2.1. Statement of the Problem
During the initial design phase of an embedded wall, it is preferable to minimize the use of anchors and pins. In cases where the goal is to avoid these additional supports entirely, accurate estimation of wall displacement becomes crucial since the free-standing body of the free embedded cantilever wall (FECW) relies solely on passive pressure.
Figure 1 illustrates an example of a FECW.
Currently, displacement analyses are typically performed using finite element (FE) methods. However, FE methods can be time-consuming and expensive compared to manual calculations. The FE-based formulae presented in this study aim to simplify the wall-type selection process during the initial design phase. These formulae are specifically developed for estimating horizontal displacements at the “wall-top” and “wall-bottom” locations, as indicated in
Figure 1.
Around the FECW, two distinct zones are defined: the “wall-back” and “wall-front” zones. The wall-front zone refers to the retaining zone where passive earth pressure develops above the point of rotation. The distribution of passive pressure in this zone typically follows a parabolic shape (as shown in
Figure 1b, based on Padfield and Mair [
5]). However, for practical purposes, this distribution is often simplified to a triangular shape (as depicted in
Figure 1c). In the wall-back zone, the active pressure distribution predominates above the point of rotation (as shown in
Figure 1b,c). Below the point of rotation, the pressure state lies somewhere between active and passive. For simplicity in practice, the active and passive pressure are inverted below the point of rotation (as illustrated in
Figure 1c).
The wall-back zone is further subdivided into three zones, Zone 1, Zone 2, and Zone 3, while the wall-front zone is referred as Zone 4. Each of these zones is characterized by specific components, including soil unit weight (γ), soil friction angle (ϕ), wall–soil interface friction angle (δ), and soil modulus (E). The corresponding subscripts 1, 2, 3, and 4 are added to denote the components specific to each zone. The flexural rigidity of the wall (EI) is also taken into account. It is assumed that the water table is located at the wall-bottom (
Figure 1).
2.2. Validation of the FE Model with Chavda et al. [20]
Chavda et al. [
20] conducted laboratory tests using a sand-filled box, where polyacetal rods were employed to retain the soil (as depicted in
Figure 2). The length of each rod was 405 mm, and they varied in diameter between 8 mm, 10 mm, and 12 mm, depending on the specific test configuration. The rods were tightly aligned with no gaps between them. The relative density of the sand was adjusted to 15%, 35%, 65%, and 85% across different test configurations.
In each test, a 50 mm section of the sand was excavated, and horizontal displacement readings were obtained using a linear variable differential transformer (LVDT) positioned at the top of the middle rod. To validate the test results, Chavda et al., 2017 performed three-dimensional (3D) finite element (FE) modeling using the PLAXIS-3D software. They compared the results obtained from the tests with the corresponding FE results for three configurations, wherein the rod diameters were 8 mm, 10 mm, and 12 mm, respectively.
In this study, a two-dimensional (2D) finite element (FE) mesh of the validation model was created using the MIDAS GTS NX (ver. 2019-1.1) software.
Figure 3 presents the details of the mesh configuration. The longitudinal dimensions of the actual test conducted by Chavda et al. [
20] were adopted, along with other relevant dimensions. In the FE program, the polyacetal rods were modeled as beam elements, and the flexural stiffness (EI) was automatically calculated by the software for a depth of 1 m.
Staged construction was employed in the FE model analyses. In the first construction step, the initial geological stresses were calculated, and the displacements were set to zero. In the second step, the beam (wall) was activated, and the displacements were once again set to zero. In subsequent stages, a layer of soil with a height of 50 mm was removed, as shown in
Figure 3. This process was repeated five times.
In the reference study, the internal friction of the sand was determined through direct shear tests, while the soil modulus was estimated from a plate load test conducted in the sand box. Various relative density levels were examined, namely, 15%, 35%, 65%, and 85%. In this study, the test performed in the sand box at a relative density of 35% was incorporated. The sand with a relative density of 35% had a unit weight (γ) of 14.72 kN/m3 and an internal friction angle (ϕ) of 30°. The soil modulus at 35% relative density, which was determined based on the plate load test, was relatively small, namely, 1365 kPa. In the reference study, the soil modulus value was estimated as 3000 kPa for the sand with an 85% relative density. It is worth noting that the soil modulus of clean sand tends to increase with increasing confining pressure. Considering the relatively small confining pressure developing in the test box, the range of soil modulus values falls within a reasonable range.
The soil in the FE model was simulated using the Mohr–Coulomb soil model. In a typical FE mesh, it is important to have a sufficiently small mesh size in the area of interest. In this validation study, the critical area was around the polyacetal rods with a mean diameter of 10 mm, which were modeled as beam elements. To ensure continuity around the rods, similar-sized mesh elements with mid-side nodes (10 mm × 10 mm quadrilaterals) were employed. The rest of the model was also meshed with 10 mm × 10 mm elements, although a coarser mesh would have been sufficient (as shown in
Figure 3).
The 2D mesh included horizontal fixities on the sides and vertical fixities at the bottom, as depicted in
Figure 3. The analysis condition of the model was assumed to be plane-strain, meaning that no strains develop in the out-of-plane direction. Although the model is 2D, the MIDAS GTS NX program handles the stiffness matrix in three dimensions. Therefore, for compatibility purposes, fixities were included in the out-of-plane direction (Z direction) at the nodal points. The unit weight and modulus of elasticity of the polyacetal rods were reported to be 14.55 kN/m
3 and 3,000,000 kPa, respectively. All input parameters reported in the reference study were adopted “as is” except for the internal friction of the sand, which was set to 30.75° instead of 30°. This adjustment was made because the 2D FE system collapsed at the last excavation stage when the internal friction angle was set to 30° (
Table 1). However, Chavda et al. [
20] was able to achieve reasonably close results using a 3D FE model with an internal friction angle of 30°. The small difference in friction angles is considered reasonable since the reference study used a 3D model. To the best of the author’s knowledge, 3D models tend to yield slightly better results compared to 2D models. Additionally, small variations in the friction angle were extremely critical in this study because the system was close to failure after the last excavation step. Around the wall, the soil–wall interface friction angle was set to 60% of the internal friction angle (
Figure 3). The relationship between the internal friction angle (ϕ) and the soil–wall interface friction angle (ϕ
int) can be expressed using the following equation:
Based on
Figure 4, the displacements obtained from the MIDAS GTS NX program for rod diameters of 8 mm, 10 mm, and 12 mm were compared with the test and PLAXIS 3D analysis results conducted by Chavda et al. [
20]. The comparison shows that the results from the MIDAS GTS NX program are reasonably close to the experimental and PLAXIS 3D analysis results.
2.3. Validation of the FE Model with Basha et al. [21]
Another example of a test on the displacement characteristics of the cantilever walls has recently been performed by Basha et al. [
21], who measured the displacement of a cantilever wall embedded in sand contained by a steel-reinforced tank 3300 mm in length, 2000 mm in height, and 300 mm in width (
Figure 5a). The cantilever wall consisted of 6 reinforced concrete piles 60 mm in diameter and 1500 mm in length. The piles overlapped with each other and were centered at a distance of 48 mm (
Figure 5b). The tests were performed at two different relative densities for sand, namely, 60% and 80%. In each test, a uniform surcharge pressure applied on the surface behind the wall (4 kPa, 8 kPa, or 12 kPa). In each test, the sand in the front of the wall was excavated at a maximum depth of 750 mm. The minimum embedment depth of the wall was 750 mm. The horizontal wall displacement was recorded at 250 mm, 500 mm, and 750 mm excavation depths.
The test configuration with 8 kPa surcharge pressure and 80% relative density was applied to the FE model. The FE configuration of Basha et al.’s test was similar to that of test by Chavda [
20]. The details of the mesh are illustrated in
Figure 6.
The material properties used in the finite element model are presented in
Table 2, along with the ones provided in the reference study. The two most critical parameters for the wall displacement are the internal friction angle and the soil modulus. The maximum value given in the reference study for the internal friction angle (42.9°) was adopted, due to the fact that the sand was in dense state and the horizontal displacement developed in the tests did not indicate a condition in which the sand behind the wall was close to the failure. Janbu offered an equation where the initial soil modulus is an exponential function of confining pressure
σ3 (Equation (2)) [
24]. Exponent “
n” is typically given as 0.5 for dense sand (Duncan and Chang [
25]).
Chavda et al. [
20] estimated the soil modulus of the sand with 85% relative density as 3000 kPa. Assuming that the unit weights of dense sand at both tests were more or less equal, the mean wall backfill depth can represent the confining pressure. The mean wall backfill depth in the test by Chavda et al. [
20] was 250 mm/2 = 125 mm. The same height was 750 mm/2 = 375 mm for the test by Basha et al. [
21]. In this case, using Equation (2), the corresponding soil modulus for the test by Basha et al. will be 3000 kPa × (375 mm/125 mm)0.5 ≈ 5200 kPa (
Table 2). The pile-wall was modelled as a beam element with an equivalent thickness of 50 mm (
Figure 5b).
The displacements obtained from the MIDAS GTS NX program and the test performed by Basha et al. [
21] were compared in
Figure 7. The results from two sources came out to be very similar. The agreement between the numerical analysis and the experimental results provides confidence in the accuracy and reliability of the FE model for simulating the behavior of the free embedded cantilever walls.
2.4. The Setup of FE Model for Formula Derivation
The equations for FECWs were derived utilizing 431 FE model configurations. The overall mesh configuration varied with respect to the wall size. A representative mesh configuration is presented in
Figure 8. The heights (H) of the walls ranged from 1 to 8 m, and, for each wall height, a common mesh was used as a base from which different sub-configurations could be derived. These meshes are presented in
Section S2, Figures S1–S8. The embedment depth (d) varied from 0.6 H to 1.2 H. For example, to derive different embedment depths, the length of the beam was changed in the common mesh. Further various sub-configurations could be derived by only changing the soil modulus and unit weight and internal friction angle of the common mesh.
The mesh size was determined based on a convergence optimization procedure. The details of this procedure are given in
Section S3. In all mesh configurations, quadratic mesh elements with mid-side nodes were used and the size of the mesh element was 50 mm around the beam, whereas it was between 100 and 250 mm on the sides. During the analyses, staged construction was adopted. After the generation of initial stresses, 0.5 m- to 2 m-thick layers were removed and the displacements on the wall beams were recorded.
Table 3 summarizes the parameter ranges used in the 431 finite element (FE) model configurations for the analysis of free embedded cantilever walls (FECWs). These parameters, along with their variations, are also visually presented in
Figure 1 and
Section S1. The friction angles (ϕ
1, ϕ
2, ϕ
3, and ϕ
4) were varied between 25° and 42°. The wall–soil interface friction angles were set to 0.6 times the corresponding soil friction angle (0.6ϕ
1, 0.6ϕ
2, 0.6ϕ
3, and 0.6ϕ
4). The surcharge load intensity ranged from 0 kN/m to 15 kN/m. The unit weight of the soil and the soil modulus varied between 16–24 kN/m
3 and 10–250 MPa, respectively. The wall height ranged from 1 m to 8 m. The flexural rigidity of the wall, represented by the product of the bending modulus and the moment of inertia (EI), ranged from 2500 kN·m
2 to 20,000,000 kN·m
2. This range includes different types of walls such as soldier piles, sheet piles, contiguous piles, secant piles, and concrete diaphragm walls (Long et al. [
10]). These parameter ranges were utilized to cover a wide spectrum of practical scenarios and to study the behavior of FECWs under various conditions.