1. Introduction
High penetration of PV systems into AC systems reduces the grid strength, i.e., the AC system short circuit ratio (SCR) is reduced. The reduction in the SCR is due to a high impedance of long transmission lines connecting the PV systems, which are located far away from load centers [
1]. In addition, the reduction in the SCR may also be due to the increased level of penetration of the inertialess PV system [
2]. The grid strength is described by the SCR, where a weak grid is defined by the SCR < 3 [
2]. With the increasing level of PV system penetration into the grid, the system stability becomes a challenging issue, as the grid becomes weak [
3,
4,
5]. PV systems are connected to the grid through VSCs [
6], which are controlled to inject a clean current to the grid.
The main method used to control VSCs is based on vector control in the synchronous reference frame (
dq) [
7,
8,
9]. Vector control consists of cascaded control loops containing a DC link voltage controller (DVC), a PCC (point of common coupling) voltage controller (AVC), and an inner current loop controller (CC) [
10]. The DVC regulates the terminal voltage to follow the reference level by generating the active current reference, while the AVC regulates the PCC voltage to produce the reactive current reference. Furthermore, the CC regulates the current flowing into the grid to follow the reference set by the outer loop controllers. Apart from control loops, a PLL is necessary for the synchronization process of the VSC to the grid [
11].
Stability issues encountered in distributed PV systems connected to a weak grid could be due to the physical dynamics of the PV system, to the control loop interactions or to the combination of both. To investigate the causes of the unwanted oscillations in power systems with high penetration VSC interfaced sources, many methods have been developed. References [
1,
12,
13] proposed a reduced small-signal model to investigate the effects of outer control loops, grid dynamics and PLL on the system stability. The model only addresses the causes of low-frequency oscillations encountered when the inverter interacts with a weak grid. It has been found that the PLL, outer control loop (which includes the PCC voltage controller and DC link voltage controller), and the grid strength are the main cause of low-frequency instability issues [
4,
14]. The same results have been revealed in [
5,
15], when a full order or accurate small-signal model of the system as called by the author was used. These forms of instabilities are quite challenging and limit the integration of solar energy into the grid system. Therefore, in order to cope with the instabilities caused by the high integration of PV systems into a weak grid, different control methods are generated.
An improved PLL system has been proposed [
16,
17]. The proposed PLL uses a virtual impedance to compensate for the voltage drop across the line impedance in order to extend the operational capability of the system. The proposed control method yields good performance. However, such control strategies do not decouple the control loop interactions. The impact of control loop interactions was addressed in [
7], where a multivariable controller was turned using H_inf. Nevertheless, the outer loop controllers were turned without considering the effects of PLL. An alternative robust vector current controller was proposed considering the effects of PLLs [
3]. In reference [
5], the author proposed a control method to damp the low-frequency oscillations, where the measured PCC voltage is used to update the
d-axis current reference, while in [
4], the author uses the measured grid current and PCC terminal voltage to set the DC link voltage reference level. All the above-mentioned methods aim to stabilize the VSC system interacting with a weak grid.
All models presented in the above sections lack a deep understanding of the degree of system control loop interactions. In addition, high-frequency instabilities that may be due to the control loop and grid interaction have not been touched. Therefore, in order to address the aforementioned problems, this paper proposes a simplified full order model that reflects on high and low-frequency instabilities.
For a weak grid, the ac terminal voltage is sensitive to the change in active power, which is controlled through the DC-link voltage controller. As a result, the DC-link controller, the ac-voltage controller that regulates the ac terminal voltage and the PLL are dynamically coupled. The resonance oscillations may take place due to those loops coupling. Thus, a decoupling methodology is required to limit the interaction between the DC-link controller, AVC controller and the PLL. Therefore, a simple compensation method that aims to damp the low-frequency oscillations induced by the outer control loop, the PLL and the grid dynamics, is proposed.
