1. Introduction
The T-type three-level PWM converter has a merit in terms of harmonic reduction by generating a multi-level output voltage waveform compared to the traditional 2-level PWM converter. Also, it can reduce conduction loss compared to a similar NPC three-level PWM converter, so it is widely considered as a candidate in low voltage applications [
1,
2]. Therefore, many studies are being conducted to utilize the T-type three-level PWM converter in various applications [
2,
3,
4,
5,
6,
7].
However, in the T-type three-level PWM converter, neutral point voltage control is essential for stable operation, and it carries out various neutral point voltage control between the upper and lower DC-link voltages depending on the application field [
3,
8]. To accomplish this purpose, an offset voltage is normally used, and the resultant neutral point current is inserted to the output DC-link side.
In a balanced load condition, the offset voltage is not necessary because the required neutral point current is zero. On the other hand, in an unbalanced load condition, an enough offset voltage should be provided to generate the required neutral point current value. Since this offset voltage does not affect the whole DC-link voltage and three-phase sinusoidal input current, only upper and lower DC-link voltages control can be effectively performed. However, the amount of offset voltage that can be applied is limited and varies depending on the given system specification. This implies that the balance control of the upper and lower DC-link voltages may not be achieved according to the unbalanced load condition, and means that the maximum allowable unbalanced load condition exists in the T-type three-level PWM converter.
Therefore, in this paper, based on the analytical modeling derived for the neutral point current in the T-type three-level PWM converter [
9], the maximum allowable unbalanced load condition for the balance control between the upper and lower DC-link voltages is theoretically analyzed. Through this, it is possible to verify in advance how much the unbalanced load condition can be accommodated for the stable operation in the T-type three-level PWM converter system. To analyze this condition, a space vector PWM-based T-type three-level PWM converter operation was assumed, and simulations and experimental tests were conducted to verify its effectiveness.
3. Allowable Unbalanced Load Conditions
Based on the analytical result for the neutral point current, in order to analyze the allowable unbalanced load condition in the T-type three-level PWM converter, the equivalent circuit for the converter’s output side was used as shown in
Figure 4.
Through the balanced three-phase values, the following equation is satisfied.
Here, the ip and in are the positive and negative side instantaneous output current, respectively.
In steady state, the average current flowing through the capacitor becomes zero, so the neutral point current can be expressed as follows.
Here, the capital letters mean the average value of each current shown in
Figure 4.
From (11) and (13), the required offset duty in the system is expressed as follows.
From (14), it can be known that the offset duty is not required under a balanced load condition (IL = IH), while some offset duty is required under unbalanced load conditions (IL ≠ IH).
However, the required offset duty should be smaller than the maximum possible offset duty that is allowable in the system, and it is given by (15) under the space vector PWM based operation.
Here, the modulation index (m) is calculated from (5) through the system specification.
In other words, the maximum possible offset duty (
dos_max) in (15) is a value determined by the converter’s topology and operational point, which means any unbalanced loads can be controlled by applying the required offset duty without changing the hardware if the condition of (15) is satisfied. However, in case of out of that condition, it can be solved through additional circuit configuration such as voltage balancer [
11,
12,
13,
14].
Figure 5 shows the maximum possible offset duty (
dos_max) and the actually required offset duty (
dos) under unbalanced load conditions based on the system specifications in
Table 1. The grid current (
Ig) in (14) can be calculated by using the output power (
Po) and the grid line-to-line voltage (
Vg,ll) given in
Table 1.
While the upper load was fixed at 100%, the change in duty was monitored by gradually decreasing the lower load as shown in
Figure 5 where Δ
P(
%) corresponding to the horizontal axis is expressed as (17).
It can be seen that the required offset duty (dos) increases as the difference in each output power increases. Until the required offset duty (dos) is smaller than the maximum possible offset duty (dos_max), the balance control of each DC-link voltage is well performed even under unbalanced load conditions. However, when the difference in output power becomes greater than about 43%, the required offset duty (dos) exceeds the maximum possible offset duty (dos_max) so that balanced output voltage control cannot be maintained anymore. This allows determination of the maximum allowable unbalanced load conditions for a given system.
4. Simulation and Experimental Results
Simulations were performed through PSIM to verify the analyzed allowable unbalanced load conditions.
Table 1 shows the system specifications and parameter values used in the simulation.
Figure 6 shows the operational waveforms under a balanced load condition. Each 100% load was applied to both upper and lower DC-link voltages, and the three-phase sinusoidal grid voltages and currents were controlled to be in phase. Since the real neutral point current (
io) is a pulsating waveform due to the PWM operation, the averaged neutral point current (
io_Ts) at every sampling period was measured. As expected, the average neutral point current value during one grid period was zero due to the balanced load condition. Also, it can be seen that the upper and lower DC-link voltages (
vH and
vL) maintained a balanced state. As well, no offset duty was applied to the final duty (
doa), in other words, the final duty (
doa) was symmetrical based on 0.5.
Figure 7 shows the operational waveforms under unbalanced load conditions. In both cases, 100% load was applied to the upper DC-link, and the load connected to the lower DC-link was reduced.
Figure 7a is a condition where the output power deviation (Δ
P) corresponds to 40%. Thus, the offset duty was included in the final duty (
doa), and it can be seen that the final duty was shifted to the upper side as a whole. Nevertheless, as expected in
Figure 5, it corresponds to the condition that the balance control can be performed, and the upper and lower DC-link voltages maintain a balanced state. However,
Figure 7b is a condition where the output power deviation (Δ
P) corresponds to 45%, and the final duty (
doa) is caught at the upper limit, so the relevant balance control cannot be performed. This is also consistent with what is expected in
Figure 5, and the upper and lower DC-link voltages show an unbalanced state.
Figure 8 shows the photograph for the experimental test.
Figure 9 shows the experimental waveforms under a balanced load condition. Each 100% load was applied to both the upper and lower DC-links, and the unit power factor control was satisfied by controlling the phases between the grid line-to-line voltage (
vgab) and grid phase current (
iga) to be π/6. Also, the neutral point current (
io) was an averaged waveform at every sampling period, and it can be seen that the average value was zero due to the balanced load condition. Also, the upper and lower DC-link voltages (
vH and
vL) were balanced, and the final duty (
doa) was symmetrical with respect to 0.5.
Figure 10 and
Figure 11 show the experimental waveforms under unbalanced load conditions. First,
Figure 10 shows the waveforms corresponding to 100% load at the upper DC-link and 60% load at the lower DC-link, which is a condition where the output power deviation (Δ
P) corresponds to 40%. Due to the total load reduction, the peak value of the grid current (
iga) was decreased compared to
Figure 9, and the average value of the neutral point current (
io) was also decreased to about −3.2 A because of the unbalanced load. Nevertheless, the offset duty was applied to the final duty (
doa), and thus the duty was shifted upward as a whole. Thus, as expected in
Figure 5, each DC-link voltage maintained a balanced state.
Figure 11 shows the waveforms corresponding to 100% load at the upper DC-link and 55% load at the lower DC-link, which is a condition where the output power deviation (Δ
P) corresponds to 45%. The final duty (
doa) was caught at the upper limit, and the relevant balance control was not achieved, which is consistent with what is expected in
Figure 5. Therefore, it was confirmed that the upper and lower DC-link voltages are not regulated equivalently.
Thus, the analysis for the allowable unbalanced load condition in the T-type three-level PWM converter was verified through the simulation and experimental results.