FER indicates the percentage of data frames correctly received over the total data frames sent through the communication system, and it can be determined as:
The Channel Capacity,
C, indicates the maximum bits of data that the communication system can transmit in the unit time [
25], and is defined as:
where
and
are the lower and upper frequency bands of the G3-PLC,
S(
f) is the PSD of the G3-PLC, and
N(
f) is the PSD of the noise, which encompasses two contributions:
where
N_0 (
f) denotes the PSD of the background noise and
N_EMI (
f) denotes the PSD of the noise from the DC-DC converter. Eventually, the Channel Capacity Loss is defined as:
where
CG3 and
C0 denote the Channel Capacity of the G3-PLC with and without the noise from the DC-DC converter (
N_EMI).
5.1. Effects of the Conveter Switching Frequency
This section presents experimental results showing the effects of the switching frequency of a randomly modulated power converter on the G3-PLC system. Hence, different switching frequencies from 10 kHz to 100 kHz are considered for this analysis.
Figure 6 shows the FER calculated from 3000 frames of data transmitted through the G3-PLC when different switching frequencies are applied to the DC-DC converter resorting to RPPM. The input of the DC-DC converter is fixed to 50 V. The FER is significantly higher in the G3-PLC bandwidth (when the switching frequency of the DC-DC converter is in the range of 35–91 kHz), with a maximum value of around 60 kHz (i.e., the center frequency of the PLC bandwidth). However, the FER is not significant where the switching frequency of the DC-DC converter is out of the bandwidth of the G3-PLC. This result allows draws the conclusion that RPPM could only influence the G3-PLC when the switching frequency of the power converter is in the bandwidth of the G3-PLC system.
A similar analysis involving RFM was carried out in [
14], with the same input voltage of the DC-DC converter (50 V), and switching frequency varied from 50 to 75 kHz. Some of the results obtained in [
14] are summarized in
Table 3. The comparison allows appreciation of the fact that RFM (with 15–30% modulation index) causes significantly larger FER (more than 40%) compared to RPPM, with a maximum FER of 8% obtained at 20% modulation index (which is the maximum possible pulse position variation, as defined in (9)) around the intermediate switching frequency (60 kHz). Even with lower modulation indexes, RFM causes higher FER than RPPM. This is because the bandwidth of the noise generated by a DC-DC converter with RFM is wider (i.e., the noise is more spread) than with RPPM. This can be easily appreciated in
Figure 7, where the CE exiting the same DC-DC converter driven by different modulation schemes (PWM, RFM, and RPPM at the 20 kHz switching frequency) are compared. The comparison unveils that even if RFM is more effective than RPPM for EMI reduction, RPPM offers significant advantages in terms of coexistence with communication systems. Of course, better performance of RFM can be obtained by adjusting the working parameters, i.e., by reducing the modulation index of RFM it is possible to have lower interference to the G3-PLC, but with lower CE reduction. This corroborates the conclusion that choosing the right modulation scheme is to be intended as a trade-off between EMI reduction and the coexistence issue.
This conclusion is also confirmed when the Channel Capacity is considered. As depicted in
Figure 8, the Channel Capacity of the G3-PLC reduces when the switching frequency of the converter is near the intermediate frequency of the G3-PLC system. However, for switching frequencies out of the bandwidth of the G3-PLC, the Channel Capacity is not significantly affected. The worst Channel Capacity in the case of RPPM obtained is at switching frequencies around 60–63 kHz (498 kb/s) and results to be significantly higher than the minimum Channel Capacity obtained in [
14] with the DC-DC converter driven by the RFM (390 kb/s at the spreading factor ‘α = 30%’ and 63 kHz switching frequency).
These observations are also confirmed in terms of Channel Capacity Loss. Indeed,
Figure 9 shows that the G3-PLC Channel Capacity Loss takes maximum value (18%) at 60 kHz, which results to be significantly lower than the maximum Channel Capacity Loss (48%) observed in [
14] for RFM (with spreading factor ‘α = 30%’).
5.2. Effects of Random Number Update Rate and Modulation Index
In this section, the effects of the RNUR and the modulation index of a randomly modulated power converter on the G3-PLC system are investigated.
The RNUR of the random number (see
Appendix A) plays a significant role on signal transmission because, with the higher RNUR of the random number, the pulse position of the RPWM changes rapidly.
The modulation index determines how much the pulse position could be varied with respect to the switching period. CE reduction is proportional to the modulation index because higher value result in higher reduction of the CE peak. Indeed, the maximum pulse position variation,
, should be:
Based on the results obtained in
Section 5.1, to analyze the effects of the RNUR of the random number and the modulation index, three switching frequencies are chosen, in which one is around the intermediate frequency of the G3-PLC (60 kHz) where maximum disturbance due to random modulation is registered (see
Section 5.1) and the other two are out of the frequency band of the G3-PLC (10 kHz and 100 kHz). A range of RNUR and modulation index values are considered to assess the performance of the G3-PLC.
Figure 10 shows the FER obtained when the switching frequency of the randomly modulated converter is 60 kHz, and the RNUR and the modulation index take values in the intervals 0.16–100% and 5–20%, respectively. The obtained result shows that the FER is directly proportional to both the RNUR and the modulation index. The FER increases when the RNUR and the modulation index increase. This result further confirms that there is a trade-off between EMI reduction and coexistence, i.e., increasing the modulation index helps in reducing the peaks of the converter CE (see
Figure 11). However, it causes more disturbance to the G3-PLC.
The Channel Capacity of the G3-PLC with respect to the RNUR and the modulation index is depicted in
Figure 12. The Channel Capacity exhibits significant reduction when both the RNUR and the modulation index are increased. The reduction with the RNUR is significant for large values of the modulation index. Conversely, for small modulation indexes, limited variations are observed. These results are also confirmed in terms of Channel Capacity Loss, as shown in
Figure 13. Normally, the Channel Capacity Loss also increases with an increase in both the RNUR and the modulation index.
The performance of the G3-PLC for switching frequencies outside the PLC bandwidth are shown in
Figure 14 and
Figure 15, respectively, confirming an increase in the FER when both the RNUR and the modulation index increase. However, the amount of variation in
Figure 14 and
Figure 15 is insignificant compared to the results in
Figure 10.
Therefore, it is possible to conclude that the RNUR and the modulation index of a randomly modulated power converter play a significant role in affecting the G3-PLC only when the switching frequency of the power converter overlaps with the bandwidth of the G3-PLC and is negligible for switching frequencies out of the bandwidth of the G3-PLC. This conclusion is confirmed also in terms of Channel Capacity and Channel Capacity Loss, whose plots are omitted for the sake of brevity.
6. Conclusions
In this paper, the coexistence between power and data lines in G3-PLC systems in the presence of randomly modulated power converters has been investigated. More specifically, among the available RPWM schemes, this work focused on RPPM. The effects of different parameters of an RPW-scheme driving power converter (switching frequency, modulation index, and RNUR) on the G3-PLC are assessed by experiments. Communication performance is evaluated in terms of FER, Channel Capacity, and Channel Capacity Loss. The obtained results have confirmed that switching frequencies close to the bandwidth of the G3-PLC causes interference in the PLC system more than those out of the frequency bandwidth. The comparison versus similar results obtained by considering other RPWM techniques has showed that there is a trade-off between CE reduction and coexistence with communication systems. Namely, even if RPPM is not as effective as other schemes (as, for instance, RFM) in reducing the CE exiting the converter, this modulation scheme outperforms RFM in terms of coexistence with communication systems. Moreover, the effects of other RPWM parameters, such as the RNUR and the modulation index, on the PLC system have been experimentally examined to draw general conclusions on the effectiveness of RPWM in assuring coexistence. Results showed that the RNUR and the modulation index of RPPM have a direct effect on the communication channel. Indeed, the performance of the G3-PLC degrades with the increase in the RNUR and the modulation index. However, this is true only when the switching frequency of the randomly modulated converter overlaps with the bandwidth of the G3-PLC. Otherwise the effect is almost negligible.
Based on the experimental analysis, it is possible to draw two main conclusions. First, a randomly modulated power converter may deteriorate PLC performance when the converter switching frequency is near the bandwidth of the communication channel. The interference can be avoided or reduced to a minimum by choosing different/non overlapping frequency bands for the converters and/or the PLC systems. Another conclusion is that, among the available RPWM schemes, RPPM is less detrimental than RFM. Obviously, RFM may also result in less interference to the PLC if a lower modulation index is chosen, but with compromising CE reduction.