Next Article in Journal
Energy and Demand Forecasting Based on Logistic Growth Method for Electric Vehicle Fast Charging Station Planning with PV Solar System
Next Article in Special Issue
A Review of Denial of Service Attack and Mitigation in the Smart Grid Using Reinforcement Learning
Previous Article in Journal
Fractionation of Lignocellulosic Fibrous Straw Digestate by Combined Hydrothermal and Enzymatic Treatment
Previous Article in Special Issue
A Two-Level Model Predictive Control-Based Approach for Building Energy Management including Photovoltaics, Energy Storage, Solar Forecasting and Building Loads
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Virtual Inertia Adaptive Control Strategy of ESU in DC Microgrid

1
Department of Electrical Engineering, Harbin Institute of Technology, Harbin 150001, China
2
State Grid Weihai Supply Company, Weihai 264200, China
3
Department of New Energy, Harbin Institute of Technology at Weihai, Weihai 264200, China
4
Electric Power Research Institute, State Grid Shandong Electric Power Company, Jinan 250000, China
*
Author to whom correspondence should be addressed.
Energies 2022, 15(17), 6112; https://doi.org/10.3390/en15176112
Submission received: 25 May 2022 / Revised: 8 August 2022 / Accepted: 18 August 2022 / Published: 23 August 2022
(This article belongs to the Special Issue Smart Grids and Renewables)

Abstract

:
With the increasingly obvious DC characteristics at both ends of the source and load sides of the low-voltage distribution network, the application scenarios of low-voltage DC microgrid gradually appear. Compared with the AC system, the DC microgrid has the characteristics of low inertia, weak damping, and poor anti-disturbance capabilities, all of which are important for improving operational stability. A virtual inertia adaptive control approach for fast-tracking energy storage under varied disturbances is presented using energy storage as a virtual inertia unit. Firstly, a stability analysis model including constant power load is constructed for the low-voltage DC microgrid; then, the control logic of the virtual inertia of the energy storage system is designed. Finally, the corresponding model is built in MATLAB/SIMULINK and the experiment platform to verify the correctness and effectiveness of the proposed control strategy.

1. Introduction

With the strategic goals of “Dual Carbon” and “New Power System”, applications such as the zero-carbon and low-carbon elements represented by distributed photovoltaics, electric vehicle charging piles, and distributed energy storage will thrive in the microgrid. It will result in large-scale, disorderly, and decentralized access to the low-voltage distribution network, posing serious difficulties to its current management and control systems [1,2,3]. The above zero-carbon and low-carbon elements listed above all exhibit DC properties. To perform the orderly management and active control of DC-type power sources, loads, and energy storage elements, partial networking is carried out through low-voltage DC. This is an effective way to improve the coordination and interaction of low-voltage sources, power grids, loads, and energy storage, which achieves large-scale local consumption of distributed clean energy and reliable power supply for loads [4].
Although the low-voltage DC microgrid has the technical advantages of simple control objective and high conversion efficiency, it contains a constant power load (CPL) and converter with constant power control, both of which have a negative impedance characteristic, which is detrimental to the system’s stable operation under disturbance [5,6]. Therefore, the research concentrates on the virtual damping or inertia control, and the low-voltage DC microgrid’s stability modeling analysis. The energy storage unit (ESU) can be regarded as a first-order inertia loop, with control research focusing on how to improve the system’s equivalent inertia and effectively cope with powerful impacts. Refs. [7,8,9] measured the power disturbance, and then decomposed the middle- and high-frequency components by the frequency domain decomposition method as the charging and discharging instructions of energy storage to stabilize the fluctuation. Ref. [10] proposed a parallel-droop control strategy based on virtual impedance to realize the distributed coordination of different ESUs. Furthermore, Refs. [11,12] distributed the transient power under disturbance based on the ratio of the nominal capacity of each ESU but ignored the impact of the state of charge (SOC) on the transient power support. When the ESU has a low SOC but a big nominal capacity, the power distributed does not match the actual charging and discharging capacity, making it difficult to trace system disturbances, compromising system stability. In [13], an ESU charge and discharge strategy based on switching control retained its SOC within [0.3, 0.7] to realize transient power distribution. These works mentioned are generalized as being result oriented in that they study the transient control of single or multiple ESUs under disturbance. Conversely, the cause-oriented ones conduct modeling analysis and adaptive control of the virtual inertia provided by energy storage in the transient process, thus there has been no investigation into the nature of low inertia and weak damping in the system.
Setting suitable values for key parameters in the control loop is critical for achieving the optimal transient control impact. In addition, the parameter setting is usually obtained through system stability modeling and sensitivity analysis. The stability analysis of the DC microgrid system includes static stability, small disturbance stability, and large disturbance stability [14,15]. The most extensively utilized approach at the moment is small disturbance stability analysis. The impedance approach and the state-space method are also used in small disturbance stability analysis. Refs. [16,17] established an input and output impedance analysis model for a common DC bus microgrid, performed qualitative analysis on the sensitivity of important parameters such as sag using the Middlebrook impedance ratio criteria, and finally specified the parameter’s tolerable value range using the Nyquist curve. However, it is unclear if various converters are separated into input or output impedance in a DC microgrid with a multi-segment bus layout, and certain converters may display distinct impedance characteristics due to different operating modes. In order to acquire the dominating poles of the system, a state-space model was built in [18,19], and then an appropriate value range was achieved by root locus analysis of important parameters. Although the state-space technique may handle the challenge of modeling a multi-bus complex system, it is more difficult to model and calculate than the impedance method.
To address the above issues, this paper firstly elaborates the system structure and configuration on which a virtual inertia control model of ESU is established to derive the virtual inertia configuration in the control process and the distribution scheme among multiple ESUs. Then the system stability analysis model is established, and the key parameters in the virtual inertia are adjusted. The correctness and effectiveness of the proposed control strategy are verified at two levels: time domain simulation and experimental platform construction, respectively.

2. System Structure and Mathematical Modeling

According to their functions or external control features, the internal units of the DC microgrid may be split into two types: (1) Balancing unit, which is the equipment that provides the DC microgrid with stable voltage support. It is usually a microgrid’s grid-connected DC/AC converter or an ESU grid-connected DC/DC converter. (2) Power unit, which is the power-output unit that follows the outer loop reference. In general, it is the load grid-connected DC/DC and photovoltaic grid-connected DC/DC grid-connected converter. In some operating modes, the grid-connected DC/DC converter for energy storage can also be used as a power unit, as shown in Figure 1. The system operation mode is divided into the grid-connected operation mode and the off-grid operation mode. The control strategies and attributes of each unit under different operation modes are shown in Table 1. When the microgrid operates in grid-connected mode, the grid-connected voltage source converter (VSC) is set as the balance unit to control the constant DC voltage, and ESU acts as the power unit to eliminate the power difference in the system or suppress power fluctuations, which is a constant power control in essence. When the microgrid operates in the off-grid mode, grid-connected VSC stops operating. At this time, multiple distributed energy storage systems operate in the droop control strategy to share the power variation in the system and maintain voltage stability. Here, energy storage is used as the inertia support unit, and the super capacitor with high power density is selected as energy storage unit, which is collectively referred to as ESU below. Compared with energy-based energy storage, it can release high energy in a short time to cope with all kinds of disturbances, and at the same time, its long cycle life can cope with frequent charging/discharging command switching when it carries out leveling fluctuations. As for the inner and outer loop control strategies of power and energy storage grid-connected DC/DC converters, there is no difference between the two basic control block diagrams.

3. Adaptive Control Strategy of Virtual Inertia of Energy Storage Unit

3.1. Basic Control Strategy of ESU

ESU bidirectional DC-DC converters can operate in either boost or buck mode and provide bidirectional power delivery. They are usually applied as converters in energy storage systems that are linked to the power grid. The ESU operates in the constant power control mode when connected to the grid, which means that the constant low voltage or constant current control is utilized to charge and discharge according to the required power. In off-grid mode, it operates in droop control mode to regulate the high voltage; in the two extreme cases of power saturation and severe power scarcity, the ESU may also operate in idle mode. The working mode selection and control block diagram of ESU are shown in Figure 2 and Figure 3.

3.2. Virtual Inertia Control Strategy of ESU

The grid-connected VSC controls the voltage in the grid-connected mode system by drooping. Droop is simply a dampening control that cannot monitor disturbances with zero delays. To enhance this, the energy storage control approach is modified to detect the disturbance in VSC response first, releasing inertia promptly to increase system transient performance and assure stability. The continuous low voltage charge and discharge control technique is chosen as the foundation, and the design concept is as follows: the voltage per unit value of the ESU side equals the voltage per unit value of the DC bus side. This assures that ESU is ’directly’ connected to the grid. The improved control strategy is shown in Figure 4.
In Figure 4, u c . i and U c . i are the low-voltage side voltage and the reference voltage of i th ESU; u b u s and U b u s represent the bus voltage and bus reference voltage; i l c . i and i h c . i are the current and the bus side current of i th ESU; and d c . i represents the duty cycle, respectively. Feedforward control is used in inner loop control to increase the voltage dynamic consistency between the energy storage side and the bus side, where F is the feedforward coefficient. The energy storage voltage per unit value is almost equivalent to the bus voltage per unit value:
u c . i U c . i · u b u s . p . u .
where u b u s . p . u . is bus voltage per-unit value. Equation (1) shows that U c . i can reflect the ESU operating level and is also proportional to the amount of released inertia in the transient state. When there is a power disturbance Δ P L . p . u . , the DC bus voltage fluctuates as illustrated in Equation (2).
2 C b u s U b u s 2 2 P G d Δ u b u s . p . u . d t = Δ P L . p . u .
where C b u s is the bus-to-ground capacitor, P G is the reference value of Δ P L . p . u . and LOM1-1, LOM3-1 begin C b u s U b u s 2 2 P G is the inertia stored by the system. Define H m g = C b u s U b u s 2 2 P G . This value is directly related to the inherent equivalent capacitance value C b u s at the busbar. The power per-unit value change of ESU is further derived as shown in Equation (3):
Δ P c i . p u = U c i 2 C c i P G d Δ u c i d t , Δ u c i = U c i Δ u b u s . p u Δ P c i . p u = 2 H c i d Δ u b u s . p u d t , H c i = U c i 2 C c i 2 P G
where Δ u c i = U c i Δ u b u s . p u can be considered the relationship between Δ P c i . p u and Δ u b u s . p u . H c i characterizes the virtual inertia injected into the DC bus by the ith ESU during transient operation. During the transient operation of the system and when more than one energy storage unit is involved, there are two problems: (1) how much inertia in total needs to be allocated to ESU and according to what principle; (2) according to what principle these inertias are distributed among multiple energy storage. First of all, in addition to the inertia response of the system itself in Equation (2), the power dynamic balance of the system in the transient process also involves ESUs, the grid-connected VSC and the load changes. The PV unit in Figure 1 is considered to have constant output power in the transient state, so it does not participate in the dynamic balance of the system power. The power dynamic balance of the system in the transient state is shown in Equation (4).
2 H m g d Δ u b u s . p u d Δ t + 2 s H c · Δ u b u s . p u + G v s c · Δ u b u s . p u + Δ P L . p u = 0
where G v s c is the closed-loop control transfer function of the grid-connected converter, ignoring current inner-loop dynamic effect, G v s c = k p + k i s . H c is the configuration of the total virtual inertia of the ESU, which is the superposition of each subterm H c i . The expression for the DC bus voltage variation is obtained by equivalently varying Equation (5) as follows:
Δ u b u s . p u = 1 2 · H m g · s s 2 + k p · s / 2 H c + ( 2 H m g + k i ) / 2 H c · Δ P L . p u
Make
ξ = k p 2 H c · 2 H c 2 k i + 2 H m g ω n = k i + 2 H m g 2 H c
Therefore, Equation (5) can be written as
Δ u b u s . p u = 1 2 · H m g · s s 2 + 2 ξ · ω n · s + ω n 2 · Δ P L . p u
Equation (7) is a typical form of the second-order system, where ξ is the damping ratio, ω n is the oscillation frequency. These two parameters determine the characteristics of the system, such as overshoot, regulation time and damping state. Taking the regulation time T s as the inertia support time under the transient state of ESU, and then as the configuration principle of H c , ignoring the influence of the sinusoidal function. It is considered that when the exponential function decays to the steady-state error Δ = 0.02 , the transient process ends, and the formula of the adjustment time T s can be expressed as Equation (8):
T s ( 2 % ) = 1 ξ · ω n [ 4 1 2 · ln 1 ξ 2 ] 4 ξ · ω n
From Equations (6) and (8), the following equation can be obtained:
T s = 4 ξ · ω n = 16 H c k p
Given T s and control parameter k p , the total virtual inertia H c can be obtained, which means ESU needs to generate inertia H c under the matching system regulation time T s . After determining the total inertia H c , it is also necessary to specify how to allocate it among multiple ESUs. The principle of distribution is similar to the method of power allocation among multiple converters based on their respective capacities under parallel peer-to-peer control, which can be based on the ratio of the maximum inertia H c m a x of each ESU, as shown in Equation (10).
H c = C c U c 2 2 P G = C c 1 U c 1 2 2 P G + + C c i U c i 2 2 P G
The transient output power between ESUs is allocated according to the inertia ratio. The above inertia output time is matched according to the system regulation time T s ( 2 % ) , which completes the inertia and output power distribution among multiple ESUs.

3.3. Stability Calculation and Parameter Design

The maximum inertia configuration of ESU and the selection of the equivalent capacitance parameters of the DC bus will affect the stability of the system. The configuration of the maximum inertia H c m a x of ESU can be designed by giving the maximum step load level Δ P L m a x in Equation (5). Δ P L m a x needs to be calculated from the stability. The calculation of maximum load step power level belongs to the category of large disturbance stability, and the mixed potential function and stability criterion is established to set it. First, the system is equivalent to a steady state model as shown in Figure 5.
Based on the above analysis, ignoring all converters voltage and current dynamic control, the system can be equivalent to an ideal voltage source with series resistance. The right side can be equivalent to a CPL. P is the sum of the power of power units, U r e f is the reference voltage of balanced unit. Based on Figure 5, the following equation can be obtained:
d i d t = 1 L d U r e f U b u s R L i d U b u s d t = 1 C b u s i U b u s R P U b u s
where U b u s and i are state variables. Based on Ref. [20] for the modeling method and criterion of MPF, the MPF equations of the DC microgrid are listed as follows:
P ( i , U b u s ) = i s b i R L i d i + U s b R U R U b u s d U b u s R + i p s b i p U b u s d P U b u s + i s b i U r e f d i + ( U b u s ) ( i P U b u s U b u s R )
The right side of the equation shows the current potential function of each subterm in Figure 4, and they further build LEF as shown in Equation (13).
F ( i , U b u s ) = ( λ 1 λ 2 2 ) P ( i , U b u s ) + 1 2 L d ( U r e f U b u s R L i ) 2 + 1 2 C b u s ( U b u s R + P U b u s i ) 2
where λ 1 and λ 2 are two eigenvalues respectively, as shown in Equation (14).
λ 1 = R L L d λ 2 = ( 1 / R P / U b u s 2 C b u s
The MPF stability theorem states that when the bus voltage U b u s is greater than a certain minimum value U b u s m i n , the partial derivative of F ( i , U b u s ) with respect to time will be less than zero and the system is stable. The LaSalle invariant set [21] is further introduced to portray EDA [22] of the system as shown in equation Equation (15).
E D A = { ( i , U b u s ) | F ( i , U b u s ) m i n ( F m a x 1 , F m a x 2 ) }
where F m a x 1 is the value corresponding to the maximum tight set of LEF and F m a x 2 = m i n F ( i , U b u s m i n ) . This theorem overcomes the difficulty of judging whether the LEF is positive definite. Whether the initial operating point is within the post-step operating point EDA determines the stability. The specific criteria are described as follows: operating point x s 1 ( i 1 , U b u s 1 ) estimates the region within EDA, the partial derivative of F ( i , U b u s ) with respect to time is always less than zero, and the system is stable. Therefore, when the system steps from x s 0 ( i 0 , U b u s 0 ) to x s 1 ( i 1 , U b u s 1 ) , the system will eventually converge to the point x s 1 if the starting point x s 0 ( i 0 , U b u s 0 ) is within the EDA of x s 1 ( i 1 , U b u s 1 ) ; otherwise, the system will be unstable. This process determines Δ P L m a x . p u in Equation (5). After setting the critical stability step value Δ P L m a x . p u , H c m a x is rectified by parameter sensitivity analysis.

4. Simulation Results

4.1. Comparison of Time-Domain Simulations of Reduced-Order Models

According to the parameter configuration in Table 2, the reduced-order model in Figure 5 is compared with the full-order model (switch model) in the time-domain simulation, and the results are shown Figure 6.
In Figure 6, the constant load power is stepped from 80 kW to 160 kW at t = 1.5   s . During the transient process, the reduced-order model has almost the same dynamic characteristics as the full-order model, which proves the validity of the established reduced-order model.

4.2. Stability and Inertia Sensitivity Analysis

Given C b u s = 0.1 F , EDA and convergence under different power steps are shown in Figure 7.
In Figure 7, when the system first steps from x s 0 = 0 to x s 1 = 100 kW and then steps to x s 2 = 150 kW, the initial point of each step is within the EDA of the end point of the step, and it is known from the previous stability criterion that the step is stable and will eventually converge to the point to be stepped (black path). If the step from x s 0 = 0 to x s 2 = 150   k W , initial point is not in EDA of the point to be stepped, and the stability criterion shows that x s 0 will not converge to x s 2 (red path) and the system will be unstable. The above analysis determines the maximum step load of the system Δ P L m a x = 100   k W , and the maximum configuration inertia H c m a x of ESU is further clarified by substituting Δ P L m a x . p u = 0.7 into Equation (5). The trajectory of the two characteristic roots during the change of the total output inertia H c m a x of ESU from 1.4 to 0.2, that is, U c from 320 V to 560 V, is shown in Figure 8. From the results of the parameter sensitivity analysis, it can be seen that when ESU outputs inertia H c changes from 1.4 to 0.2 ( U c . p u from 0.8 to 1.4), the system pole gradually approaches the imaginary axis, and when H c m a x = 0.4 ( U c . p u = 1.3 ) , the pole is located in the imaginary axis and the system is critically stable. When the parameters change further, the pole will be located in the right half-plane and the system is destabilized. Selecting three groups of parameters H c m a x = 0.4 , 0.6 , 0.9 , the corresponding time-domain simulation is shown in Figure 9, and the Bode plot is shown in Figure 10.
H c m a x = 0.4 , 0.6 , 0.9 correspond to the blue, red, and black curves, respectively. It can be seen that when H c m a x = 0.4 , the system is in critical stability and close to constant amplitude oscillation, which is consistent with the stability analysis results. And with the continuous increase of inertia, the transient response time of the system is shorter, and it can enter a stable state faster (comparison of red and black curves). From Figure 10, with the increase of inertia, the phase angle margin increases from 4 to 26 . 8 (damping is positive), and the system oscillation disappears. Although larger inertia leads to faster response, it may cause system to have no overshoot, acting as over-damping. Therefore, it is not that the larger inertia, the better, but need to achieve a moderate matching of inertia. Under the above-mentioned disturbance conditions, the matching inertia is selected as H c m a x = 0.9 . In this paper, the two ESUs configuration scheme is used, and the maximum inertia ratio of the two is 2:1.

4.3. Time-Domain Simulation Analysis of ESU Inertia Output Distribution

Given T s = 10 s, the required H c = 0.6 at this T s is calculated by Equation (9). The two ESUs are distributed according to the maximum inertia ratio H c 1 = 0.4 and H c 2 = 0.2 . Here, T s can be calculated under actual oscillation according to the waveform playback, analytical method or fast Fourier analysis, which is not repeated in this paper. Further, according to Equation (10), U c 1 = 122.5   V and U c 2 = 86.6   V , the transient power distribution is Δ P e s s p u . 1 : Δ P e s s p u . 2 = 2:1, the simulation results are shown in Figure 11, Figure 12 and Figure 13. When t = S I 10 s and t = 30 s, the load is suddenly increased by 0.6 p.u. and decreased by 0.6 p.u. respectively. During the transient process of the system, the two ESUs output inertia according to the inertia distribution ratio, which cooperates with the VSC in response time. The voltage is controlled within a reasonable range, and the actual process is consistent with the theoretical analysis.

4.4. Experimental Verification

Based on the above time-domain simulation verification, the DC microgrid experimental platform is further built, as shown in Figure 14. Module S is a TopCon series bidirectional DC source module, 32   k W × 8500   V . It can be used as PV, ESU and DC load. Module B is the system 400   V , single-pole DC bus. Module C is the configuration control management system, which realizes the function of communication manager while effectively controlling the microgrid from millisecond level to hourly level. Module vsc is the DC microgrid grid-connected bidirectional converter. Module pv is the PV grid-connected converter. Modules sc1 and sc2 simulate the grid-connected bidirectional converter of energy storage units 1 and 2 respectively. Module L is the CPL grid-connected converter. In the experiment, the simulation is carried out according to the working conditions in the time-domain simulation. The response of ESU and the power curve of each module are shown in Figure 15.
In Figure 15, the experimental system simulates the sudden increase and decrease in the 90   k W DC load at t = 5   s and t = 15   s , respectively. ESU and the grid-connected VSC perform time sequence coordination when the load is disturbed, and ESU takes the lead in responding to provide inertia support according to the proportion. ESU 1 and ESU 2 respectively support a maximum power of 60   k W and 30   k W . The proposed strategy is verified to be correct and effective.

5. Conclusions

In this paper, an inertia adaptive control method under decentralized configuration is proposed for ESU in DC microgrid. This method takes advantage of the fast response characteristics of the energy storage inertia unit and quickly matches the inertia when the system is disturbed so as to improve the system performance in transient state. Meanwhile, a reduced-order equivalent model of the system is constructed, and the key parameters in inertia control of ESU are set through stability analysis. Finally, the correctness and effectiveness of the proposed strategy are verified by time-domain simulation and experiments. The set of ESU inertia control methods designed in this paper can be extended to ESU cluster systems, providing a practical solution for stable control of DC microgrids and distributed ESU cluster systems.

Author Contributions

Conceptualization, T.W. (Tao Wang); Investigation, T.Z.; Resources, M.L.; Visualization, H.L. (Hongchen Liu); Writing—original draft, T.W. (Taiyu Wang); Writing—review & editing, H.L. (Hongshan Li). All authors have read and agreed to the published version of the manuscript.

Funding

This work is supported by the National Natural Science Foundation of China (No. 61773137), the Natural Science Foundation of Shandong Province (No. ZR2019MF030).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:
ESUEnergy storage unit
DCDirect current
SOCState of charge
VSCVoltage source converter
MPPTMaximum power point tracking
DGDistributed generator
PVPhotovoltaic
SCSource converter
LCLoad converter
CPLConstant power load
VCCVoltage and current closed-loop control
MPFMixed potential function
LEFLyapunov-type energy function
EDAEstimated domain of attraction

References

  1. Li, Q.; Zhang, J. Solutions of voltage beyond limits in distribution network with distributed photovoltaic generators. Autom. Electr. Power Syst. 2015, 39, 117–123. [Google Scholar]
  2. Walling, R.; Saint, R.; Dugan, R.C.; Burke, J.; Kojovic, L.A. Summary of distributed resources impact on power delivery systems. IEEE Trans. Power Deliv. 2008, 23, 1636–1644. [Google Scholar] [CrossRef]
  3. Yuan, K.; Song, Y.; Li, J.; Sun, C.; Wu, Z.; Yuan, B.; Xue, Z.; Jin, X. Harmonic Characteristics of Distributed Generation and Electric Vehicle Supplying Access to the Grid. Proc. CSEE 2018, 38, 54. [Google Scholar]
  4. Liu, H.; Xiong, X.; Ji, Y.; Wu, M.; Rui, L.; Sun, L. Cluster Control Research of DC-type Distributed Generators Based on Multi-microgrids Technology under DC Distribution System. Proc. CSEE 2019, 39, 9. [Google Scholar]
  5. Li, X.; Guo, L.; Wang, C.; Li, Y. Key technologies of DC microgrids: An overview. Proc. CSEE 2016, 36, 2–17. [Google Scholar]
  6. Li, Z.; Kong, L.; Pei, W. Analyses of Stability Criterion and Key Factors of DC Microgrid Under Large Disturbance. High Volt. Eng. 2019, 45, 3993–4002. [Google Scholar]
  7. Bellache, K.; Camara, M.B.; Dakyo, B. Transient power control for diesel-generator assistance in electric boat applications using supercapacitors and batteries. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 6, 416–428. [Google Scholar] [CrossRef]
  8. Jin, Z.; Meng, L.; Guerrero, J.M.; Han, R. Hierarchical control design for a shipboard power system with DC distribution and energy storage aboard future more-electric ships. IEEE Trans. Ind. Inform. 2017, 14, 703–714. [Google Scholar] [CrossRef] [Green Version]
  9. Chen, X.; Zhou, J.; Shi, M.; Yan, L.; Zuo, W.; Wen, J. A novel virtual resistor and capacitor droop control for HESS in medium-voltage DC system. IEEE Trans. Power Syst. 2019, 34, 2518–2527. [Google Scholar] [CrossRef]
  10. He, L.; Li, Y.; Guerrero, J.M.; Cao, Y. A comprehensive inertial control strategy for hybrid AC/DC microgrid with distributed generations. IEEE Trans. Smart Grid 2019, 11, 1737–1747. [Google Scholar] [CrossRef]
  11. Xu, Q.; Hu, X.; Wang, P.; Xiao, J.; Tu, P.; Wen, C.; Lee, M.Y. A decentralized dynamic power sharing strategy for hybrid energy storage system in autonomous DC microgrid. IEEE Trans. Ind. Electron. 2016, 64, 5930–5941. [Google Scholar] [CrossRef]
  12. Lin, P.; Wang, P.; Xiao, J.; Wang, J.; Jin, C.; Tang, Y. An integral droop for transient power allocation and output impedance shaping of hybrid energy storage system in DC microgrid. IEEE Trans. Power Electron. 2017, 33, 6262–6277. [Google Scholar] [CrossRef]
  13. Chen, J.; Song, Q. A decentralized dynamic load power allocation strategy for fuel cell/supercapacitor-based APU of large more electric vehicles. IEEE Trans. Ind. Electron. 2018, 66, 865–875. [Google Scholar] [CrossRef]
  14. Wang, X.; Li, X. Small-signal stability analysis of islanded DC microgrid with wind power. Electr. Power Autom. Equip. 2017, 37, 92–99. [Google Scholar]
  15. Li, P.; Li, X.; Wang, C.; Guo, L.; Peng, K.; Zhang, Y.; Wang, Z. Review of stability analysis model and mechanism research of medium- and low-voltage flexible DC distribution system. Electr. Power Autom. Equip. 2021, 41, 3–21. [Google Scholar]
  16. Vasquez, J.C.; Guerrero, J.M.; Miret, J.; Castilla, M.; De Vicuna, L.G. Hierarchical control of intelligent microgrids. IEEE Ind. Electron. Mag. 2010, 4, 23–29. [Google Scholar] [CrossRef]
  17. Zhi, N.; Zhang, H.; Xiao, X.; Yang, J. System-level stability analysis of DC microgrid with distributed control strategy. Proc. CSEE 2016, 36, 368–378. [Google Scholar]
  18. Herrera, L.; Yao, X. Computation of stability metrics in DC power systems using sum of squares programming. In Proceedings of the 2017 IEEE 18th Workshop on Control and Modeling for Power Electronics (COMPEL), Stanford, CA, USA, 9–12 July 2017; pp. 1–5. [Google Scholar]
  19. Loop, B.P.; Sudhoff, S.D.; Żak, S.H.; Zivi, E.L. Estimating regions of asymptotic stability of power electronics systems using genetic algorithms. IEEE Trans. Control Syst. Technol. 2009, 18, 1011–1022. [Google Scholar] [CrossRef]
  20. Li, X.; Liu, N.; Song, X. Large-signal stability criteria of AC/DC hybrid microgrid based on AC constant power loads. High Volt. Eng. 2021, 47, 11. [Google Scholar]
  21. Zhang, Y.; Wang, C.; Zhang, H. Chaos control of parameter magnet synchronous motor based on finite time LaSalle invariant set. J. Syst. Simul. 2020, 32, 8. [Google Scholar]
  22. Li, X.; Wang, Z.; Guo, L. Transient stability analysis of PLL synchronization in Weak-Grid-Connected VSCs based on the largest estimated domain of attraction. Proc. CSEE 2022, 42, 29–38. [Google Scholar] [CrossRef]
Figure 1. Topological structure of DC microgrid system.
Figure 1. Topological structure of DC microgrid system.
Energies 15 06112 g001
Figure 2. Different control modes of ESU.
Figure 2. Different control modes of ESU.
Energies 15 06112 g002
Figure 3. Control block diagram of ESU under different modes.
Figure 3. Control block diagram of ESU under different modes.
Energies 15 06112 g003
Figure 4. Improved control block diagram.
Figure 4. Improved control block diagram.
Energies 15 06112 g004
Figure 5. Equivalent circuit model of DC microgrid system.
Figure 5. Equivalent circuit model of DC microgrid system.
Energies 15 06112 g005
Figure 6. Time-domain simulationcomparison between reduced-order model and full-order mode.
Figure 6. Time-domain simulationcomparison between reduced-order model and full-order mode.
Energies 15 06112 g006
Figure 7. Time domain simulation comparison between reduced-order model and full-order mode.
Figure 7. Time domain simulation comparison between reduced-order model and full-order mode.
Energies 15 06112 g007
Figure 8. Parameter sensitivity analysis.
Figure 8. Parameter sensitivity analysis.
Energies 15 06112 g008
Figure 9. Time domain simulation result. Blue, red and black curves represent H c m a x = 0.4 , H c m a x = 0.6 and H c m a x = 0.9 respectively.
Figure 9. Time domain simulation result. Blue, red and black curves represent H c m a x = 0.4 , H c m a x = 0.6 and H c m a x = 0.9 respectively.
Energies 15 06112 g009
Figure 10. Bode plot. Blue, red and black curves represent H c m a x = 0.4 , H c m a x = 0.6 and H c m a x = 0.9 respectively.
Figure 10. Bode plot. Blue, red and black curves represent H c m a x = 0.4 , H c m a x = 0.6 and H c m a x = 0.9 respectively.
Energies 15 06112 g010
Figure 11. VSC active power curve.
Figure 11. VSC active power curve.
Energies 15 06112 g011
Figure 12. Bus voltage curve.
Figure 12. Bus voltage curve.
Energies 15 06112 g012
Figure 13. ESU output curve.
Figure 13. ESU output curve.
Energies 15 06112 g013
Figure 14. DC microgrid experimental platform.
Figure 14. DC microgrid experimental platform.
Energies 15 06112 g014
Figure 15. Experimental results.
Figure 15. Experimental results.
Energies 15 06112 g015
Table 1. Operating status of each unit of DC microgird.
Table 1. Operating status of each unit of DC microgird.
Operating ModeUnitControl ModeUnit Attribute
Grid-connected modeGrid-connected VSCDroopBalance unit
ESUConstant powerPower unit
PhotovoltaicMPPTPower unit
LoadConstant powerPower unit
Off-grid modeGrid-connected VSC//
ESUDroopBalance unit
PhotovoltaicMPPTPower unit
LoadConstant powerPower unit
Table 2. Parameters of DC microgrid system.
Table 2. Parameters of DC microgrid system.
NameValue
Power level of balanced unit and power unit150 kW
C b u s / C c 1 / C c 2 0.1 F/8 F/8 F
Output voltage U r e f 400 V
Resistance R L /Reactance L d 0.8 Ω / 36.5 mH
Parallel resistance R90 Ω
SC reference voltage V r e f 1 210 V
SC inductance L 1 /capacitance C 1 /Resistance R 1 0.7 mH/ 0.9 mF/22 m Ω
SC voltage loop proportional/integral coefficient1/10
SC current loop proportional/integral coefficient1/10
LC reference voltage V r e f 2 40 V
LC inductance L 2 /capacitance C 2 /Resistance R 2 0.7 mH/ 0.5 mF/15 m Ω
LC voltage loop proportional/integral coefficient1/1
LC current loop proportional/integral coefficient1/100
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Wang, T.; Li, H.; Wang, T.; Liu, M.; Zhu, T.; Liu, H. Virtual Inertia Adaptive Control Strategy of ESU in DC Microgrid. Energies 2022, 15, 6112. https://doi.org/10.3390/en15176112

AMA Style

Wang T, Li H, Wang T, Liu M, Zhu T, Liu H. Virtual Inertia Adaptive Control Strategy of ESU in DC Microgrid. Energies. 2022; 15(17):6112. https://doi.org/10.3390/en15176112

Chicago/Turabian Style

Wang, Tao, Hongshan Li, Taiyu Wang, Meng Liu, Tong Zhu, and Hongchen Liu. 2022. "Virtual Inertia Adaptive Control Strategy of ESU in DC Microgrid" Energies 15, no. 17: 6112. https://doi.org/10.3390/en15176112

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop