Next Article in Journal
A Layered Method Based on Depth of Focus for Rapid Generation of Computer-Generated Holograms
Previous Article in Journal
Comparison of the Workday and Non-Workday Carbon Emission Reduction Benefits of Bikeshare as a Feeder Mode of Metro Stations
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Evaluation of the Fire Impact of Cellulose-Based Indoor Building Finishing Materials According to Changes in Room Size Aspect Ratio

1
Graduate School of Safety Engineering, Incheon National University, Incheon 22012, Republic of Korea
2
Fire Disaster Prevention Research Center of Safety Engineering, Incheon National University, Incheon 22012, Republic of Korea
*
Author to whom correspondence should be addressed.
Appl. Sci. 2024, 14(12), 5108; https://doi.org/10.3390/app14125108
Submission received: 7 May 2024 / Revised: 3 June 2024 / Accepted: 10 June 2024 / Published: 12 June 2024

Abstract

:
In modern society, the size of buildings tends to expand due to technological advances. However, while prioritizing performance design and specific building materials, fire research has fallen short of creating a comprehensive fire characteristic database for building materials. This study presents a plan for building a big data resource to evaluate the fire performance of cellulose-based flame retardant building finishing material in buildings of varying sizes. The three types of building finishing materials applied in this study are polyurethane foam, MDF, and cellulose-based building finishing materials. The variables were determined based on the floor area, and the change in floor area was calculated using the aspect ratio, a dimensionless number. Data analysis utilized the Fire Dynamics Simulator (FDS) to determine the time required to meet life safety standards for temperature, visibility, and Fractional Effective Dose (FED). The results confirm a correlation between the safe evacuation time (ASET) and increasing floor area. Additionally, the study demonstrates that cellulose-based flame-retardant building finishing material effectively maintains safe evacuation times even with increasing floor areas, as evidenced by increases of 41.0 s, 13.2 s, and 97.5 s in temperature, visibility, and FED, respectively.

1. Introduction

The worldwide average number of fire accidents was 2.4 million annually from 1993 to 2020, leading to approximately 40,000 deaths [1]. Moreover, in 2021, fire-related fatalities averaged 1.3 deaths and 4.9 injuries per 100,000 people, with building fires comprising around 31.3% of all fires [1].
Modern society is showing rapid growth in the construction industry due to the development of technology, and buildings are gradually expanding in size, as seen by the increase in enlargements and high-rise buildings, due to overcrowding populations [2,3]. However, this trend is accompanied by a gradual rise in fire accidents within buildings, leading to numerous deaths and significant property damage each year. As a result, interest in fire safety management in buildings is growing [4]. Therefore, a fire safety evaluation must be conducted in the construction planning stage to mitigate fire risk, which necessitates specialized expertise for accurate assessments [5].
In 2022, a fire at an apartment in Bronx, New York, USA, resulted in 17 deaths and 44 injuries due to smoke inhalation [6]. Smoke generated by the combustion of combustible substances during building fires is highly toxic, containing soot particles and steam, and it severely impairs occupants’ visibility, which is a primary cause of casualties [7,8]. Notably, building finishes composed of chemicals release a significant amount of harmful substances during combustion [8].
In addition, heat spreading through building finishing materials contributes to the growth of fires, making it imperative to scrutinize the progression of indoor building fires regarding temperature elevation over time. This can be achieved by employing HRR (heat release rate) and THR (total heat release) values [9,10].
In a previous study focused on fire prevention in buildings, Cui et al. introduced a knowledge graph aimed at visualizing the causes of fire, the fire development process, and the evacuation procedures based on building fire case information in China [11].
Zhang et al. addressed the limitations of the indicator system method currently employed in evaluating the fire risk of high-rise buildings. They proposed a new method for analyzing the probability of fire occurrence, which integrates the spatial Markov chain model [12].
Dong et al. investigated the temporal distribution and flow of smoke in buildings with complex structures using two software tools, Pyrosim and Revit [13].
Zhang et al. emphasized the significance of evacuation routes by investigating the utilization of large-scale crowd evacuation routes using the hierarchical node relocation model (HNRM), taking into account the intricacies of the fire evacuation process within complex structures [14].
Kodur et al. discussed the adverse effects of fire hazards in buildings and the constraints of current fire safety measures. Additionally, they underscored the importance of developing fire suppression systems, adopting fire design approaches, characterizing building materials, and implementing performance-based codes as methods to enhance fire safety [15].
Kim et al. conducted a fire hazard assessment for various building finishing materials in medical facilities using FDS and Pathfinder simulations. Their findings suggested the potential use of cellulose-based construction finishing materials and proposed measures to evaluate the safety of occupants during evacuation [16].
Ahn et al. conducted a study on construction finishing materials, where they experimented with manufacturing fire-resistant finishing materials by incorporating expandable graphite and magnesium hydroxide into cellulose-based construction finishing materials. As a result of the experiment, findings suggested the potential for eco-friendly construction finishing materials through the recycling of waste paper and highlighted the impact of particle size of expandable graphite on flame-retardant performance [17].
Han proposed the necessity of legal regulations concerning the fire vulnerability and flame-retardant performance of recently interior finishing materials. This proposal was based on fire combustion tests, flame propagation tests, and smoke density tests conducted on polyethylene combustible synthetic resin insulated wallpaper, commonly used for insulation and interior effects [18].
Kang et al. conducted a physical test on the vertical fire diffusion of outer wall finishing materials, combining the flame-retardant properties of polyurethane boards—commonly used as insulation materials in Asia—with aluminum sheets or granite materials, and evaluated the extent of fire diffusion resulting from this combination [19].
Park et al. conducted experiments following the test regulations of IMO Res to assess the combustibility and emission of combustion gases from flame-retardant plywood. As a result of the experiment, they suggest the potential of flame-retardant plywood as a building finishing material, achievable through enhancements in the surface functionality of wood [20].
Previous fire research has primarily focused on fire analysis techniques, fire risk factors, enhancements of evacuation routes, and improving overall fire safety. Also, research on building finishing materials has centered on developing new materials, emphasizing the importance of flame-retardant properties, and evaluating their impact on fire spread.
However, the structure of buildings is diversifying rapidly, yet the fire characteristics of new building finishing materials are not being integrated into a database. In addition, the current performance-based design should incorporate the fire characteristics of building finishing materials to mitigate fire risks like malfunctioning firefighting equipment. To address these concerns, this study aimed to identify the diversifying building structures and fire characteristics of building finishing materials and propose a research plan for constructing big data.
To understand how building structure influences fire characteristics, this study employed simulations to examine the effect of various building finishing materials on the internal space. Additionally, we selected the aspect ratio of floor area as the key variable to develop a strategy for utilizing basic data related to size variations. The variable chosen for building size was the aspect ratio of the floor area. Computational fluid dynamics (CFD) analysis was conducted using a Fire Dynamics Simulator (FDS) to assess fire characteristics. Parameters such as Fractional Effective Dose (FED), temperature, and visibility were selected for the analysis, and a quantitative evaluation was performed.

2. Experimental and Methods

2.1. Experimental Conditions

In modern society, buildings come in various shapes, but square shapes are common. This study aims to examine the fire characteristics of building finishing materials as the size of the building increases. The variable used to measure the building size is the floor area, with the aspect ratio of width to length (W:L) increasing from 1:1 to 1:5. However, to simulate harsh conditions, the indoor space was fixed at a low ceiling height of 2.2 m. Figure 1 illustrates the aspect ratios used in this study, while Table 1 outlines the actual sizes used for modeling.

2.2. Fire Analysis

2.2.1. Fire Modeling

In this study, the ignition source was a 0.2 m × 0.2 m × 0.2 m wooden block, and the simulation confirmed flame spread with the building finishing materials attached to the wall. Additionally, the fire room was configured as a closed space with no external air inflow. Polyurethane foam and MDF are commonly used building materials in Asia (including Korea) contributing to the high fire risk. To address this concern, we selected three different building finishing materials to highlight the importance of using flame-resistant materials and the need to evaluate the fire performance of newly developed building finishing materials. The building finishing materials selected for this study included polyurethane foam, MDF, and cellulose-based flame-resistant finishing materials [17,21]. The cellulose-based flame-retardant building finishing material (CFBFM) comprises 100 g of cellulose, 30 g of expanded graphite, and 20 g of magnesium hydroxide. Figure 2 depicts the flowchart of specimen production.
The specimen was manufactured with dimensions of 10 cm × 10 cm × 2 cm, conforming to the ISO 5660-1 standard [22] to confirm the flame-retardant performance. The manufacturing procedure was carried out by mixing water, expanded graphite, and magnesium hydroxide with finely pulverized waste paper, 3D printing it [23], and drying it.
The physical property values of MDF and CFRBFM were measured through a cone calorimeter (FESTEC Co., Seoul, Republic of Korea) and LFA 1000 (LINSEIS, Selb, Germany) experiments. Data values provided by FDS were used for the polyurethane foam. Table 2 outlines the reaction parameters of the building finishing materials, while Table 3 specifies the boundary conditions.

2.2.2. Mesh Resolution

The calculation accuracy strongly depends on the FDS mesh size. The size of the analysis grid can be determined by the characteristic fire diameter using Equation (1) in the fire plume analysis:
D * = Q ˙ ρ C p T g 2 / 5
where D * : characteristic fire diameter, Q ˙ : total heat release rate (kW), ρ : outside air density (kg/m3), C p : specific heat (kJ/kg·K), T : outside air temperature (K), g : acceleration of gravity (m/s2), and δ χ : nominal size of a mesh cell.
The D * / δ χ parameter is only valid if the value is between 4 and 16 [24]. The D * applied to this analysis is 0.503 m, and in this paper, D * / δ χ has a value of 10.06.

2.2.3. Safety Criteria

The life safety criteria in performance-based design are defined by parameters such as temperature, visibility, oxygen (O2), carbon monoxide (CO), and carbon dioxide (CO2), measured at a height of 1.8 m above the floor, which corresponds to the respiratory threshold for evacuees [25]. Temperature affects residents by causing thermal effects, and high temperatures of 60 °C or higher increase the risk of respiratory issues and skin burns [26,27]. Visibility is a factor that can obstruct evacuation due to the blocking of occupants’ view. Therefore, it is defined as safe when visibility is secured at more than 5 m [28]. Additionally, O2, CO, and CO2 values can be calculated using the Fractional Effective Dose (FED), which assesses the behavioral impact of gas concentration in the respiratory zone of the occupant. Equations (2)–(5) depict the calculation methods for FED [29].
F E D t o t = F E D C O × H V C O 2 + F E D O 2
F E D C O = 4.607 × 10 7 C C O 1.036 t
F E D O 2 = t 60 e x p 8.13 0.54 20.9 C O 2
H V C O 2 = e x p 0.1930 C C O 2 + 2.0004 7.1
where, t: unit time(s), C C O : CO concentration (ppm), C O 2 : O2 concentration (%), and C C O 2 : CO2 concentration (%).
The FED value serves as a criterion for assessing the impact of harmful gases resulting from combustion on the human body. An FED value of 1 indicates fatality for 50% of the occupants. Additionally, an FED value of 0.3 is considered an index of human body incapacitation [30,31].
In this study, the measurement criteria for fire risk assessment were divided into three categories: temperature, visibility, and FED. Table 4 outlines the life safety criteria utilized in this study.

3. Results

3.1. Analysis Result

Analysis Result of Safety Criteria

In this study, the measurement locations for life safety criteria were chosen as the farthest points from the ignition source, based on the height of 1.8 m from the floor, representing the breathing area. Table 5 details the location of each measurement point based on aspect ratios.
The arrival time of the life safety criteria can be defined as ASET (available safety egress time), and the measurement results showed that the ASET varied depending on the building finishing material. Figure 3 illustrates the variation in the ASET for each building finishing material according to the aspect ratio, while Table 6 presents the ASET values for each building finishing material.
The simulation results confirmed that the ASET was delayed as the aspect ratio increased. With the aspect ratio increasing from 1 to 5, the arrival times of temperature, visibility, and FED safety criteria for polyurethane foam were delayed by 6.0 s, 6.0 s, and 4.4 s, respectively. For MDF, similar delays were observed: 7.6 s for temperature, 8.0 s for visibility, and 8.4 s for FED criteria. CFRPBM exhibited the most significant delays with increasing aspect ratio. The reference excess times for temperature and visibility increased by 8.0 and 7.6 s, respectively. However, the FED excess time saw a much larger delay of 117.6 s.
The average increase in the ASET for temperature, visibility, and FED with the increase in aspect ratio was 1.5 s, 1.5 s, and 1.1 s, respectively, for polyurethane foam and 1.9 s, 2.0 s, and 2.1 s for MDF. CFRBFM exhibited an average increase of 2.0 s, 1.9 s, and 29.41 s, respectively, indicating its superior performance in the FED category compared to the building finishing material of the control group.

