1. Background
Climate change and energy saving are major global issues at present. The Paris Agreement signed in 2015 stipulates that all participating countries should strengthen their global response to the threat of climate change and keep the global average temperature rise within 2 °C, preferably within 1.5 °C [
1]. Besides, China is committed to increasing its nationally determined contributions by adopting more powerful policies and measures, which aims to reach the peak of carbon dioxide emissions by 2030 and carbon neutrality by 2060. China’s industrial energy consumption accounts for more than 70% of the total social energy consumption, in which about 50% is industrial waste heat with different mediums and temperatures; meanwhile, the current industrial waste heat recovery rate is only about 30% [
2]. Thus, how to recover waste heat efficiently is quite significant and urgent, and could reduce carbon dioxide emission sharply. Meanwhile, most traditional industrial processes are driven by burning coal, oil or natural gas with limited energy efficiency, which have huge carbon emissions. In order to increase the energy efficiency and reduce carbon emission significantly, the heat pump is widely used in different industrial processes [
2,
3,
4].
Heat pumps are divided into compression heat pumps (CHP) and absorption heat pumps (AHP). The COP of a compression heat pump is mainly limited by the working fluid and cycle type. Besides, adopted working fluids aim at lower pollution or even being pollution-free. Hydrofluorocarbons are being replaced by hydrofluoroolefins (HFO), hydrochlorofluoroolefins (HCFO) and natural refrigerants, gradually. Wu [
5] et al. compared the COP of six refrigerants and R718 owned the best system performance and Carnot efficiency. Frate et al. [
6] compared the systematic COP and the capacity heating capacity, which showed that R1233zd(E) is the better working fluid. In order to increase the heat sink temperature and COP of the compression heat pump, an intermediate heat exchanger is adopted in the cycle for a two-stage compression. Mateu-Royo [
7] et al. compared five vapor compression processes, which showed that single-stage and two-stage circulation using IHX were more suitable for high-temperature heat pumps. Kosmadakis [
8] et al. compared R1234ze(Z), R1233zd(E) and R1336mzz(Z) and recommended the refrigerant R1234ze(Z) as having the better performance; however, the heating limit of this single-stage cycle was 140 °C.
The absorption heat pump is a quite effective waste heat recovery device with ammonia solution or lithium bromide solution as a working fluid [
9,
10]. The AHP with H
2O/LiBr has been widely used for cogeneration systems and waste heat recovery [
11,
12], in which the evaporation temperature is higher relatively. Meanwhile, NH
3/H
2O is used when the evaporation is below 0 °C due to its low freezing point. In order to improve the COP of heat pumps with NH
3/H
2O, ammonia/salt mixtures (e.g., NH
3/NaSCN and NH
3/LiNO
3) were adopted for AHP systems for both heating and cooling applications [
13,
14]. Yang et al. [
15] proposed a new type of open absorption heat pump to recover industrial waste gas and flue gas for a better COP. Wu et al. [
16] conducted a comparative study on different absorption cycles to obtain the most suitable running mode for district heating and domestic hot water in cold areas. Besides, more new cycle processes are proposed for improving the performance of different kinds of heat pumps. Xu et al. [
17] proposed a double-section absorption heat pump for recovering low-grade waste heat deeply and Sun et al. [
18] used DEAHP to recover low-grade heat at a thermal power plant.
In order to obtain a super high temperature lift or heat sink temperature, a hybrid heat pump system is proposed to integrate the advantages of absorption and compression heat pumps. There are two types of hybrid heat pump systems in reported studies. One is a compressor-assisted absorption heat pump, which adds a compressor in the absorption heat pump to change the vapor pressure. Wu [
19,
20,
21] et al. proposed a compressor-assisted absorption heat pump and constructed a mathematical model for performance simulation. Compared with conventional absorption heat pumps, the presented heat pump could reduce the consumption of driving heat source with a larger heating capacity. A compressor-assisted two-stage three-effect absorption refrigeration cycle could decrease the inlet temperature of heat source by 50 °C, as proposed by Okwose [
22]. Al-Madhagi [
23] et al. analyzed the cycle characteristics of the compressor with two different positions. In order to improve the utilization of geothermal energy, Wu [
24] recommended NH3/ionic liquid for an absorption-compression heat pump. Ji [
25] et al. studied a new type of hybrid heat pump to overcome the shortcomings of poor heating performance for a traditional air source absorption heat pumps at low temperatures, which could operate at an ultra-low temperature of −30 °C. Wu [
26] et al. developed an air source heat pump adopting H
2O/IL absorption and carbon dioxide compression for low ambient temperatures, which could improve the heating characteristics significantly. Gao et al. [
27,
28] studied a hybrid air source heat pump using R134a and LiBr for a larger temperature lift. The COP was 1.4 when the hot water was heated from 10 °C to 100 °C.
In a word, the absorption cycle can reach a higher output temperature with a lower COP, while the COP of the compression type is much higher, but it is difficult to reach higher output temperature due to the temperature and pressure restriction of the compressor. Thus, the hybrid heat pump is presented for better COP and heating temperature, which could combine advantages of both absorption and compression heat pumps. The relative current research projects are compared in
Figure 1, which indicates that little current research could reach a heating temperature over 150 °C; thus, a new hybrid heat pump is given for higher heating temperature, which could meet higher heating requirement for production processes.
This work proposes a new type of hybrid heat pump cycle to reach a high temperature, which could increase the working temperature lift significantly. The cycle adopts a new coupling process without employing the cooling tower. This cycle could reach a heating temperature of 200 °C with a satisfying performance.
3. Results and Discussion
In order to obtain a better COP of this hybrid cycle, it is necessary to compare working fluids for the compression sub-cycle and absorption sub-cycle. Ammonia solution and lithium bromide aqueous solution are widely used at present. However, the aqueous ammonia solution is toxic and external special units are needed in the ammonia distillation process; thus, the working fluid of the absorption cycle in this work selects lithium bromide aqueous solution. The working fluid of the compression cycle is selected from R142b, R134a, R1234ze, R245fa, R152a and R236fa, which are recommended for high temperature compression heat pumps at present.
When the inlet heat source temperature is 160 °C and the heat sink outlet temperature is 200 °C, there are three main parameters which affect the performance of the entire cycle significantly: coupling temperature of the low-pressure stage, coupling temperature of the high-pressure stage and pressure ratio of the compressor in the absorption sub-cycle; thus, performances of this hybrid cycle are discussed separately here.
3.1. Selection of the Working Fluid in the Compression Sub-Cycle
COP, heating capacity per unit volume and discharging temperature of different working fluids are compared at different condensation temperatures, as shown in
Figure 3,
Figure 4 and
Figure 5. It is found that R142b and R245fa show better COP, and R134a and R152a better heating capacity, meanwhile, R245fa and R236a show lower discharging temperature, whose temperature difference is less than 5 °C. Considering the significant influence of COP on systematic performance, R245fa is the better working fluid for this compression sub-cycle.
The environmental performance evaluation, which includes ODP (Ozone Depletion Potential) and GWP (Global Warming Potential) of different refrigerants is shown as
Table 4 It is clear that R1234ze owns better environmental protection, R152a and R245fa is second, and the other is the worst.
In a word, considering the environmental protection and circulation characteristics, R245fa is selected as the working fluid of the compression sub-cycle.
3.2. The Influence of Low Pressure Stage Coupling Temperature on Cycle
The COP of this hybrid cycle changes with the coupling temperature of the low-pressure stage when the coupling temperature of the high-pressure stage is 95 °C and the pressure ratio is 4, as shown in
Figure 6. When the low-pressure stage coupling temperature rises from 40 to 60 °C, the COP of the compression sub-cycle changes from 3.28 to 5.53. It can be found that the low-pressure stage coupling temperature shows a greater influence on the compression sub-cycle and the temperature difference between the two sides of the compression sub-cycle decreases when this temperature increases, which could decrease irreversible loss and increase COP directly.
The COP of this hybrid cycle varies with the coupling temperature of the low-pressure stage, as shown in
Figure 7. COP of the hybrid cycle increases from 2.30 to 3.03 when the coupling temperature changes from 40 °C to 60 °C, mainly due to the improvement in compression sub-cycle performance.
The energy flow of this cycle is shown in
Figure 8. The heating performance decreases from 938.2 kW to 934.4 kW under simulated working cases, when the electrical consumption of absorption sub-cycle compressor increases from 147.1 kW to 152.8 kW and the compressor power consumption in the compression sub-cycle decreases from 260.6 kW to 155.2 kW significantly.
3.3. The Influence of High Pressure Stage Coupling Temperature on Cycle
The relationship of the sub-cycle COP with the coupling temperature of the high-pressure stage when the low-pressure stage coupling temperature is 50 °C and the compressor pressure ratio is 4 is shown in
Figure 9. It shows that COP of the compression sub-cycle decreases from 6.51 to 3.66. The reduction of COP of the compression sub-cycle is attributed to the increase in the temperature difference between low and high pressure stages.The relationship of the coupling cycle COP with the high pressure stage coupling temperature is shown in
Figure 10. The change of the coupled cycle COP and the change of the compression sub-cycle COP shows a similar trend, which varies from 3.30 to 2.44.
The energy flow of this hybrid cycle is shown in
Figure 11. The heating load slightly increases from 918.9 kW to 942.2 kW. Meanwhile, the electrical consumption of the absorption sub-cycle compressor increases slightly from 146.6 kW to 151.3 kW when the generator load is 837.4 kW. The electrical consumption of the compression sub-cycle compressor increases by almost 80%, which varies from 132.1 kW to 234.5 kW.
3.4. Influence of Compressor Pressure Ratio
It is found that the COP of the compression sub-cycle remains constant when the coupling temperature of low-pressure stage and high-pressure stage are 40 °C and 95 °C, respectively, while the variation trend of the absorption sub-cycle and coupling cycle COP with the compressor pressure ratio is shown in
Figure 12. It shows that the COP of the absorption sub-cycle increases from 0.48 to 0.52, while the hybrid COP decreases from 2.79 to 2.02, which is due to the increase in absorber load and compressor power consumption, but the latter is much more obvious.
The energy flow of this hybrid cycle is shown in
Figure 13. It can be found that the heating performance increases from 842.6 kW to 1009 kW. Besides, the generator load is 837.4 kW, and the power consumption of the absorption sub-cycle compressor increases from 38.59 kW to 229.4 kW when the electrical consumption of the compression sub-cycle compressor decreases from 264 kW to 258.6 kW at first, increasing to 270 kW later.
3.5. Optimal Condition of Hybrid Cycle
It is apparent that the best working condition at a certain pressure ratio can be obtained through changing the coupling temperature of the low-pressure stage and the high-pressure stage. The optimal working conditions and the corresponding cycle performance under different pressure ratios are shown in
Figure 14 and
Figure 15.
The optimal coupling temperatures of the high-pressure stage under different pressure ratios are shown in
Figure 14, when the low pressure stage coupling temperature is 55 °C. It can be seen that the coupling temperature of the high-pressure stage decreases from 109 °C to 72 °C. At the same time, the hybrid cycle COP shows firstly an increasing trend and then decreases later, reaching the maximum value of 3.249 when pressure ratio is 6.5.
The application of the compressor can reduce the high-temperature stage coupling temperature effectively. The COP of the compression sub-cycle increases significantly with the decrease in coupling temperature of the high-temperature stage, as shown in
Figure 15, while the COP of the absorption sub-cycle shows a trend of increasing firstly and then decreasing later with a maximum COP of 0.49 when the pressure ratio is 6.
In summary, better COP of this cycle is obtained when the pressure ratio is 6.5, the coupling temperature of the low-pressure stage is 55 °C and the coupling temperature of the high-pressure stage is 73 °C.
3.6. Exergy Analysis of Hybrid Cycle
From the point of view of exergy, the energy conversion and loss in the process are analyzed to provide reference for system application and optimization. Under the conditions that the inlet and outlet temperatures of the heat source are 160 °C and 140 °C, and the heat sinks are 180 °C and 200 °C separately, the efficiency of each component is calculated as shown in
Table 5. It can be seen that the exergy efficiency of generator, absorber and compressor is much lower, while that of the hybrid heat exchanger is higher relatively, which is due to the small temperature difference in its heat transfer process.
4. Conclusions
In order to reach a heating temperature over 200 °C, this work proposes a new type of coupled heat pump cycle, which is simulated by EES and REFPROP, and the main parameters of the cycle are discussed and optimized. The following conclusions are found:
- (1)
Simulation of compression sub cycle with R142b, R134a, R1234ze, R245fa, R152a and R236fa is analyzed, and R245fa is selected, with a higher COP and lower discharging temperature;
- (2)
The COP of the coupling cycle increases with the coupling temperature of the low pressure stage when the pressure ratio is 4 and the coupling temperature of the high-pressure stage is 95 °C; the coupling cycle COP increases with the coupling temperature of the high pressure stage when the pressure ratio is 4 and the coupling temperature of the low-pressure stage is 50 °C;
- (3)
COP of the coupling cycle decreases with the pressure ratio, and the maximum COP is 2.785 when the pressure ratio is 1.5 when the coupling temperatures of the high-pressure stage and the low-pressure stage are 95 °C and 40 °C;
- (4)
The optimal operating conditions when the heat source temperature is 160 °C and the heat sink temperature is 200 °C are obtained by comparing the optimal operating conditions under different pressure ratios. The COP takes the maximum value 3.249 when the pressure ratio is 6.5, the low-pressure stage coupling temperature is 55 °C and the high-pressure stage coupling temperature is 73 °C. Meanwhile, the simulation results of exergy efficiency under optimal operating conditions show that generator, absorber and compressor should be improved to enhance cycle performance.
- (5)
The exergy efficiency of evaporation and condensation is higher due to the small temperature difference in its heat transfer process.
In addition, the heat transfer process of all components will be given to optimize the heat transfer area, reducing equipment size and initial investment, with a sample unit in our next research plan. This new type of heat pump is promising for industrial heat recovery cases, with satisfactory performance.