The proposed method uses the DC-link voltage error deviation to generate the additional reactive current reference. The obtained compensating reactive current is added to the reactive current reference from the PCC voltage control loop. By updating the reactive current reference with respect to the DC-link voltage, the instability issues induced by the control loops coupling are overcome. Further, the proposed control strategy also benefits from easy implementation and good robustness against AVC, DVC and PLL bandwidth variation, as well as the grid strength variation. The performance of the proposed method is evaluated by using the small-signal stability analysis based on the derived small-signal model. At last, but not the least, the comparative evaluation of the proposed control method with the conventional control method is performed.
The rest of the paper is structured as follows: in
Section 2, the configuration of PV generation connected to a weak AC grid is described and its small-signal model, including PV generator, control loop dynamics, VSC power stage and grid model is derived. The stability analysis of conventional control method is presented in
Section 3 and a proposed low-frequency oscillations damping method is presented in
Section 4.
Section 5 presents a comparative stability analysis of the conventional method and the proposed method, while in
Section 6, the simulations results are presented. Finally, the conclusions are drawn in
Section 7.
3. Characteristics of PV Generator and its Mathematical Model
The main building block of a PV generator is a PV cell that converts solar energy to electrical energy. Due to the low power generated by PV cells, they are combined in series and parallel configurations to form a PV module, which can be also parallel and serially configured to form PV panels to increase power. Furthermore, PV arrays are combined in series and parallel configurations to generate the required power and produce the required DC link voltage. In compact and simple ideal form representation, a PV generator is modeled using a single diode model, due to its simplicity and accuracy. The model presented in
Figure 2 contains the current source representing the photonic current generated by the PV cell, where that current mainly depends on solar irradiance and the cell temperature, the parasite diode (D), parallel resistor (
Rp) and series resistance (
Rp).
Mathematically, the simplified ideal PV module used to capture solar energy and convert it into electrical can be modeled by its V-I characteristics as expressed as in Equation (1) [
19,
20,
21] when the parasite resistances are ignored.
where the PV characteristics parameters in Equation (1) such as:
q = (1.602 × 10
−19 C) is the electron charge,
K = (1.38 × 10
−23) is the Boltzmann constant,
T is the module temperature,
Iph is the photon current,
Irs is the saturation current and A is the ideality factor.
ns and
np represent the number of the interconnected PV module in series and parallel, respectively. The photonic current of the PV generator is determined as indicated in Equation (2), and it is linearly dependent on the solar insolation.
The module temperature affects the photonics current as well.
where
Tref is the module reference temperature,
Isc is the module short-circuit current at the reference temperature,
G(W/m
2) is the solar insolation and
Kt is the module temperature coefficient.
The output power extracted from the PV array can be obtained using Equation (3), where the generated power depends on the solar insolation and the terminal PV voltage.
Figure 3 shows the output power of the PV generator in the function of the PV terminal voltage at a different level of solar insolation.
In this paper, a Mitsubishi PV array of a model “PVUD190MF5” is considered [
22]. The output power of the PV system under different solar irradiation as a function of the DC terminal voltage, with series-connected modules of
ns = 33 and the parallel-connected string of
np = 16 which can generate 100 KW when working at MPPT, is shown in
Figure 3.
From
Figure 3, the output power of a PV generator at any value of the solar insolation and module temperature varies nonlinearly as a function of the terminal voltage, where it exhibits two zero power points, with one corresponding to the open-circuit voltage and the other to the short-circuit voltage, respectively, and one single maximum power point. It is desirable to operate the grid-connected PV generator to the maximum power point for harvesting the maximum possible power available. Therefore, to guaranty that the PV generator outputs the possible maximum output power under variations of the environmental conditions, the PV terminal voltage is regulated by the MPPT algorithm [
23], to remain closer to the maximum power point voltage (
vmpp). The incremental conductance and P&O (perturb and observe) are the most used due to their accuracy and simplicity in implementation. In this paper, a P&O is adopted.
4. Small-Signal Model of Grid-Connected PV Inverter
Considering both the power part and control system as represented in
Figure 1, the small-signal mathematical model can be derived for stability analysis. The system is considered to be a 3-phase balanced system. All system variables and control loops are represented in
dq reference frame. During steady-state operation, the grid
dq reference frame is oriented with the converter
dq rotating frame, whereas that is not the case when the converter operating is in transient mode. Therefore, the mismatch between the grid reference frame and the converter reference frame is modeled using the grid angle generated by PLL. Note that, as the control loop does not use the grid current, the
Lc inductor may be taken as the grid impedance in combination with
Lg. For simplicity, the variable in the grid
dq frame will be superscripted by “g” while the variable in the converter frame is maintained as it is; the subscript “0” represents the steady-state value of that variable and Δ represents small signal variations around the operating point.
4.1. Frame Transformation
The input variables in grid
dq reference frame are transformed into converter reference using Equation (4a), whereas the output variables of the converter in converter
dq frame are transformed back into grid
dq reference frame through Equation (4b)
where
x =
xd + jxq represents the variable in converter
dq reference frame,
xg = xdg + jxqg represents the variable in the grid reference frame, and
δ is the grid angle output of PLL.
In linearized form around steady-state operating point, the expressions (4a) and (4b) are obtained in Equation (5a–d)
The capacitor filter dynamics and grid inductor current through Lg + Lc are the only ones modeled in grid dq frame, while the remaining are modeled in the converter dq frame.
4.2. Phase-Locked Loop (PLL)
The conventional second-order SRF–PLL in [
11] is used to measure the grid angle. As can be seen in
Figure 1b, it consists of
abc/dq transformation, a PI regulator and VCO (voltage controlled oscillator) represented by the integrator. The
PIpll controller regulates
q-axis voltage to zero and outputs the grid rotation frequency deviation with respect to nominal frequency. Since the
q-axis voltage is regulated to zero, the
d-axis voltage always aligns with the capacitor voltage vector. Afterward, the sum of the angular frequency deviation and the reference angular frequency are integrated to generate the grid angle.
The mathematical equations representing the PLL dynamics are expressed in (6a) and (6b).
where
ωpll is the rotational frequency deviation,
kiω and
kpω are the phase-locked PI integral constant and proportional constant of
PIpll, respectively,
γpll is the PLL integral state and
ωref is the reference angular frequency.
Linearizing the Equation (6a,b), a state-space representation of PLL is obtained in (7).
where
xpll = [
δ,
γpll]
T,
Apll and
Bpll are the state matrix and state input matrix,
Cω and
Dω are the angular frequency output matrix and disturbance input matrix, respectively, and
Cδ is the synchronous angle output matrix Due to space limitation, the state-space matrices are not presented here.
4.3. DC Bus Voltage Control (DVC) and AC Voltage Control (AVC)
The outer control loops are responsible for generating the inner current references that flow into the converter. Both AVC and DVC are implemented using the classical PI controller. The DVC processes the error between the reference DC-link voltage, which is generated by the MPPT and the measured DC-link voltage to generate the d-axis current reference. The DC-link stability is guaranteed by maintaining the power generated by the PV generator equal to the power flowing to the grid. The dynamics of the MPT in this model are omitted and their impact on the stability of the system remains a topic for future study. On the other side, the AVC generates the reference reactive inductor current by regulating the d-axis component of the capacitor filter voltage to follow its reference for voltage support purpose.
The mathematical dynamics expressing the AVC and DVC are shown in Equation (8).
where
x1 and
x2 are the state variable of DVC and AVC, respectively;
Kpdc and
kpv are the proportional constants of DVC and AVC PI-controllers, respectively;
Kidc and
kiv are the integral constants of DVC and AVC PI-controllers, respectively; and
idref and
iqref are the
d-axis and
q-axis current references, respectively.
After linearization of equations in (8), the state space equations of outer control-loops results in (9).
where
Aout,
Bout,
Bout1,
Bout2, C
out,
Dout,
Dout1 and
Dout2 are the outer control loops state matrices and
xref = [
vmpp,
vcdref]
T.
4.4. Inner Current Control Loop (CC)
The inner current controller, as shown in
Figure 1b, also uses a PI-controller to regulate the current flowing through the filter inductor current. The reactive power is controlled by the
q-axis current, whereas the active power is regulated through the
d-axis current. The current controller tracks the error difference between
idqref and the measured filter
ifdq current error to generate the modulating signal. The
dq-axis feed-forward decoupling and capacitor voltage feed-forward through gain
kv are used for improving the system performance [
24]. The inner loop current controller dynamics are obtained in Equation (10) and after linearization, a state-space model representation is illustrated in Equation (11).
Where
γ1 and
γ2 are the state variable of the current controller,
Ac,
Bc,
Bc1,
Bc2, C
c,
Dc,
Dc1,
Dc2 and
Dc3 are the matrices of the state-space model of the current controller and
vidq* are the output variables of the current controller. We can note that, as the current controller bandwidth was chosen to be 1/5 of the switching frequency, the delay introduced by the modulator may be omitted. This results in
vidq* = vidq.
4.5. Converter Filter Inductor Dynamics
As shown in
Figure 1a, the dynamic model of the inverter side filter inductor in
dq reference frame can be represented in Equation (12), and its linearized state-space model in Equation (13).
where
Af, Bf and
Bf1 are the matrices of the filter inductor state-space model.
4.6. DC-Link Capacitor Dynamics
The dynamics rate of change of DC-link voltage is expressed mathematically by the PV power and grid power imbalance as shown in Equation (14).
where
Ppv and
Pin are the PV power and input power to the inverter, respectively.
The power generated by the PV generator depends on the solar insolation and temperature (see Equation (3)). The input power to the VSC can be expressed as in (15).
The linearized DC-link dynamics is shown in (16).
To include the PV generator dynamics in the model, the expression (17), is obtained from Equation (3).
where
Gd is the conductance of the PV generator.
The state-space model of the DC link is obtained in (18) from (16) and (17).
where
Apv,
Bpv and
Bpv1 are the matrices of DC-link state-space model.
4.7. Grid Dynamics Model
The grid dynamics consist of
Cf, Lc and
Lg. Applying the KVL, the equations describing the grid dynamics can be obtained as in Equation (19).
where
Lt =
Lg +
Lc, vcdqg is the capacitor filter voltage in grid
dq frame,
ifdqg is the filter inductor current in grid
dq frame,
igdqg is the grid side inductor current in grid
dq frame and
edq is the grid terminal voltage in
dq frame.
Linearizing the equations in (19) around the steady-state operating point and taking into account the angular frequency dynamics, the state-space model of the grid side is obtained in (20).
where
xg = [
vcdqg, igdqg]
T, and
Ag, Bg, Bg1 and
Bg2 are matrices of the state-space model of grid dynamics.
4.8. Overall State-Space Model
The overall small-signal representation of the grid-connected PV inverter shown in
Figure 1 is illustrated in
Figure 4. It is obtained by combining the converter and the grid system model as shown in
Figure 4. The linearized aggregate state-space model of the overall system with 13 states variables and 2 input variables, is expressed in Equation (21). Where
Asys is the state matrix of the system,
Bsys is the state input matrix and
Csys is the system output matrix. The proposed system model can easily be extended for multiple inverters operating in parallel, without requiring virtual resistance to define the PCC voltage as in [
25]. However, in this study, a single inverter connected to a weak grid is considered and the stability analysis of parallel grid-connected PV inverters remains a topic for future study.
where
5. Stability Analysis
To analyze the stability of the PV system based on the derived small-signal model, the study system parameters in
Figure 1 are defined in
Table 1. The nominal power of the PV generator is 100 kVA. The inner current loop has been designed with a bandwidth equal to 1/5 of the switching frequency (
fsw). The AVC loop bandwidth was chosen as 20 Hz and a DVC bandwidth of 50 Hz was used. The AVC, DVC and the CC have been designed based on reference [
26] for the specified above bandwidth. The LCL filter values, the parameters of the current controller, DC-link voltage controller, AVC loop controller and PLL controller are defined in
Table 1. The parameters of the PLL controller were obtained as in [
11] for a bandwidth of PLL equal to 10 Hz.
The analysis of the outer control loops interaction when the system operates under weak grid conditions is presented. The impact of control parameters variation on the stability of the system is analyzed based on the eigenvalues sensitivities.
5.1. Control Loop Interaction
From the state-space model, the DC link voltage closed-loop and the ac capacitor voltage closed-loop transfer functions are derived. The bode plots of the transfer functions of the closed-loop are shown in
Figure 5. The frequency response of the DC voltage closed-loop is shown in
Figure 5a when the AVC bandwidth (BW_pcc) is 5 Hz, 10 Hz, 25 Hz and 35 Hz with the DC link controller bandwidth set to 50 Hz, while the PLL bandwidth is 10 Hz.
As shown in
Figure 5a, the AVC has a significant impact on DC-link stability. For low AVC bandwidth; for example, BW_pcc = 5 Hz, the system is unstable due to the peak resonance effects with negative damping ratio induced in low-frequency range. As the AVC bandwidth increases, the low-frequency oscillations are damped and the system becomes stable. This may be due to the fact that when the inverter interacts with the weak grid, the AVC is necessary to stabilize the system. However, increasing the AVC bandwidth impacts the high-frequency oscillations. The high-frequency resonance effects appear to be closer to 1100 rad/s and shift toward 1000 rad/s as the BW_pcc increases.
The high-frequency effects are due to the resonance induced by the LCL filter. As can be seen from
Figure 5, the high-frequency instabilities dominate the DC link channel compared to the ac voltage link channel, as there may be a non-zero amplification gain. Therefore, the AVC bandwidth is selected large enough to limit low-frequency oscillations and must not be high to avoid high-frequency resonances.
Figure 5b shows the AVC closed-loop response with the variation of the DVC controller bandwidth. The lower frequency resonances are amplified when the DVC bandwidth increases closer to the PLL bandwidth and is damped for a DVC bandwidth greater than the PLL bandwidth. The PLL and DVC interactions are portrayed in
Figure 5b.
In the same way, the impact of the PLL bandwidth on the closed-loop AVC is shown in
Figure 5c. For a PLL bandwidth (BW_pll) closer to the AVC bandwidth, for example when BW_pll = 20 Hz and Bw_pll = 25 Hz, the closed-loop system has a negative phase margin, as can be seen in
Figure 5c. As a result, the system becomes unstable. The PLL bandwidth in this case is selected lower than the AVC bandwidth, where a 10 Hz is selected.
5.2. Eigenvalues Analysis
The eigenvalue method is used to assess the system’s stability based on the small-signal model shown in
Figure 4.
Table 2 shows the eigenvalues of the overall system at the steady-state operating point with system values in
Table 1. The corresponding oscillation frequencies and damping ratios for each mode are also presented in
Table 3.
Since all the eigenvalues have a negative real part, the system is stable for the system and control parameters in
Table 1. As can be observed from
Table 2, there exist four groups of complex conjugate eigenvalues that determine the dynamics of the system. Among them, complex conjugates eigenvalues λ
9,10 are closer to the imaginary axis, with a lower damping ratio and a small oscillation frequency of 18.19 Hz. Therefore, eigenvalues λ
9,10 are the critical eigenvalues to determine the system’s stability. The eigenvalues λ
7 8 have the lowest oscillation frequency of 10 Hz. However, they do not affect the system’s dynamics as they have a higher damping ratio. The remaining complex eigenvalues λ
3,4 and λ
5,6 are associated to the
LCL filter, with oscillation frequency closer to the resonance frequency of the
LCL, as can be noted, from
Table 2.
From
Table 3, the participation factor of each state variable in a particular mode corresponding to that eigenvalues are shown. The highlighted participation factors correspond to the dominant state with a participation factor greater than 0.15 for each mode. From
Table 3, it can be observed that the states corresponding to
Lf and
Cf have no impact on critical eigenvalues. The
vcd and
igd states affect the eigenvalues λ
3,4. Thus, the change in DVC and AVC controller parameters will affect the mode λ
3,4.
On the other hand, the vcq and igq states affect the eigenvalues λ5,6; meaning that they are sensitive to PLL parameter changes. The states that affect the critical eigenvalues are the states corresponding to DVC, AVC, Lg and PLL. Therefore, if there is any change in the control parameters of DVC, AVC and PLL, the system’s stability is affected. In addition, any variation in line inductance or line resistance affects the robustness of the system, as they are crucial in determining the strength of the grid. Moreover, the states corresponding to the q-axis current control also impact the critical eigenvalues. This may be due to the fact that the d-axis’ ac voltage is regulated through the q-axis’ current and the q-current determines the voltage drop across the line inductor if the grid Xg/Rg ratio is very high. To understand how all the states enumerated above affect the system’s robustness, a root locus is used to plot the sensitivity for the eigenvalues over the change of control parameters and grid strength. Only the eigenvalues closer to the imaginary axis will be shown on the root locus.
6. Proposed Damping Method for Low-Frequency Resonance Oscillations
As described in the sections above, the coupling effects between the control loops consisting of the AVC, DVC and PLL interacting with the weak grid deteriorate the robustness of the system. Therefore, a control method to damp the low-frequency oscillations by reducing the coupling effects between DC-link voltage loop and AVC loop is proposed. For a PV-inverter connected to a weak grid, the PCC voltage is sensitive to the active power flowing to the grid controlled by
d-axis current through DC-link voltage regulation. Conventionally, the PCC voltage is regulated through
q-axis current control. As the PCC voltage is sensitive to both active and reactive currents when the inverter interacts with a weak grid, a control method that considers the effects of both
d-axis and
q-axis current on PCC voltage to enhance inverter robust performance is proposed. The proposed compensation method, as shown in
Figure 6, modifies the
q-axis current reference by using the DC voltage deviation error. The controller
Kdamp expressed in (22) processes the DC voltage error and generates the compensating additional reactive current reference.
where
Kid is the integral constant and
a is the pole of the integrator, which is chosen to be closer to zero.
The performance of the proposed control method can be analyzed based on the eigenvalues loci generated from the augmented state-space model developed in
Figure 5 by the proposed damping loop dynamics. A comparison of the proposed control method and the conventional control is performed.
The outer loop dynamics in Equation (8) can be rewritten as in Equation (22). Where
x3 is the state variable of the damping loop.
8. Simulation Results
To verify the stability analysis carried out in the previous section, time-domain simulations were performed in PLECS simulation software. The steady-state operating data are shown in
Table 1.
The transient’s response of the DC-link voltage under variation of the solar insolation, system strength, and the outer loop control bandwidth were analyzed. In addition, the grid angle measured by the PLL, and the capacitor d-axis voltage response were also analyzed. It is easier to say that, the transients in DC link voltage are reflected to the active power while the transients in the filter capacitor d-axis are reflected in reactive power when the converter operates under a strong grid. When the inverter is subjected to the disturbances and operate under weak grid conditions, the coupling effects that exist between the terminal capacitor voltage, DC-link power port and the grid dynamics induce large oscillations in reactive power compared to the oscillation in active power.
Figure 14a shows the ac voltage angle response following a step change of PLL bandwidth at time t = 2 s.
Figure 14b shows the DC-link capacitor voltage and
d-axis terminal ac voltage when the PLL bandwidth frequency is subjected to a step change from 5 Hz to 20 Hz at time t = 2 s. The growing oscillations resonating at a frequency of 24.8 Hz in both DC link voltage and ac
d-axis voltage are yielded when the PV inverter is controlled by the conventional method. The instabilities are due to the presence of positive eigenvalues caused by the PLL bandwidth increase, as described in previous sections. However, when the proposed control system is activated, the system performance is well damped, regardless of the step-change in frequency at 2 s. Therefore, the robustness of the system over any change in the PLL bandwidth is improved as presented in the analysis.
Figure 15a,b shows the transients’ response of the output DC link voltage,
d-axis ac voltage and the grid voltage angle for a step-change in AVC control bandwidth. As can be observed from
Figure 15, the system becomes unstable when the AVC bandwidth frequency changes from 20 Hz to 5 Hz, if the system is under conventional control method. Growing undamped oscillations that oscillate at 9.22 Hz are induced. Compared to the conventional control method, the proposed control system maintains the system’s stability, even for a low AVC control bandwidth, as can be observed in the results presented in
Figure 15. With the proposed control, flexibility in designing the AVC controller is achieved. This is because the system is robustly stable over a large range variation of the AVC controller bandwidth.
Figure 16a shows the output response of the grid angle when the grid strength changes, and
Figure 16b shows the DC-link voltage and ac
d-axis voltage. The grid inductor changes from
Lg = 4.5 mH to
Lg = 5.15 mH at 1 s. Based on
Figure 16a,b, it is observed that, for a step change of grid inductance that characterizes the grid strength, the induced oscillations die away with time in both control methods. However, for the proposed method, the system oscillations are rapidly damped compared to the traditional method. For both output voltage and grid angle, the steady-state is attained at time 1.3 s for the proposed control, whereas for the conventional method, the steady-state is reached at time 1.8 s. Furthermore, the transient overshoot for the proposed control is reduced compared to the conventional method.
For the convention method, the peak to peak overshot of 0.1 radians, 0.2 P.U and 0.03 P.U for grid angle,
d-axis ac voltage and DC-link voltage, respectively, are obtained. The peak to peak overshoot when the oscillation damping control method is applied becomes 0.13 radians, 0.125 P.U and 0.0075 P.U for grid angle,
d-axis ac voltage and DC-link voltage, respectively. The same performance can be observed in
Figure 17b showing the output reactive power and active power under step change of grid inductance. Higher reactive power overshoots of 0.08 P.U for undamped system and 0.05 for the proposed control are yielded.
Apart from control and the system parameter, another factor affecting the stability of the system is the power rating of the system. The power rating depends on the solar insolation, which can change depending on weather conditions.
Figure 17b shows the output power response,
Figure 18a shows the grid voltage angle and
Figure 18b shows the DC-link and ac
d-axis voltage for solar insolation changes from 900 W/m
2 to 1100 W/m
2. Following that step change of solar insolation, the DC-link voltage changes from 1.07 P.U to 1.083 PU, whereas the active power changes from 0.785 to 0.97 PU. Correspondingly, the reactive power changes from 0.14 to 0.26 PU. Based on the results shown in
Figure 17, a highly damped response is produced while the proposed method is used. It can be observed that the system remains stable in both control methods as the oscillations resulting from a step-change in solar insolation die away. However, the settling time for the proposed method is shortened to 0.2 s from 0.6 s (for the convention method). In addition, similar to the analysis carried above, the transient overshoots of the proposed method are very low compared to the response of the undamped system. For the damped system, the reactive power overshoot is 0.01 PU, while the undamped system yields 0.09 PU, the ac capacitor voltage angle overshoot is 0.15 radians and 0.075 radians for conventional and proposed control method, respectively. In addition, the overshoot of
d-axis ac voltage is 0.15 P.U and 0.05 for the conventional and proposed methods, respectively.
9. Conclusions
This paper firstly analyzed the stability of a single-stage PV inverter connected to a weak grid. The small-signal stability analysis was performed to evaluate the conventional control method’s performance and highlighted possible sources of instabilities. The main sources of instabilities were found to be the grid dynamics, the outer control loops and the PLL. The interaction of outer control loops of the inverter and the weak grid could worsen the system’s stability, thus limiting the level of integration of the grid-connected PV inverter. In order to boost the performances of the grid-connected PV inverter, a control methodology that could limit the control loops interaction was proposed. The proposed control method employs DC-link voltage error to modulate the reference reactive power current flowing into the grid.
The results of simulation in PLECS were presented to verify the performance of the proposed control methodology over the conventional method. According to the simulation results, the proposed system achieves improved system responses compared to the conventional control method. For the proposed control method, the enhanced oscillations damping and reduced transients overshot are guaranteed for a large variation range of the DC-link, PCC voltage and PLL controller bandwidth. Furthermore, the system’s robustness is improved, even when the inverter is connected to a very weak grid, thanks to the proposed controller. The simulation results confirm the robust performance of the derived small-signal model and the proposed low frequencies damping method.