3.2. Change in Floor Area with Same Aspect Ratio

To further analyze the impact of building finishing materials based on the area of the fire room, we assumed that only the area was expanded without changing the aspect ratio. The aspect ratio was fixed at 1, and the length was extended by 2 m per case for additional simulations. Figure 4 depicts the conditions for the simulation with a fixed aspect ratio, and Table 7 details the sizes applied to the simulation.
In same aspect ratio conditions, the change in area results in a significant increase compared to conditions where the aspect ratio changes. This is due to the smoke’s radial expansion driven by heat buoyancy, which significantly impacts arrival times. Figure 5 illustrates the variation in the arrival time of safety standards for different building finishing materials under fixed aspect ratio conditions, while Table 8 presents the ASET of building finishing materials for each case.
The simulation results showed varying ASET differences between temperature, visibility, and FED criteria in Cases 1 and 5. For polyurethane foam, these delays ranged from 10.0 s (temperature) to 10.4 s (visibility) and 20.4 s (FED). Similarly, MDF exhibited delays of 21.2 s (temperature), 20.4 s (visibility), and 27.2 s (FED). However, CFRBFM displayed a significantly larger disparity. The time differences for CFRBFM were 164.0 s (temperature), 52.8 s (visibility), and a substantial 331.2 s (FED). The average increase in the ASET for temperature, visibility, and FED with the increase in area was 2.5 s, 2.6 s, and 5.11 s, respectively, for polyurethane foam and 5.3 s, 5.1 s, and 6.8 s for MDF. In contrast, CFRBFM exhibited increases of 41.0 s, 13.2 s, and 82.8 s, respectively, demonstrating superior performance in temperature and FED compared to the building finishing material of the control group. These results indicate enhanced safety in indoor fire diffusion suppression and occupant breathing areas.

3.3. Distribution of ASET in Room Size Conditions

The ASET of the building finishing material tended to increase with the increase in the aspect ratio. However, it was confirmed that there was no significant difference between the ASET changes in polyurethane foam and MDF. On the other hand, while the ASET change for CFRBFM did not differ significantly in the temperature and visibility items, it was observed that the ASET increased significantly with the increase in the aspect ratio in the FED item.
Therefore, when CFRBFM is used as indoor finishing material, the correlation between excess time and the aspect ratio of temperature and visibility is represented by Equation (6), while the correlation between the FED and aspect ratio is represented by Equation (7).
y T ,   V = 0.10107 x 2 + 1.41607 x + 2.163
y F E D = 1.54286 x 2 + 38.62514 x + 31.444
Figure 6 illustrates the ASET distribution of CFRBFM based on life safety criteria.
An increase in the aspect ratio of the floor area results in a corridor-shaped structure. Therefore, we conducted an additional fire impact assessment of building finishing materials to account for changes in area while maintaining the same aspect ratio. With the aspect ratio being maintained at 1, an increase in the area corresponds to an increase in the square of the length.
As a result of the simulation, when CFRBFM is used as an indoor finishing material, the correlation between the ASET of temperature, visibility, and FED and the length of the floor area is shown in Equations (8)–(10), respectively. However, in Case 5, the ASET for FED was not measured during the simulation operation time and was excluded.
y T e m p e r a t u r e = 4.83571 x 2 39.92557 x + 73.032
y V i s i b i l i t y = 0.77125 x 2 2.4935 x + 5.432
y F E D = 0.82687 x 2 + 38.83675 x 12.2675
Applying Equation (10), the FED standard ASET for Case 5 is predicted to be 458.79 s. Figure 7 illustrates the distribution of the ASET for CFRBFM based on life safety criteria under the same aspect ratio condition.
In terms of temperature and visibility of CFRBFM, the ASET showed a similar distribution, but the difference in the ASET increased when a certain length was exceeded. Trend line analysis confirmed that the trend line of temperature and the trend line of visibility intersect at approximately 6.74 m. Therefore, it is judged that mixing Equations (9) and (10) based on a floor length of 6.74 m provides a more accurate correlation for CFRBFM’s ASET of the temperature criteria.

4. Discussion

Fire development in a compartment proceeds in the order of growth, full development, and decline. The risk of a flashover phenomenon occurs when the internal temperature rises above 600 °C during this process [32,33]. Therefore, the temperature change observed during the simulation can be used to predict the flashover phenomenon. Figure 8 presents the distribution of temperature changes over time for different building finishing materials.
The simulation analysis revealed that polyurethane foam exceeded 600 °C within 50 s and reached a maximum temperature of 1265 °C, regardless of compartment structure and size. In contrast, MDF reached a maximum of 978 °C, lower than polyurethane foam but still exceeding 600 °C within 100 s, posing a risk of a flashover phenomenon.
In contrast, CFRPBM exhibited a significantly lower maximum temperature of around 433 °C. In the largest compartment (Case 5), the maximum temperature only reached around 72 °C, highlighting the fire suppression effect due to its flame-retardant properties.
The results may vary depending on openings like doors or windows in the compartment, which can affect airflow. However, it is judged that securing data for building finishing materials can be a valuable tool for ensuring the safety of occupants.

5. Conclusions

In this study, a fire impact assessment was conducted on three types of building finishing materials (polyurethane foam, MDF, and CFRBFM) in response to changes in the indoor floor area. For the fire risk assessment, the ASET of life safety criteria in three items—temperature, visibility, and FED—was measured, and the following results were derived through an analysis of the measurement results.
(1)
When the aspect ratio increased by 1, the ASET for temperature and visibility rose by an average of 1.5 to 2.0 s for all three building finishing materials. However, the impact on the FED’s ASET varied considerably. Polyurethane foam and MDF saw average increases of 1.1 s and 2.1 s, respectively. In contrast, CFRBFM exhibited a substantial increase of 29.41 s, highlighting a significant difference in fire safety performance for larger compartments.
(2)
Increasing the area while maintaining the aspect ratio resulted in an average ASET increase of 2.5 s to 6.81 s for polyurethane foam and MDF. CFRBFM, however, exhibited a larger increase in the ASET, with average delays of 41.0 s, 13.2 s, and 82.8 s for temperature, visibility, and FED, respectively. This suggests that CFRBFM may offer an advantage in securing an ASET for temperature and FED in larger compartments.
(3)
Regardless of the type of increase in the floor area, both polyurethane foam and MDF exhibited a slight increase in the ASET within 8.5 s as the area expanded, with smoke spreading over the entire area within 42.0 s.
(4)
The ASET of CFRBFM showed different results depending on the shape of the floor area. When the floor area was increased proportionally by the aspect ratio, the increase in the ASET tended to be uniform. However, when the area increased with the same aspect ratio, it was observed that the increase in the ASET gradually rose. In particular, in the case of temperature, it was noted that the increase in the ASET escalated rapidly when the length of the floor surface exceeded 6 m. This was attributed to the flame-retardant performance of CFRBFM. Therefore, it was demonstrated that the larger the size of the room, the more effective it was in securing the ASET.
(5)
The fire risk assessment of building finishing materials was conducted by incrementally increasing the floor area in five stages based on the aspect ratio. As a result of the study, when the building finishing material is CFRBFM, the correlation between temperature, visibility, FED’s ASET, and changes in floor area conditions can be expressed by the trend equation provided in Equation (6) through (10).
(6)
By monitoring temperature changes over time, we observed a maximum internal temperature increase of 433 °C for CFRPBM within 400 s. This finding suggests a very low risk of flashover, indicating CFRPBM’s strong flame-retardant performance.
(7)
This study investigated the effectiveness and correlation between fire risk and cellulose-based building finishing materials by assessing fire risk while varying the building’s floor area based on its aspect ratio. This research method demonstrates the potential of big data analysis for evaluating fire risk, predicting fire characteristics and making ASET predictions based on the chosen building finishing materials.
However, further research is necessary to explore the combined impact of changes in both area and volume, including the fire space height and the reference length used for aspect ratio calculations. Additionally, comprehensive big data and ensuring the reliability of building finishing materials require further research and cross-validation using various up-to-date numerical models. Experimental data, including thermal pyrolysis data, are also considered essential for determining the chemical properties of building finishing materials.

Author Contributions

Conceptualization, D.R. and Y.K.; methodology, D.R. and Y.K.; software, Y.K.; formal analysis, Y.K.; investigation, Y.K.; resources, Y.K.; data curation, Y.K.; writing—original draft preparation, Y.K.; writing—review and editing, D.R.; visualization, Y.K.; supervision, D.R. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The raw data supporting the conclusions of this article will be made available by the authors on request.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Internal Association of Fire and Rescue Services. Center for Fire Statistics World Fire Statistics. 2023. Available online: https://ctif.org/world-fire-statistics (accessed on 1 March 2024).
  2. Wu, L.; Lv, D.; Cheng, W. The phased evaluation and information visualization of city building fire hazards. In Proceedings of the 2010 4th International Conference on Bioinformatics and Biomedical Engineering, iCBBE 2010, Chengdu, China, 18–20 June 2010; pp. 2–5. [Google Scholar]
  3. Choi, D.C.; Kim, H.K.; Ko, M.H.; Kim, I.T.; Hwang, H.S. Survey on Existing High-Rise Building Fire Safety Assessment Based on Fire Compartment and Fire Protection System Maintenance. Fire Sci. Eng. 2020, 34, 72–78. [Google Scholar] [CrossRef]
  4. Ali, K.; Mubin, S. Measuring Effectiveness of Safety Management System of Multistory Building: Fire Safety Audit. Urban. Archit. Constr. 2023, 14, 289–306. [Google Scholar]
  5. Benson, C.M.; Elsmore, S. Reducing fire risk in buildings: The role of fire safety expertise and governance in building and planning approval. J. Hous. Built Environ. 2022, 37, 927–950. [Google Scholar] [CrossRef]
  6. Wikipedia, 2022 Bronx Apartment Fire. Available online: https://en.wikipedia.org/w/index.php?title=2022_Bronx_apartment_fire&oldid=1212092248 (accessed on 1 March 2024).
  7. NFPA Homepage. Reporter’s Guide: The Consequences of Fire. 2018. Available online: www.nfpa.org/News-and-Research/Publications-and-media/Press-Room/Reporters-Guide-to-Fire-and-NFPA/Consequences-of-fire (accessed on 27 November 2023).
  8. Seo, S.; Shin, S. A Study on the Fire Safety Performance of Interior Surface Materials in a Building. Korea Saf. Manag. Sci. 2013, 367–382. Available online: https://db.koreascholar.com/Article/Detail/320421 (accessed on 30 December 2023).
  9. Babrauskas, V. Ignition: A century of research and an assessment of our current status. J. Fire Prot. Eng. 2007, 17, 165–183. [Google Scholar] [CrossRef]
  10. Zhou, B.; Yoshioka, H.; Noguchi, T.; Wang, K. Experimental study of time-averaged upward fire propagation speed of expanded polystyrene external thermal insulation composite systems masonery façade. Fire Mater. 2021, 45, 193–204. [Google Scholar] [CrossRef]
  11. Cui, X.; Xu, Y.; Ruan, M.; Pan, Z.; Zhang, Z. Construction and application of knowledge graph for dispatching training. In Proceedings of the Sixth International Conference on Computer Information Science and Application Technology (CISAT 2023), Hangzhou, China, 26–28 May 2023; p. 43. [Google Scholar] [CrossRef]
  12. Zhang, Y.; Wang, G.; Wang, X.; Kong, X.; Jia, H.; Zhao, J. Regional High-Rise Building Fire Risk Assessment Based on the Spatial Markov Chain Model and an Indicator System. Fire 2024, 7, 16. [Google Scholar] [CrossRef]
  13. Dong, W.; Cai, Y.; Chen, J. Building Fire Simulation Analysis Based on Pyrosim and Revit. In Proceedings of the 2022 Chinese Automation Congress, CAC 2022, Xiamen, China, 25–27 November 2022; Volume 2022-Janua, pp. 4097–4100. [Google Scholar]
  14. Zhang, L.; Liu, J.; Tan, S. Research on Knowledge Navigation Strategy for Complex Building Fire Evacuation. In Proceedings of the 2023 9th International Conference on Electrical Engineering, Control and Robotics, EECR 2023, Wuhan, China, 24–26 February 2023; pp. 229–234. [Google Scholar]
  15. Kodur, V.; Kumar, P.; Rafi, M.M. Fire hazard in buildings: Review, assessment and strategies for improving fire safety. PSU Res. Rev. 2019, 4, 1–23. [Google Scholar] [CrossRef]
  16. Kim, Y.; Park, D.; Kim, S.; Rie, D. A Study on the Quantitative Fire Performance Evaluation Method of Building Finishing Materials with a Focus on Medical Facilities. Sustainability 2023, 15, 9373. [Google Scholar] [CrossRef]
  17. Ahn, C.; Park, D.; Kim, Y.; Rie, D. Fire performance, toxicity, and thermal diffusivity of wastepaper mixed with magnesium hydroxide, depending on the particle size of expandable graphite. Cellulose 2023, 31, 587–605. [Google Scholar] [CrossRef]
  18. Han, B.H. A Study on Evaluating the Fire Risk of the Foam Block Interior Finishing Material through the Fire Combustion Test. Ph.D. Thesis, Gachon University, Seongnam-si, Republic of Korea, 2019. [Google Scholar]
  19. Kang, K.; Chae, S.; You, J. A Study on the Diffusion of Vertical Fire in a Real Scale Type by Stone and Aluminum Panel Finishing Materials. J. Korean Soc. Hazard Mitig. 2022, 22, 1–8. [Google Scholar] [CrossRef]
  20. Park, H.J.; Jian, H.; Wen, M.; Jo, S.U. Toxic Gas and Smoke Generation and Flammability of Flame-Retardant Plywood. Polymers 2024, 16, 507. [Google Scholar] [CrossRef] [PubMed]
  21. Kim, Y.; Park, D.; Rie, D. Evaluation of the Flame-Retardant Performance and Fire Risk of Cellulose Building Finishing Material Due to the Particle Size of Expandable Graphite. Sustainability 2023, 15, 5426. [Google Scholar] [CrossRef]
  22. ISO 5660-1; Reaction-to-Fire Tests—Heat Release, Smoke Production and Mass Loss Rate—Part 1: Heat Release Rate (Cone Calorimeter Method) and Smoke Production Rate (Dynamic Measurement). ISO: Geneva, Switzerland, 2015.
  23. Ahn, C.; Park, D.; Hwang, J.; Rie, D. A Study on the Reliability of Mass, Density, and Fire Performance of Recycled Wastepaper Building Finishing Material Made with Large Wet Cellulose 3D Printers. Sustainability 2022, 14, 13090. [Google Scholar] [CrossRef]
  24. Salley, M.H.; Kassawara, R.P. Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications, Volume 7: Fire Dynamics Simulator (FDS); U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research (RES): Rockville, MD, USA, 2007; ISBN 1800553684. [Google Scholar]
  25. National Fire Safety Codes 203: Changes to the Law; Republic of Korea. 2021. Available online: https://www.law.go.kr/admRulSc.do?menuId=5&subMenuId=41&tabMenuId=183&query=nfsc203#liBgcolor0 (accessed on 18 January 2024).
  26. Zhou, M.; Zhou, B.; Zhang, Z.; Zhou, Z.; Liu, J.; Li, B.; Wang, D.; Wu, T. Fire Egress System Optimization of High-Rise Teaching Building Based on Simulation and Machine Learning. Fire 2023, 6, 190. [Google Scholar] [CrossRef]
  27. Xiong, K.; Weng, M.; Liu, F.; Lu, Y. Numerical Study on Evacuation Evaluation and Strategy of Theater with Rotating Auditorium. Buildings 2022, 12, 1202. [Google Scholar] [CrossRef]
  28. Li, M.X.; Zhu, S.B.; Wang, J.H.; Zhou, Z. Research on Fire Safety Evacuation in a University Library in Nanjing. Procedia Eng. 2018, 211, 372–378. [Google Scholar] [CrossRef]
  29. McGrattan, K.; McDermott, R.; Hostikka, S.; Floyd, J. NIST Special Publication 1019-5 Fire Dynamics Simulator (Version 5) User’s Guide. In Nist Special Publication; U.S. Departmemt of Commerce: Washington, DC, USA, 2010. Available online: https://nvlpubs.nist.gov/nistpubs/Legacy/SP/nistspecialpublication1019-5.pdf (accessed on 11 December 2023).
  30. Klein, R.A. SFPE Handbook of Fire Protection Engineering (1995); SFPE: Washington, DC, USA, 1997; Volume 29, ISBN 9781493925643. [Google Scholar]
  31. National Fire Protection Association. NFPA 101 Life Safety Code 2021; National Fire Protection Association: Quincy, MA, USA, 2021. [Google Scholar]
  32. Lucherini, A.; Torero, J.L. Defining the fire decay and the cooling phase of post-flashover compartment fires. Fire Saf. J. 2023, 141, 103965. [Google Scholar] [CrossRef]
  33. Bishop, S.R.; Drysdale, D.D. Fires in compartments: The phenomenon of flashover. Philos. Trans. R. Soc. A Math. Phys. Eng. Sci. 1998, 356, 2855–2872. [Google Scholar] [CrossRef]
Figure 1. Floor area aspect ratio.
Figure 1. Floor area aspect ratio.
Applsci 14 05108 g001
Figure 2. Flowchart of the specimen production and experimental order [21,22].
Figure 2. Flowchart of the specimen production and experimental order [21,22].
Applsci 14 05108 g002
Figure 3. Trends in safety criteria arrival time variation for each building finishing materials.
Figure 3. Trends in safety criteria arrival time variation for each building finishing materials.
Applsci 14 05108 g003
Figure 4. Simulation condition of same aspect ratio.
Figure 4. Simulation condition of same aspect ratio.
Applsci 14 05108 g004
Figure 5. Trends in safety criteria arrival time variation for each building finishing materials under same aspect ratio conditions.
Figure 5. Trends in safety criteria arrival time variation for each building finishing materials under same aspect ratio conditions.
Applsci 14 05108 g005
Figure 6. Distribution of ASET in CFRBFM with aspect ratio changes.
Figure 6. Distribution of ASET in CFRBFM with aspect ratio changes.
Applsci 14 05108 g006
Figure 7. Distribution of ASET in CFRBFM under same aspect ratio conditions.
Figure 7. Distribution of ASET in CFRBFM under same aspect ratio conditions.
Applsci 14 05108 g007
Figure 8. Distribution of temperature variation by building finishing materials.
Figure 8. Distribution of temperature variation by building finishing materials.
Applsci 14 05108 g008aApplsci 14 05108 g008b
Table 1. Fire room size.
Table 1. Fire room size.
PropertiesW (m)L (m)H (m)
Aspect ratio 1222.2
Aspect ratio 24
Aspect ratio 36
Aspect ratio 48
Aspect ratio 510
Table 2. Reaction parameter.
Table 2. Reaction parameter.
PropertiesPolyurethane FoamMDFCFRBFM
Density (kg/m3)40.0536.1530.0
Specific heat (kJ/kg·K)1.01.84.122
Conductivity (W/m·K)0.050.20.835
Heat of combustion (kJ/kg)30,000.019,702.51246.7
CO yield (kg/kg)0.03100.06680.0284
Soot yield (kg/kg)0.100.0095150.009861
Table 3. Boundary condition for fire simulation.
Table 3. Boundary condition for fire simulation.
PropertiesCondition
Heat Release Rate (HRR)200 kW
Air Temperature20 °C
Simulation Time400 s
Interior Finishing Material Thickness2 cm
Table 4. Performance criteria for life safety [25,30].
Table 4. Performance criteria for life safety [25,30].
PropertiesLimit
Respiratory limit line1.8 m
Fractional Effective Dose (FED)<0.3
Temperature<60 °C
Visibility>5 m
Table 5. Fire room measurement point by aspect ratio.
Table 5. Fire room measurement point by aspect ratio.
PropertiesW, L, H (m)
Fire SourceMeasurement Point
Aspect ratio 10.1, 0.1, 0.21.9, 1.9, 1.8
Aspect ratio 21.9, 3.9, 1.8
Aspect ratio 31.9, 5.9, 1.8
Aspect ratio 41.9, 7.9, 1.8
Aspect ratio 51.9, 9.9, 1.8
Table 6. ASET for each building finishing material by aspect ratio change.
Table 6. ASET for each building finishing material by aspect ratio change.
PropertiesAspect ratio
12345
Polyurethane foamTemperature3.20 s4.80 s6.00 s7.60 s9.21 s
Visibility3.20 s4.80 s6.00 s7.60 s9.21 s
FED8.40 s8.80 s10.40 s11.61 s12.80 s
MDFTemperature3.20 s4.80 s6.40 s8.40 s10.80 s
Visibility3.20 s4.80 s6.40 s8.40 s11.20 s
FED14.40 s16.41 s18.81 s21.21 s22.81 s
CFRBFMTemperature3.60 s5.20 s7.20 s9.61 s11.61 s
Visibility4.00 s5.20 s7.20 s10.00 s11.61 s
FED68.81 s101.22 s135.64 s159.62 s186.45 s
Table 7. Fire room size of same aspect ratio condition.
Table 7. Fire room size of same aspect ratio condition.
PropertiesW (m)L (m)H (m)
Case 1222.2
Case 244
Case 366
Case 488
Case 51010
Table 8. ASET for each building finishing material under same aspect ratio conditions.
Table 8. ASET for each building finishing material under same aspect ratio conditions.
PropertiesCase
12345
Polyurethane foamTemperature3.20 s6.00 s8.80 s11.20 s13.21 s
Visibility3.20 s6.00 s8.80 s11.20 s13.61 s
FED8.40 s12.40 s16.00 s22.81 s28.82 s
MDFTemperature3.20 s6.00 s10.40 s17.61 s24.42 s
Visibility3.20 s8.40 s12.40 s17.61 s23.61 s
FED14.40 s22.01 s27.61 s36.03 s41.65 s
CFRBFMTemperature3.60 s7.20 s11.61 s41.22 s167.62 s
Visibility4.00 s7.20 s17.21 s36.81 s56.81 s
FED68.81 s156.02 s250.81 s351.25 s>400.00 s
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Kim, Y.; Rie, D. Evaluation of the Fire Impact of Cellulose-Based Indoor Building Finishing Materials According to Changes in Room Size Aspect Ratio. Appl. Sci. 2024, 14, 5108. https://doi.org/10.3390/app14125108

AMA Style

Kim Y, Rie D. Evaluation of the Fire Impact of Cellulose-Based Indoor Building Finishing Materials According to Changes in Room Size Aspect Ratio. Applied Sciences. 2024; 14(12):5108. https://doi.org/10.3390/app14125108

Chicago/Turabian Style

Kim, Yongjoo, and Dongho Rie. 2024. "Evaluation of the Fire Impact of Cellulose-Based Indoor Building Finishing Materials According to Changes in Room Size Aspect Ratio" Applied Sciences 14, no. 12: 5108. https://doi.org/10.3390/app14125108

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop