Next Article in Journal
An Explicable Neighboring-Pixel Reconstruction Algorithm for Temperature Distribution by Acoustic Tomography
Previous Article in Journal
Utilization of Window System as Exhaust Air Heat Recovery Device and Its Energy Performance Evaluation: A Comparative Study
Previous Article in Special Issue
Making School-Based GHG-Emissions Tangible by Student-Led Carbon Footprint Assessment Program
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Suitability Evaluation of Different Measured Variables to Assess the Occupancy Patterns of a Building: Analysis of a Classroom of a School in Madrid during the COVID-19 Pandemic

by
María Nuria Sánchez
1,*,
Emanuela Giancola
1,
Silvia Soutullo
1,
Ana Rosa Gamarra
2,
Rafael Olmedo
1,
José Antonio Ferrer
1 and
María José Jiménez
1,3
1
Energy Efficiency in Buildings Unit, Department of Energy, CIEMAT, E-28040 Madrid, Spain
2
Energy Systems Analysis Unit, Department of Energy, CIEMAT, E-28040 Madrid, Spain
3
Plataforma Solar de Almería, CIEMAT, Carretera de Senés s/n, Tabernas, E-04200 Almería, Spain
*
Author to whom correspondence should be addressed.
Energies 2022, 15(9), 3112; https://doi.org/10.3390/en15093112
Submission received: 18 February 2022 / Revised: 12 April 2022 / Accepted: 20 April 2022 / Published: 25 April 2022
(This article belongs to the Special Issue Acting for the Transition to a Low-Carbon Economy in Schools)

Abstract

:
Building occupancy is one of the relevant variables to understand the energy performance of buildings and to reduce the current gap between simulation-based and actual energy performance. In this study, the occupancy of a classroom in an educational center monitored over a full year was experimentally assessed. The classroom had different occupancy levels during the school year, with a theoretical minimum of eleven students, and no occupancy during vacations and weekends. Different variables such as indoor air temperature, relative humidity, CO2 concentration, overall electrical energy consumption of the educational center, electrical energy consumption of the building in which the monitored classroom is located, and heating energy consumption were recorded. We analyzed which of these variables were possible indicators of classroom occupancy, using the school timetable as a theoretical reference value for the validation of the results. Based on previous studies, one-hour moving averages are used to better identify the occupancy patterns by smoothing the fluctuations that are not a consequence of a change in the classroom occupancy. Histograms of each variable are used to identify the variable ranges associated within the occupancy: occupied or empty. The concentration of CO2 and electric measurements, identified in previous works as suitable to assess the occupancy patterns of rooms like offices with lower levels of occupancy, are recognized as potential occupancy indicators. It is therefore concluded that a higher level of space occupancy does not affect the result, and the same variables are identified as potential occupancy indicators.

1. Introduction

Current environmental threats, as well as the scarcity of resources and the impact of climate change, are a major concern for the sustainable development of cities [1,2], with districts playing an important role in the transition to climate-neutral cities [3]. Under this framework, 17 Sustainable Development Goals (SDGs) have been defined in the 2030 Agenda [4], whose objective is to promote sustainable development in cities. Quality education, climate change, clean energy or sustainable cities are key factors to achieve the energy transition. Aver et al. [5] highlighted the importance of a quality education (SDG 4) in achieving the SDGs and proposed some recommendations that can be applied at different educational levels. Fulzele et al. [6] conceptually analyzed the impact that the COVID-19 pandemic had on the environment and energy SDGs (7—Affordable and clean energy, 9—Industry, innovation and infrastructure and 13—Climate action), finding positive and negative factors in all cases. The quantification of this influence was done through a methodology based on the severity and importance of the impact on the SDGs. Their conclusions showed a lesser impact of the pandemic on SDG 7, a stagnant process on SDG 9, and a negative impact on SDG 13. Ameli et al. [7] assessed different post-COVID-19 scenarios to minimize the negative effects on the achievement of the SDG objectives in Iran, using a qualitative method based on fuzzy cognitive maps. In this study, five strategies (eco-management, sustainable food, market revitalization, inclusive education and support in the energy sector), and combinations of them, and three post-COVID-19 scenarios were considered.
Energy efficiency measures [8] can help to achieve the SDG objectives. Nurunnabi et al. [9] assessed how these measures enhance corporate social responsibility (CSR) in a way that facilitates compliance with the SDGs, especially with SDG 7. Di Foggia [10] showed that energy efficiency measures must meet the requirements of citizens and industry in order to achieve the SDGs. This study, based on the analysis of empirical data collected and published by the Financial Institutions Group, identified the following critical drivers: standardization, low transaction costs, energy prices, and stability of the regulatory framework.
With regard to the legal framework, different European governments adopt directives focused on the construction of more efficient buildings [11], enabling inclusive and dynamic urban growth [12]. This growing interest in promoting energy efficiency in buildings has highlighted the need to increase the knowledge of the energy performance of buildings and the use of effective solutions [13] and validated design approaches [14]. In this context, occupant behavior is one of the key sources of uncertainty for building energy analysis, being also one of the main causes of the performance gap [15]. Multiple international initiatives are focused on potentially contributing to energy saving targets from behavior measurements [16] and further developing occupant simulation [17,18]. Hou et al. [19] incorporate the interaction between building occupancy and urban systems considering users’ Wi-Fi connections. Other authors proposed electric load profiles from smart meter readings to model occupancy profiles in residential buildings [20]. Mitra et al. [21] evaluate occupancy schedules in residential buildings in the USA from cluster analysis of the overall U.S. population’s activities, throughout twelve years. Additionally, occupancy profiles of non-residential buildings were determined by clustering mobile positioning data from social media platforms [22]. Moreover, aggregated building stocks are especially affected by this performance gap. Bianchi et al. [23] developed an approach to modeling occupancy-driven building loads to better estimate the impact of energy conservation measures. Most of the previous analyses were focused on residential buildings and the current time particularities due to the fact that higher ventilation requirements have to be further evaluated [24].
This paper is focused on the experimental assessment of the occupancy pattern, as input that can contribute to improving the reliability of the energy performance assessment of buildings. Indeed, occupation is precisely identified as one of the most relevant issues that have an influence. This research analyses the suitability of different variables to obtain the occupancy patterns from measurements recorded by on-board monitoring systems in an in-use educational building. The aim was to identify which one represents this variable more accurately, helping to reduce more effectively the discrepancies between measured and simulated energy consumption.
Indoor air temperature, relative humidity and CO2 concentration are variables affected by human presence. Furthermore, electricity consumption due to artificial lighting, computers or thermal conditioning systems are also related to occupancy levels. Therefore, all these four variables were evaluated as occupancy indicators for this type of buildings.
The proposed approach has been applied to a classroom of a public high school in Madrid. The classroom has different levels of occupancy and users with different habits depending on the subject taught. The schedule for the schoolchildren has been used as a reference to validate the results. The future studies will focus on a comparison with the occupancy patterns normally used in the simulation of educational centers. This will allow the quantification of the impact of this improvement and its application to the modeling of this type of building.
The paper was structured in the following way: first, technical basics are described, then we describe the experimental set up and the devices required in the monitoring of a reference classroom. Thirdly, a description of the experimental campaign is carried out. Finally, the methodology applied to obtain occupancy patterns in educational buildings was defined.

2. Materials and Data

2.1. Educational Building Features

The assessed educational center is the public High School named IES Gabriel García Márquez (Figure 1). It is located in the Hortaleza district in the northeast of Madrid, characterized by a Mediterranean continental climate [25,26]. The high school complex includes two buildings and an open courtyard. The main building was built in 1988. An extension was later arranged in 2004 by annexing a new building, to meet the center’s demands. There are around nine hundred students currently enrolled at the school. In addition to different facilities, i.e., a library and a gym, the main building has 22 classrooms of similar dimensions, and one of them was selected for this study of occupancy patterns in schools.
The selected classroom was representative to assess occupancy patterns in this High School according to the total volume and the type of activities carried out inside. As mentioned above, all classrooms had similar dimensions and geometry but the one selected to assess occupancy patterns provided interesting variability in the number of students and hours of occupancy throughout the week. This room was north-oriented and located on the ground floor of the main building with a net floor area of 58 m2 and 2.86 m height (Figure 2a). On the north wall, the room had two triple wing upper windows with wing dimensions 0.86 × 0.38 m2 (Length × Height) and two triple wing lower windows with wing dimensions 0.86 × 0.88 m2 (Length × Height). Entrance to the classroom was through a door sized 0.82 × 2.03 m2 (Length × Height) and located on the wall opposite to the windows.

2.2. Main Characteristics of the Monitoring Solution

The IES Gabriel García Márquez was instrumented to continuously record measurements associated with ensuring the well-being of students and to support research activities on sustainability and consumption issues [27,28]. This was done under the framework of the ClimACT Project [29]. The Transition to a low Carbon Economy in schools was developed under the priority axis “Low Carbon Economy” from Interreg SUDOE programme.
A distributed data acquisition system was installed in a meshed network architecture based on wireless sensors’ measurements via radio frequency. Monitoring devices were focused on measuring the air temperature, the relative humidity, and the CO2 concentration inside the classroom. Wireless communications were carried out through an external antenna supplied with the equipment and an internal battery provided an approximate autonomy of three years.
The data-logger included a radiofrequency module for the communication of the temperature, humidity, and CO2 probes. It had a GPRS 3G module for access and data transmission, and an internal module of electrical analysers used to evaluate electricity consumption. Regarding this last issue, the three-phase circuits measured were: general, main building and boilers; all of them located in the electrical switchboard of the main building.
Data were recorded in the data-logger on a uSD memory card for one year. Data access was managed by making a local area net connection to the data-logger ethernet device. The data-logger was assigned a private IP address on the same local network of school PCs. For remote connections, 3G modems were also available. Via modem, it is possible to send data to an FTP server. Furthermore, a TCP/IP connection to the ethernet web, allowed data to be sent to the PCs within a network for remotely accessing this device through the internet.

2.3. Experimental Campaing

This study was based on an annual monitoring period. The experimental measurements evaluated in this research were recorded from April 2020 to April 2021. This period comprised two different academic years (2019/20 and 2020/21) with the subsequent particularities:
-
Academic Year 2019/2020 (from April 2020 to June 2020): No occupancy due to COVID-19 pandemic.
-
Academic Year 2020/2021 (from September 2020 to April 2021): Occupancy based on reduced capacity due to COVID-19 restrictions. In all classrooms, the lowering of the student ratio meant that every second desk was left empty. In addition, ventilation of classrooms was encouraged at the beginning of each class for at least 15 min, with the recommendation to keep windows open during the entire class. The classroom door remained open whenever it was possible, trying to promote cross ventilation.
Monitoring devices inside the classroom are visualized in Figure 2a. The temperature/humidity sensor and the CO2 probe were located on the South wall at 2.5 m height.

3. Methodology: Occupancy Pattern Assessment

The methodology was focused on the experimental assessment of the occupancy profiles in schools to enhance building performance evaluation. School occupancy patterns were closely linked to the duration and frequency of the classes and the corresponding standstill periods. These particularities had a significant impact on energy use and building management.
The objective of this methodology was to assess the suitability of different variables to obtain the occupancy profiles in schools. In this research, the methodology was applied to a reference classroom. The indoor air temperature, the relative humidity, the CO2 concentration, and the electricity consumption measurements were proposed as candidate variables to be used as occupancy indicators. These variables were obtained from measurements recorded by building monitoring/control systems. The recorded variables do not allow the actual occupancy level of the classroom (the number of people in the classroom) to be obtained, but to estimate its occupied/empty status. However, this information is sufficient to achieve the objective of the proposed methodology, that is, to further investigate different variables as possible indicators of occupancy patterns but considering non-intrusive and cost-effective measurements as critical factors.

3.1. Preliminary Analysis: Data Overview

First, recorded data overview and data pre-processing was done. The classroom occupancy profiles of the different candidate variables were assessed and compared. A sensitive handling of data was done before estimating the occupancy pattern of the classroom. Indoor air temperature, relative humidity, CO2 concentration, and total electricity consumption were measured and evaluated as indicators of the occupancy status.
The typical annual behavior of these variables is displayed in Figure 3. In addition, Figure 4 shows daily and weekly patterns of these four variables evaluated in a monthly period. Two months were compared, corresponding to vacation and school term periods (August 2020 and November 2020, respectively). These two periods represented opposite statuses with respect to the level of occupation. These qualitative analyses evidenced some correlation between the variables and the occupancy status of the classroom.
Depending on the candidate variable analyzed, the preliminary analysis (Figure 3 and Figure 4) showed more or less clearly two differentiated statuses of the classroom occupancy: empty and occupied. These figures provide a first assessment, qualitative in this case, of the correlation between each variable and the occupancy status of the classroom. Each variable considered as a candidate indicator (indoor air temperature, relative humidity, CO2 concentration, and total electricity consumption) showed some degree of dependency with the occupancy status, being within a range when the office was occupied and in another range when it was empty. Therefore, these unknown ranges must be determined quantitatively from the data measurements.
Since any numerical value of these variables must be in a range that corresponds to the occupied or empty status, the sensitive handling of data determined the corresponding periods for each status. All candidate variables were affected by the classroom occupancy, but Figure 4 showed this dependency was more evident for the CO2 concentration, and total electricity consumption data. However, the precise identification of reliance between the variables and occupancy status must be further discussed. Therefore, and based on previous studies [30,31], one-hour moving averages of data are used to better identify the occupancy patterns. This technique avoids fluctuations in measurements that do not come from changes in the occupancy status of the classroom.
The performances of combinations of variables were assessed in a previous work where we applied the same methodology [30,31], and the studied combinations did not perform better than using just one variable. According to this finding, we have limited this work not considering combinations.

3.2. Measurement Ranges for Occupancy

Histograms of candidate variables were generated to refine the measurement ranges associated with classroom occupancy status. One-hour moving averages of data measurements were used to generate these histograms. Full data range was divided in consecutive subranges, and data occurrences associated to each one, identified the different classroom occupancy levels. Data subranges were defined based on different intervals depending on the candidate variable as shown in Table 1.
Regarding the electricity consumption, since accuracy depends on the load of the system, the accuracy of class 0.5 in electric consumption in Table 1 means that the accuracy is 0.5% of the reading under full load and unity power factor.
Preliminary data analyses, based on qualitative observations, conclude that the school is always empty on Monday to Friday from 20:00 h to 7:00 h, and for the whole day at the weekends and holidays. This criterion was fixed to determine the ranges of empty occupancy status linked to each candidate variable. On the other hand, it is not possible to ensure when the classroom was certainly occupied. However, the classroom was probably occupied when the data values were other than the previously established ranges.
According to this limitation, occupancy patterns of the classroom were determined for the two following statuses: certainly empty and probably occupied. Then, the global number of occurrences at each status normalized the generated histograms. The intersection of both histograms represented the breakpoint for a change in the classroom occupation status. A systematic method was applied to find the breakpoints from the histograms of the datasets. The calculation of the intersection points was based on a function developed in Matlab [32]. This function determines whether or not intersection occurs in each pair of line segments generated from the input data of each variable histogram (empty/occupied). To speed up the process, the function performs a preliminary check to eliminate pairs of line segments that could not possibly intersect.
Once the corresponding occupancy breakpoints were determined for each candidate variable, the classroom occupancy patterns were estimated and compared. The expected classroom occupancy detailed in the next section in Table 2 was used to validate these results.
These established ranges for the different indicators, except for the electricity consumption, could be modified by the user’s habits, being the status of door and windows (open or close) during school hours one of the most critical. The effect on occupancy patterns regarding this issue was not assessed in this research due to the lack of information. Another factor affecting the candidate variables was the operation of conditioning systems.

3.3. Theoretical Occupancy Patterns Identification

The student time schedule was used as the theoretical reference to validate the estimated occupancy patterns. The theoretical occupancy values of the selected classroom are specified in Table 2.
These values refer to the theoretical total number of people in the classroom, including the students and the teacher. The real occupancy values can be obtained through different pathways.
The most direct way refers to information on student school attendance. Unfortunately, there were no accessible records of student absences during the evaluated academic year, so there is no real information on the number of people. Although, a one-day experimental campaign was conducted with the collaboration of the occupants, and real occupancy data were recorded for this period. Other options related to direct measurements using occupant detection methods such as chair/desk sensors, cameras, etc., were ruled out in this methodology to ensure non-intrusiveness and cost reduction.
In summary, and taking into account these limitations, the methodology is applied to determine from which measured variables the occupancy status of the enclosures can be determined, but not their occupancy level.

3.4. Accuracy of the Estimated Occupancy Patterns

The accuracy of the estimated occupancy patterns was analyzed for each candidate variable. The obtained indicators were used to quantify the different occupancy approaches. Deviation from the theoretical occupancy times taken as reference (Table 2) was calculated. The difference between the estimated hours of occupation and the academic school hours was expressed as a percentage.
The most proper approach for classroom occupancy pattern estimation combined both maximum performance and minimum intrusiveness and cost, and referred to the monitoring system.

4. Results

Occupancy profiles in schools to enhance building performance assessments were experimentally obtained and the main results are presented in this section.

4.1. Candidate Occupancy Pattern Variables: Histograms Overview

The histograms of the different candidate variables are displayed in Figure 5. This figure shows different occupancy profiles. Depending on the overlapping degree of the curves representing the two occupancy statuses, the accuracy achieved in determining occupancy threshold is different.
The temperature and relative humidity curves in Figure 5a,b present a wider and flatter shape. In consequence, it is difficult to establish a clear occupancy status breakpoint due to the significant overlap degree between the occupancy status curves. Therefore, air temperature and humidity were discarded as ineffective occupancy indicators because they do not provide accurate estimations.
The histograms of CO2 concentration in Figure 5c, as well as histograms associated with electricity consumption measurements (Figure 5d–f), show narrow and pointed shapes. In this case, due to the lower overlapping degree, the occupancy status breakpoint was certainly identified. This performance was mainly observed in the cases of global and building electricity consumption. So, these last four candidate variables are suitable to obtain the classroom occupancy patterns.
Table 3 shows quantitative results, identifying the cut-off points for occupancy status, i.e., the value of the variables from which the room is occupied.
The dashes in the table show that, as previously indicated, it was impossible to determine a clear breakpoint for either temperature or humidity values. For the rest of the variables, the value of the threshold used to obtain the experimental occupancy patterns is indicated.

4.2. Classroom Occupancy Patterns

Estimated and theoretical occupancy patterns are displayed in Figure 6 from suitable variables: the CO2 concentration (Figure 6a,b) and the measurements associated to electricity consumption (Figure 6c–h). Monthly periods are displayed to evidence daily and weekly occupancy patterns from each suitable variable. School and vacation periods present an opposite behavior with respect to the level of classroom occupation. Two months were assessed and compared, respectively belonging to different period typology (school or vacation).
Figure 6 shows the positive occupancy status in the classroom by comparing the theoretical occupancy status with the estimated one (obtained from the experimental measurements). The value 1 in occupancy, in the case of the theoretical pattern (blue bar), refers to the fact that during these hours the classroom is theoretically occupied, not to the number of people occupying it. Similarly, the value 2 in occupancy, in the case of the experimental patterns (orange bar), refers to the fact that during these hours the experimental measurements indicate that the classroom was occupied, not to the number of people occupying it. Thus, to facilitate the visualization of the graphs, the unit value of theoretical occupancy patterns (blue bars) indicating that the classroom was theoretically occupied, was increased to the value two for the estimated status identified experimentally as occupied. Both estimated and theoretical patterns had zero value at empty classroom status.
The four suitable variables developed similar occupancy patterns throughout the year. Figure 6 showed that the reference classroom was empty at night and early in the morning during school days, the weekends, and holidays (i.e., 2 November 2020 or August 2020). However, there are some discrepancies in occupancy patterns depending on the variable used as an indicator.
Occupancy patterns from electricity consumption indicators presented more uniform patterns of occupancy on school days. The number of hours of classroom occupancy is the same every school day. This value overestimates the theoretical number of teaching hours in the reference classroom with the exception of profiles derived from the boilers electrical consumption. The boilers electric consumption is a very successful pattern indicator in the non-occupancy periods i.e., holidays, when this conditioning system was not in operation. For the rest of the year the pattern identified from this indicator was equally successful. However, this indicator differed greatly from the theoretical pattern in the coldest month, as well as from the patterns generated from the other electrical indicator variables.
The occupancy patterns obtained from the CO2 concentration indicator presented irregular occupancy profiles throughout the week during school days. It better fits the theoretical occupancy derived from the scholar schedule. However, at certain times during school hours, the room is theoretically identified as empty, but it is identified as occupied according to the CO2 concentration. Observed discrepancies could be explained either by the early entry of students into the classroom, the permanence of a student inside the classroom in the recessed time between classes, or the CO2 concentration decay once the classroom is empty.

4.3. Occupancy Patterns Performance

In this section, a quantitative assessment of the correlations found between occupancy and the investigated variables is showed as a deviation percentage of estimated occupancy patterns from the theoretical ones taken as reference.
To this end, the difference between the times the classroom was occupied according to each variable indicator minus the times the classroom was planned to be occupied according to the official scholar schedule of this classroom was calculated. This difference is displayed as a percentage of hours for each month in Figure 7. The figure shows deviations lower than 25% in all indicator variables, with a global mean deviation of 8.4%. Boilers electricity consumption and CO2 indicators presented the lowest mean percentages of 5% and 7%, respectively. On the contrary, general and building electricity consumption indicators reached higher mean percentages, up to 10% and 11%, respectively.
The occupancy patterns derived from general and building electricity consumption presented some similar behavior throughout the year.
Occupancy patterns from boilers indicators showed low deviations, comparable to the deviations observed for the CO2 indicator in the first and last five months of the considered period. The deviations for the other considered months were slightly larger for the CO2 indicator.

5. Discussion

The occupancy patterns and rates in enclosed areas vary according to the type of activity carried out. The interest of this study is precisely to analyze the impact of the type of activity carried out at the site on the replicability of the developed methodology. In previous studies [30,31], in which this same methodology was applied, the rooms evaluated were office rooms characterized by different occupancy patterns and rates. In this case, the evaluated room is a classroom. The type of activity also affected the datasets to be analyzed as possible indicators. In previous studies, the variables analyzed were related to measurements inside the room. In this case, more general measurements were tested, at building level (electric variables) and not just at room level (air temperature, relative humidity and CO2 concentration).
Optimal variable indicators for the estimation of occupancy patterns are affected by the occupancy rate, that is, the number of people in the room. In previous studies, we have observed that the level of occupancy affects the viability of CO2 concentration as an optimal indicator. In the previous study [30], in which it was concluded that CO2 concentration was “not as informative as expected”, the occupancy level was low, below three people/room. We had observed the same pattern in the Díaz-Hernández et al. [31] study. In the case of offices with low occupancy rates (one or two people/room), the concentration of CO2 as an indicator of occupancy was not as informative as expected. However, the room case with a higher occupancy level (up to ten people) identified CO2 concentration as an optimal indicator. In our study, the number of people increases to a value of twenty-two in some subjects, the most common value being fifteen.
The complexity in measuring the CO2 concentration in occupied spaces should also be noted. Previous studies highlight the relevance of ventilation strategies and air movement on its spatial uniform distribution in a room. In fact, the building ventilation strategy influences the impact of occupancy rates and air changes in indoor CO2 distribution. In this regard, Styme et al. [33] report a vertical CO2 concentration stratification in a room ventilated by a displacement system. Bulinska et al. [34] evaluated the CO2 distribution in naturally ventilated spaces concluding that sensors should be positioned either in the center of the room or towards the airflow outlet door. Pei et al. [35] conclude that mixing ventilation generates horizontal and vertical CO2 uniform distributions and therefore, in this case, the sensor location in the room is not relevant. Finally, Mahyuddin and Awbi [36] provide general procedures on the optimal positioning of CO2 sensors in a room. In this study, the sensors were positioned according to these guidelines.
Power consumption of equipment (PCs) is a good indicator for offices occupancy, but not for classrooms where electrical devices are not always used. In this latter case, more general electricity consumption measurements referring to the building and not to the classroom were found to be more appropriate as occupancy indicators.
The results of this study are limited to the estimation of the occupancy status in order to simplify the monitoring requirements. So, the indicators were suitable in the determination of whether or not an enclosure is occupied, but not in determining the number of people inside it.

6. Conclusions

Air temperature and relative humidity were both discarded as viable indicators of classroom occupancy patterns. On the contrary, the CO2 concentration as well as the electricity consumption variables proved to be optimal indicators for the estimation of these occupancy patterns.
However, these selected indicators presented some deviations between the estimated and the theoretical occupancy status. It depends on the variable used to generate the classroom occupancy pattern, but they were predominantly positive. That means the estimated classroom occupancy hours were higher than the theoretical ones. The higher the occupancy, the greater the uncertainty introduced by the users’ behavior. Therefore, the impact of users is a phenomenon to be analyzed in depth in future studies. Different factors depending on the type of indicator variable could explain the pattern’s uncertainties.
Even though the occupancy patterns identified from the boilers electrical consumption indicator had a good accuracy in the evaluated periods, they presented significant deviations in the coldest month. An increase in boiler operating hours to ensure indoor comfort conditions during school hours could explain this overestimation in occupancy. The same pattern was observed for the CO2 indicator, although, in this case, this overestimation was also observed during the autumn months.
The occupancy pattern derived from the boilers electric consumption presented a particularity: classroom occupancy was not detected if, due to mild weather conditions, the heating systems were not operating. This fact was observed in September, at the beginning of the academic year. The occupancy patterns generated from the rest of valuable variables did not present this problem.

Author Contributions

Methodology and Formal analysis, M.N.S., M.J.J.; Writing—Original Draft, M.N.S., E.G., S.S.; Data Curation, A.R.G., R.O.; Writing—Review & Editing, all authors. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Spanish National Research Agency (Agencia Estatal de Investigación) through the In-Situ-BEPAMAS project (PID2019-105046RB-I00/AEI/10.13039/501100011033). The operation of the test facilities that supported this study was developed in the framework of the ECF4CLIM project (101036505) and ClimACT project (SOE1/P3/P0429).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

The authors would like to thank all the IES Gabriel Garcia Marquez staff for their inestimable support.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. IPCC. Climate Change 2007: Synthesis Report; Contribution of Working Groups I, II and III to the Fourth Assessment Report of the Intergovernmental Panel on Climate Change; Pachauri, R.K., Reisinger, A., Eds.; IPCC: Geneva, Switzerland, 2007. [Google Scholar]
  2. Sánchez, M.N.; Soutullo, S.; Olmedo, R.; Bravo, D.; Castaño, S.; Jiménez, M.J. An experimental methodology to assess the climate impact on the energy performance of buildings: A ten-year evaluation in temperate and cold desert areas. Appl. Energy 2020, 64, 114730. [Google Scholar] [CrossRef]
  3. Zhang, X.; Penaka, S.R.; Giriraj, S.; Sánchez, M.N.; Civiero, P.; Vandevyvere, H. Characterizing Positive Energy District (PED) through a Preliminary Review of 60 Existing Projects in Europe. Buildings 2021, 11, 318. [Google Scholar] [CrossRef]
  4. Sustainable Development Goals (SDGs). Available online: https://sdgs.un.org/goals (accessed on 10 January 2022).
  5. Aver, B.; Fošner, A.; Alfirević, N. Higher Education Challenges: Developing Skills to Address Contemporary Economic and Sustainability Issues. Sustainability 2021, 13, 12567. [Google Scholar] [CrossRef]
  6. Fulzele, R.; Fulzele, V.; Dharwal, M. Mapping the Impact of COVID-19 Crisis on the Progress of Sustainable Development Goals (SDGs)—A Focus on Global Environment and Energy Efficiencies. Mater. Today Proc. 2021, in press. [Google Scholar] [CrossRef] [PubMed]
  7. Ameli, M.; Shams Esfandabadi, Z.; Sadeghi, S.; Ranjbari, M.; Zanetti, M.C. COVID-19 and Sustainable Development Goals (SDGs): Scenario analysis through fuzzy cognitive map modeling. Gondwana Res. 2022, in press. [Google Scholar] [CrossRef] [PubMed]
  8. Soutullo, S.; Sánchez, M.N.; Enríquez, R.; Olmedo, R.; Jiménez, M.J. Bioclimatic vs. conventional building: Experimental quantification of the thermal improvements. Energy Procedia 2017, 122, 823–828. [Google Scholar] [CrossRef]
  9. Nurunnabi, M.; Esquer, J.; Munguia, N.; Zepeda, D.; Perez, R.; Velazquez, L. Reaching the sustainable development goals 2030: Energy efficiency as an approach to corporate social responsibility (CSR). GeoJournal 2020, 85, 363–374. [Google Scholar] [CrossRef]
  10. Di Foggia, G. Energy efficiency measures in buildings for achieving sustainable development goals. Heliyon 2018, 4, e00953. [Google Scholar] [CrossRef] [Green Version]
  11. Directive (EU) 2018/844 of the European Parliament and of the Council of 30 May 2018 Amending Directive 2010/31/EU on the Energy Performance of Buildings and Directive 2012/27/EU on Energy Efficiency Directive. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/PDF/?uri=CELEX:32018L0844&from=IT (accessed on 18 April 2022).
  12. Soutullo, S.; Giancola, E.; Franco, J.M.; Boton, M.; Ferrer, J.A.; Heras, M.R. New simulation platform for the rehabilitation of residential buildings in Madrid. Energy Procedia 2017, 122, 817–822. [Google Scholar] [CrossRef]
  13. Sanjuan, C.; Sánchez, M.N.; Enriquez, R.; Heras, M.R. Experimental PIV Techniques Applied to the Analysis of Natural Convection in Open Joint Ventilated Facades. Energy Procedia 2012, 30, 1216–1225. [Google Scholar] [CrossRef] [Green Version]
  14. Sánchez, M.N.; Giancola, E.; Blanco, E.; Soutullo, S.; Suárez, M.J. Experimental Validation of a Numerical Model of a Ventilated Façade with Horizontal and Vertical Open Joints. Energies 2020, 13, 146. [Google Scholar] [CrossRef] [Green Version]
  15. Wei, Y.; Xia, L.; Pan, S.; Wu, J.; Zhang, X.; Han, M.; Zhang, W.; Xie, J.; Li, Q. Prediction of occupancy level and energy consumption in office building using blind system identification and neural networks. Appl. Energy 2019, 240, 276–294. [Google Scholar] [CrossRef]
  16. ASHRAE Multidisciplinary Task Group on Occupant Behaviour in Buildings (MTG. OBB). Available online: https://www.ashrae.org/ (accessed on 10 January 2022).
  17. Annex 66 of the Programme “(EBC)” of the IEA on “Definition and Simulation of Occupant Behavior in Buildings”. Available online: http://www.annex66.org/ (accessed on 10 January 2022).
  18. Annex 79 of the Programme “(EBC)” of the IEA on “Occupant-Centric Building Design and Operation”. Available online: https://annex79.iea-ebc.org/ (accessed on 10 January 2022).
  19. Hou, H.; Pawlak, J.; Sivakumar, A.; Howard, B.; Polak, J. An approach for building occupancy modelling considering the urban context. Build. Environ. 2020, 183, 107126. [Google Scholar] [CrossRef]
  20. Causone, F.; Carlucci, S.; Ferrando, M.; Marchenko, A.; Erba, S. A data-driven procedure to model occupancy and occupant-related electric load profiles in residential buildings for energy simulation. Energy Build. 2019, 202, 109342. [Google Scholar] [CrossRef]
  21. Mitra, D.; Chu, Y.; Cetin, K. Cluster analysis of occupancy schedules in residential buildings in the United States. Energy Build. 2021, 236, 110791. [Google Scholar] [CrossRef]
  22. Kang, X.; Yan, D.; An, J.; Jin, Y.; Sun, H. Typical weekly occupancy profiles in non-residential buildings based on mobile positioning data. Energy Build. 2021, 250, 111264. [Google Scholar] [CrossRef]
  23. Bianchi, C.; Zhang, L.; Goldwasser, D.; Parker, A.; Horsey, H. Modeling occupancy-driven building loads for large and diversified building stocks through the use of parametric schedules. Appl. Energy 2020, 276, 115470. [Google Scholar] [CrossRef]
  24. Anand, P.; Cheong, D.; Sekhar, C. A review of occupancy-based building energy and IEQ controls and its future post-COVID. Sci. Total Environ. 2022, 804, 150249. [Google Scholar] [CrossRef]
  25. Soutullo, S.; Sánchez, M.N.; Enríquez, R.; Jiménez, M.J.; Heras, M.R. Empirical estimation of the climatic representativeness in two different areas: Desert and Mediterranean climates. Energy Procedia 2017, 122, 829–834. [Google Scholar] [CrossRef]
  26. Soutullo, S.; Giancola, E.; Ferrer, J.A.; Jiménez, M.J.; Sánchez, M.N. How Climate Trends Impact on the Thermal Performance of a Typical Residential Building in Madrid. Energies 2020, 13, 237. [Google Scholar] [CrossRef] [Green Version]
  27. Gamarra, A.R.; Herrera, I.; Lechón, Y. Assessing sustainability performance in the educational sector. A high school case study. Sci. Total Environ. 2019, 692, 465–478. [Google Scholar] [CrossRef] [PubMed]
  28. Gamarra, A.R.; Istrate, I.R.; Herrera, I.; Lago, C.; Lizana, J.; Lechón, Y. Energy and water consumption and carbon footprint of school buildings in hot climate conditions. Results from life cycle assessment. J. Clean. Prod. 2018, 195, 1326–1337. [Google Scholar] [CrossRef]
  29. ClimACT Project. Transition to a Low Carbon Economy in Schools. Available online: https://www.climact.net/ (accessed on 10 January 2022).
  30. Diaz, J.A.; Jiménez, M.J. Experimental assessment of room occupancy patterns in an office building. Comparison of different approaches based on CO2 concentrations and computer power consumption. Appl. Energy 2017, 199, 121–141. [Google Scholar] [CrossRef]
  31. Díaz-Hernández, H.P.; Sánchez, M.N.; Olmedo, R.; Villar-Ramos, M.M.; Macias-Melo, E.V.; Aguilar-Castro, K.M.; Jiménez, M.J. Performance assessment of different measured variables from onboard monitoring system to obtain the occupancy patterns of rooms in an office building. J. Build. Eng. 2021, 40, 102676. [Google Scholar] [CrossRef]
  32. Schwarz, D. Fast and Robust Curve Intersections. MATLAB Central File Exchange. Available online: https://www.mathworks.com/matlabcentral/fileexchange/11837-fast-and-robust-curve-intersections?s_tid=srchtitle (accessed on 10 January 2022).
  33. Stymne, H.; Sandberg, M.; Mattsson, M. Dispersion pattern of contaminants in a displacement ventilated room-implications for demand control. In Proceedings of the 12th AIVC Conference, Ottawa, ON, Canada, 24–27 September 1991. [Google Scholar]
  34. Bulinska, A.; Popiołek, Z.; Bulinski, Z. Experimentally validated CFD analysis on sampling region determination of average indoor carbon dioxide concentration in occupied space. Build. Environ. 2014, 72, 319–331. [Google Scholar] [CrossRef]
  35. Pei, G.; Rim, D.; Schiavon, S.; Vannucci, M. Effect of sensor position on the performance of CO2-based demand controlled ventilation. Energy Build. 2019, 202, 109358. [Google Scholar] [CrossRef] [Green Version]
  36. Mahyuddin, N.; Awbi, H. The spatial distribution of carbon dioxide in an environmental test chamber. Build. Environ. 2010, 45, 1993–2001. [Google Scholar] [CrossRef]
Figure 1. IES Gabriel García Márquez public high school.
Figure 1. IES Gabriel García Márquez public high school.
Energies 15 03112 g001
Figure 2. Overview selected classroom (a) real image and (b) schema of the monitoring.
Figure 2. Overview selected classroom (a) real image and (b) schema of the monitoring.
Energies 15 03112 g002
Figure 3. Overview of the typical annual behavior of different variables assessed as possible indicators of occupancy status in schools.
Figure 3. Overview of the typical annual behavior of different variables assessed as possible indicators of occupancy status in schools.
Energies 15 03112 g003
Figure 4. Overview of the typical monthly behavior of different variables assessed as possible indicators of occupancy status in schools), with (a,c,e,g) data from vacation vs. (b,d,f,h) data from the scholar period.
Figure 4. Overview of the typical monthly behavior of different variables assessed as possible indicators of occupancy status in schools), with (a,c,e,g) data from vacation vs. (b,d,f,h) data from the scholar period.
Energies 15 03112 g004
Figure 5. Annual histograms of different variables assessed as possible indicators of occupancy status in schools: (a) temperature, (b) relative humidity, (c) CO2 concentration, (d) general electricity consumption, (e) building electricity consumption and (f) boilers electricity consumption. Blue line represents when the classroom was empty vs. green line when the room might be occupied.
Figure 5. Annual histograms of different variables assessed as possible indicators of occupancy status in schools: (a) temperature, (b) relative humidity, (c) CO2 concentration, (d) general electricity consumption, (e) building electricity consumption and (f) boilers electricity consumption. Blue line represents when the classroom was empty vs. green line when the room might be occupied.
Energies 15 03112 g005
Figure 6. Monthly occupancy classroom patterns obtained from the assessed candidate variables (blue bars) vs. theoretical occupancy (orange bars), with (a,c,e,g) data from vacation vs. (b,d,f,h) data from the scholar period.
Figure 6. Monthly occupancy classroom patterns obtained from the assessed candidate variables (blue bars) vs. theoretical occupancy (orange bars), with (a,c,e,g) data from vacation vs. (b,d,f,h) data from the scholar period.
Energies 15 03112 g006
Figure 7. Monthly deviation in percentage of classroom occupancy hours: estimated vs. theoretical for the CO2 concentration indicator and electricity consumption indicators.
Figure 7. Monthly deviation in percentage of classroom occupancy hours: estimated vs. theoretical for the CO2 concentration indicator and electricity consumption indicators.
Energies 15 03112 g007
Table 1. Intervals considered in the histogram generation, both tried and finally used. Additional information on the maximum uncertainty of the measurement probes.
Table 1. Intervals considered in the histogram generation, both tried and finally used. Additional information on the maximum uncertainty of the measurement probes.
Air TemperatureRelative HumidityCO2 ConcentrationSchool Electricity ConsumptionBuilding Electricity ConsumptionBoilers Electricity Consumption
(°C)(%)(ppm)(kWh)(kWh)(kWh)
Tried intervals155; 100.50.250.05
Selected intervals15100.50.250.05
Maximum uncertainty±1 °C±3.5%±30 ppmclass 0.5class 0.5class 0.5
Table 2. Theoretical occupancy patterns of classroom: Academic year 2020/2021 (until 19 April 2021).
Table 2. Theoretical occupancy patterns of classroom: Academic year 2020/2021 (until 19 April 2021).
Official TimeMondayTuesdayWednesdayThursdayFridaySat &Sun
(Hours)(Number of People)
8:25 to 9:201515015150
9:20 to 10:1515151515150
10:15 to 11:101515151500
11:10 to 11:35Not occupied (recess)
11:35 to 12:301515015150
12:30 to 13:251515150120
13:25 to 14:20012152200
Table 3. Occupancy status breakpoints.
Table 3. Occupancy status breakpoints.
VariableBreakpoint
Temperature-
Relative humidity-
CO2 concentration>470 ppm
General electricity consumption>2 KWh
Building electricity consumption>0.55 KWh
Boilers electricity consumption>0.05 KWh
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Sánchez, M.N.; Giancola, E.; Soutullo, S.; Gamarra, A.R.; Olmedo, R.; Ferrer, J.A.; Jiménez, M.J. Suitability Evaluation of Different Measured Variables to Assess the Occupancy Patterns of a Building: Analysis of a Classroom of a School in Madrid during the COVID-19 Pandemic. Energies 2022, 15, 3112. https://doi.org/10.3390/en15093112

AMA Style

Sánchez MN, Giancola E, Soutullo S, Gamarra AR, Olmedo R, Ferrer JA, Jiménez MJ. Suitability Evaluation of Different Measured Variables to Assess the Occupancy Patterns of a Building: Analysis of a Classroom of a School in Madrid during the COVID-19 Pandemic. Energies. 2022; 15(9):3112. https://doi.org/10.3390/en15093112

Chicago/Turabian Style

Sánchez, María Nuria, Emanuela Giancola, Silvia Soutullo, Ana Rosa Gamarra, Rafael Olmedo, José Antonio Ferrer, and María José Jiménez. 2022. "Suitability Evaluation of Different Measured Variables to Assess the Occupancy Patterns of a Building: Analysis of a Classroom of a School in Madrid during the COVID-19 Pandemic" Energies 15, no. 9: 3112. https://doi.org/10.3390/en15093112

APA Style

Sánchez, M. N., Giancola, E., Soutullo, S., Gamarra, A. R., Olmedo, R., Ferrer, J. A., & Jiménez, M. J. (2022). Suitability Evaluation of Different Measured Variables to Assess the Occupancy Patterns of a Building: Analysis of a Classroom of a School in Madrid during the COVID-19 Pandemic. Energies, 15(9), 3112. https://doi.org/10.3390/en15093112

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop