1. Motivation
As civilization develops, so does its energy demand. One of the most popular uses by a human is electric energy. Thus, we have many sources of it and devices that use electricity. Many of them are also the source of electromagnetic disturbances. Electronic devices are required to test electromagnetic compatibility (EMC) to ensure reliable work and not cause interference to other equipment. One of them is electrical fast transients (EFT). The popular name of them is burst. The mechanisms of propagation of these disturbances and protection of devices against their effects are known [
1].
Up to now, research works have been limited to high-voltage switches. Often, articles have described the effect of disturbance [
2,
3]. Our research focuses on the phenomenon of EFT/burst disorders by analyzing the low-voltage relay operation. The choice was made due to the ever-lower voltage levels, operation with increasingly higher frequencies and the decreasing physical dimensions of the devices. In the case of electrical and electronic devices, the size of electrics also decreases with decreasing physical size. Fewer works deal with the description of this phenomenon [
4,
5,
6]. The method of measuring the resistance to EFT/burst disturbances is described in the standard [
7].
The literature research completed by the authors leads to the conclusion that there is a lack of later publications on the subject. This article introduces research to increase the knowledge of EFT/burst disorders.
2. Introduction
Electromechanical switches are very popular in electrical engineering. They are used to fast change circuit behavior. During switching, a transient state occurs temporarily in the circuit [
8]. The instantaneous peak voltage value may be temporarily several times greater than its nominal value [
9]. Thus, malfunction issues play an important role [
10]. Due to the ubiquitous undesired noise, the source of which can be relays [
11], the resulting disturbances should be suppressed directly at the source [
10]. Switches are frequently used to interrupt inductive loads [
6]. It often accompanies its sparking. The phenomena accompanying this switching significantly reduce the service life [
5]. Manufacturers and designers of relays focus on the most significant possible service life, often ignoring the issue of electromagnetic compatibility. Switching is a source of electromagnetic disturbances. The name of this type of disturbance is electrical fast transients. The popular term is burst. It is a broadband pulsed disturbance due to a concise rise time (of the order of a few nanoseconds), having big time constant depending on circuit capacitance and resistance. Its repetition rate goes up to several kHz. Immunity testing against it is mandatory in the EMC procedure. Testing and measurement techniques are described in standard [
7].
This research focuses on getting to know and explaining the phenomenon of EFT/burst and its impact on the EMC of other devices in the unique stand presented in
Figure 1. Subsequent analysis verified the assumptions described in the standard [
7], including rise time and arc duration.
3. Literature Review
As to showering arc, much of the research refers to article [
4] from the year 1969 [
5,
6,
8]. The research used the first edition of the book published in the mid-twentieth century [
12]. The literature research completed by the authors leads to the conclusion that there is a lack of later publications on the subject. Thus, the research conducted to describe the phenomenon has been undertaken for a long time. The mechanism of arc uprising depends on the separation between contacts that must be greater than or equal to the critical separation gap between contacts and the value of sustaining current.
Six electrons determine the required separation mean accessible paths [
4]. The electrical discharge is a tiny explosion due to the sharp change in pressure between the relay contacts. Two electrical discharges have been defined: steady arc and showering arc [
13]. The arc lasts as long as a minimum sustained voltage, and the minimum sustained current must be exited. A steady arc means one burning arc. Multiple burning arcs are called a showering arc. The steady arc is initiated by the emission of electrons induced by the field and has a much smaller amplitude and breaking voltage compared to the showering arc. It can arise at opened or closed contacts [
13].
A showering arc is discharge occurring by opening the relay with inductive loads. It accompanies its large voltage transient. A correlation was noted between the shape of waveforms and the supply voltage. In contrast, between contacts, the voltage peak is limited by the breakdown voltage of glow discharge [
14]. Simulating the arc discharge through the equivalent circuit has been verified. During this research, high-frequency components of voltage and current were observed. It has been found that it is possible to estimate the influence of voltage variation and arc on radio noise [
15]. Regardless of the material from which they were made, a showering arc consists of disturbances causing radio frequency noise. However, the frequency characteristics and noise level of the radio frequency noise were not related to the contact materials [
16]. Disturbances induced by opening contacts of relay caused a malfunction of electronic equipment. The rate of malfunction decreases when the wiring spacing is increased. The influence of the parallel capacitance on the quantity of malfunction was also checked. The number of failures was much smaller for the same distance of cables from the source of disturbances [
10]. Methods of suppression of conducted and radiated types of electromagnetic interference are also effective by mitigation of the EFT. A parallel connected diode reduces the noise level due to the showering arc [
17].
Despite the remarkable progress in numerical simulations, there is a big difference between an ideal and a real relay [
11]. Other researchers compare differences between the calculation and measurement method of the arc discharge [
15]. Numerical simulations are valuable to save time and other resources, but it is worth verifying them on a physical model.
The method of measuring the resistance to EFT/burst disturbances is described in the standard [
7]. A rise time is specified in the standard. On the other hand, the arc burning time was assumed to be infinitely short. Our research aims to measure the parameters of EFT/burst disturbances and the impact of load-side parameters on disturbances. No research work has been found in this area.
4. Materials and Methods
The research stand is presented in
Figure 1. It is identical to the circuits presented in [
5,
6] in order to relate results to previous ones. It consists of a relay board with a socket; a direct current (DC) power supply Keysight EDU36311A; digital oscilloscope Keysight DSOX2002A; a voltage probe Tektronix P5100A 500 MHz, 40 MΩ, 2.5 pF, ×100; voltage probe Testec 300 MHz, 100 MΩ, 4 pF, ×100; decade capacitor; decade inductor and ferrite chokes.
The electrical circuit shown in
Figure 2 describes the stand. A one-circuit topology with verified parameters has been adopted to observe their influence. The unchangeable elements of the circuit were a metallic resistor 1 Ω THT0411, a non-inductive ceramic resistor 100 mΩ (used as the shunt) and a low-inductive cell of metallised polypropylene capacitor 1 nF. Current from the power supply was 70 mA. We tested a low-voltage relay R15-3P (DC) with contact materials AgNi, a rated voltage of 12 V, the resistance of coils in 20 °C 110 Ω ± 10%, rated power consumption of 1.5 W, and response time of 18 ms.
The voltage waveform was measured with the probe P5100A, and the current waveform was measured with the second probe Testec 2.5 kV. A decade capacitor was used to change the parameters of the circuit. Chokes were aimed to eliminate electromagnetic disturbances, and they were placed on each wire.
The test consisted in observing the changes in voltage and currents by opening the relay. The voltage waveform was measured between contacts of the relay.
The current waveform was measured at the 100 mΩ shunt mounted in series with the relay. Each package of EFT/bursts was split into cycles, as shown in
Figure 3. The parameters of one cycle were defined as shown in
Figure 3 and
Figure 4.
One cycle was composed of time to ignition
, burning arc
and restoration
. For each cycle, we measured the peak-to-peak voltage
, peak-to-peak current
, time of restoration
, time of ignition
and time of arc
, as shown in
Figure 3 and
Figure 4.
An example of ignition and the burning arc are shown in
Figure 4. The time of ignition was measured between 0.1 and 0.9 of the peak value. The method of measuring
is shown in
Figure 4.
When no current flows , the current waveform determines the zero volt level for the voltage waveform.
5. Results
EFT/Burst disturbances were recorded for the circuit presented in detail in
Figure 5 with periodic transients. Upon termination of EFT/burst disturbances, the circuit is theorized to go into a transient state.
Measurements allowed us to consider the number of cycles and measure their parameters. Depending on the capacitance value, a different number of cycles was observed and presented in
Figure 6. X in tables means the situation in which the cycle was not present. Each subsequent cycle was characterized by increased energy accumulated between the contacts. This was due to the increasing distance between the contacts. Accordingly, the length of the burning arc also increased.
Regardless of the capacitance on the load side, the peak voltage increases with successive cycles presented in
Table 1. The slope of each next cycle is due to the increasingly longer charging time before ignition of the arc.
Irrespective of the capacitance, the current value was comparable, as presented in
Table 2.
As the capacitance increased, so did the restoration time presented in
Table 3, time of arc ingintion in
Table 4 and arc length presented in
Table 5. It follows that the duration of the arc depends only on the parameters of the circuit. It was due to the possibility of accumulating more charge in the capacitor. The ignition time was proportional to the voltage between the contacts.
6. Conclusions
A method of measuring burst has been developed, dividing it into individual cycles. Then, we measured the restoration, ignition, and arc burning time. The peak value of the voltage and current flowing through the burning arc was also measured.
A decreasing number of bursts was found with increased capacitance on the load side.
An increase in the maximum voltage was observed in the subsequent EFT/burst cycles. It also caused a rise in the value of the current flowing through the burning arc. This was accompanied by an increasingly extended restoration time, ignition time and arc burning time.
The increase in the duration of subsequent cycles resulted from the increasing distance between the contacts when it is opening. This causes the length of the burning arc to extend.
The greater distance between the contacts, on the other hand, translates into a higher voltage value needed to break the dielectric.
The measured rise time is comparable with the burst rise time in the standard [
7]. According to the standard [
7], the duration of the arc is infinitely short.
Our measurements show that the showering arc is composed of a series of long-time steady arcs.
The measurement shows that after the arc goes out, the gas passivates through the breakdown, which lasts for a while before it is neutral. This phenomenon is not reported in [
5,
6] and is not taken accord in the standard [
7].
The next steps that authors will undertake are numerical simulation of the burst phenomenon.
Author Contributions
Conceptualization, J.S. and K.K.; Data curation, P.Z.; Methodology, R.R. and J.S.; Resources, P.Z.; Supervision, R.R. and J.S.; Validation, R.R.; Writing—original draft, P.Z.; Writing—review & editing, K.K. All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Acknowledgments
Thanks are due to Maciej Piasek for his help constructing and improvement the research stand.
Conflicts of Interest
The authors declare no conflict of interest.
References
- Sroka, J. Compendium on ElecroMagnetic Compatibility; Printing House of the WUT: Hong Kong, China, 2021. [Google Scholar]
- Szewczyk, M.; Kuniewski, M.; Piasecki, W.; Florkowski, M.; Straumann, U. Determination of Breakdown Voltage Characteristics of 1’100 kV Disconnector for Modeling of VFTO in Gas-Insulated Switchgear. IEEE Trans. Power Deliv. 2016, 31, 2151–2158. [Google Scholar] [CrossRef]
- Szewczyk, M.; Kuczek, T.; Oramus, P.; Piasecki, W. Modeling of Repetitive Ignitions in Switching Devices: Case Studies on Vacuum Circuit Breaker and GIS Disconnector. In Analysis and Simulation of Electrical and Computer Systems; Lecture Notes in Electrical Engineering; Springer: Cham, Switzerland, 2014. [Google Scholar]
- Mills, G.W. The Mechanisms of the Showering Arc. IEEE Trans. Parts Mater. Packag. 1969, 5, 47–55. [Google Scholar] [CrossRef]
- Ott, H.W. Electromagnetic Compatibility Engineering; John Wiley & Sons: Hoboken, NJ, USA, 2009. [Google Scholar]
- Clayton, P.R. Introduction to Electromagnetic Compatibility; John Wiley & Sons: Hoboken, NJ, USA, 2006. [Google Scholar]
- IEC 61000-4-4:2012; Electromagnetic Compatibility (EMC)—Part 4-4: Testing and Measurement Techniques—Electrical Fast Transient/Burst Immunity Test. International Electrotechnical Commission: Geneva, Switzerland, 2012.
- Slade, P.G. Electrical Contacts Principles and Applications; CRC Press: Boca Raton, FL, USA, 2014. [Google Scholar]
- Bolkowski, S. Teoria Obwodów Elektrycznych; Wydawnictwo Naukowe PWN: Warsaw, Poland, 2022. [Google Scholar]
- Uchimura, K.; Michida, J.; Nozu, S.; Aida, T. Malfunction of Digital Circuits Caused by Noise Induced in Breaking Electric Contacts. Electron. Commun. Jpn. 1989, 72, 63–73. [Google Scholar] [CrossRef]
- Howell, E.K. How Switches Produce Electrical Noise. IEEE Trans. Electromagn. Compat. 1979, 3, 162–170. [Google Scholar] [CrossRef]
- Holm, R. Electric Contacts Theory and Application; Springer: Berlin/Heidelberg, Germany, 1981. [Google Scholar]
- Uchimura, K. Electromagnetic Interference from Discharge Phenomena of Electric Contacts. IEEE Trans. Electromagn. Compat. 1990, 32, 81–86. [Google Scholar] [CrossRef]
- Mutoh, A.; Nitta, S.; Suganuma, H.; Miyajima, K. The relationship between the showering noise waveforms and the supplied voltage to contact. In Proceedings of the International Symposium on Electromagnetic Compatibility, Atlanta, GA, USA, 14–18 August 1995. [Google Scholar]
- Kubono, T.; Suzuki, H. A Method of Making an Equivalent Circuit for Breaking Arc. Electron. Commun. Jpn. 1995, 78, 106–114. [Google Scholar] [CrossRef]
- Uchimura, K.; Aida, T.; Takagi, S.; Aida, T. Showering Arcs in Breaking Au, Ag, Pd, and W Contacts and Radio Noise Caused by These Arcs. In Proceedings of the International Symposium on Electromagnetic Compatibility, Wroclaw, Poland, 26–28 June 1984. [Google Scholar]
- Matejic, M.D. Evaluation of Relay Suppression Circuits for Reducing EMI. IEEE Trans. Electromagn. Compat. 1978, 1, 207–210. [Google Scholar] [CrossRef]
| Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).