Next Article in Journal
Ultra-High-Performance Alkali-Activated Concrete: Effect of Waste Crumb Rubber Aggregate Proportions on Tensile and Flexural Properties
Previous Article in Journal
An Investigation on the Seismic Behavior of the End-Plate Connection between a Steel Beam and the Weak-Axis of an H-Shaped Column Using a U-Shaped Connector
Previous Article in Special Issue
Achieving Energy Self-Sufficiency in a Dormitory Building: An Experimental Analysis of a PV–AWHP-ERV Integrated System
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Impact of Insulation Strategies of Cross-Laminated Timber Assemblies on Energy Use, Peak Demand, and Carbon Emissions

by
Mikael Salonvaara
* and
André Desjarlais
Oak Ridge National Laboratory, Oak Ridge, TN 37830, USA
*
Author to whom correspondence should be addressed.
Buildings 2024, 14(4), 1089; https://doi.org/10.3390/buildings14041089
Submission received: 1 March 2024 / Revised: 7 April 2024 / Accepted: 10 April 2024 / Published: 13 April 2024
(This article belongs to the Special Issue Advanced Building Technologies for Energy Savings and Decarbonization)

Abstract

:
Cross-Laminated Timber (CLT) panels have many structural benefits but do not have much thermal resistance. We have developed a solution to insulate CLT structures that uses high-performance insulation panels that provide R-values up to R40/inch. The CLT panels are made of layers of wood laminates (three, five, seven or more). The solution replaces some of the wood laminates in the CLT production with the insulation panels in a staggered fashion so that the wood laminates maintain contact throughout the panel, ensuring the CLT panel’s structural integrity. The insulated CLT panels have factory-installed water-resistive barriers reducing the installation time by eliminating installing insulation and water-resistive barriers on site. Per simulations, the CLT/insulation panel achieved code-required insulation levels with commonly available insulation materials. The significance of the thermal mass of CLT/insulation hybrid building envelopes was quantified by comparing the whole building energy performance and peak demand of traditional low mass and CLT wall assemblies resulting in up to 7% reduction in peak demand for cooling in Knoxville, TN, in a multifamily building. Buildings contribute over 40 percent of carbon emissions. The proposed CLT/insulation hybrid building envelope addresses both operational and embodied carbon by having high thermal resistances due to the embedded insulation sections and eliminating the use of high embodied carbon materials such as steel and concrete. The carbon benefit is estimated.

1. Introduction

Cross-laminated timber (CLT) has gained significant traction in the building construction industry for several reasons, ranging from environmental benefits to structural performance. There are multifaceted reasons behind the increasing popularity of CLT in building construction, such as its sustainability, efficiency, versatility, and positive impact on the construction process and the built environment. The prefabrication of CLT panels off-site allows for quicker assembly times on construction sites, significantly reducing the overall build time of projects. This efficiency translates to cost savings and minimizes the environmental impact and disruption typically associated with construction activities. Compared to traditional construction materials, the lightweight nature of CLT further reduces transportation and handling costs, contributing to the economic and environmental efficiency of construction projects. This paper discusses an innovative product that further reduces construction times while providing a compact, thermally insulated CLT panel.
In April 2024, the U.S. Department of Energy released the first-ever federal blueprint to decarbonize America’s buildings sector [1]. The blueprint is designed to cut greenhouse gas emissions from U.S. buildings by 65% by 2035 and by 90% by 2050, compared to levels in 2005, focusing on fairness and community advantages. It establishes three overarching goals related to fairness, cost-effectiveness, and resilience, aimed at ensuring that the transition to low-carbon buildings aids underserved communities, lowers energy expenses, and enhances the resilience of communities to stressors. Additionally, the blueprint outlines four key strategic objectives, each with defined performance goals, to facilitate the overall reduction in emissions: Increase building energy efficiency, accelerate onsite emissions reductions, transform the grid edge, and minimize embodied life cycle emissions. Compared with steel and concrete construction, CLT is a low-impact material with a much lower carbon footprint. Using a material such as CLT offers carbon benefits through the sequestered carbon throughout the lifetime of the timber, and unlike concrete and steel, it is a regenerative material.
In their comprehensive literature review, Cabral and Blanchet [2] highlight the significant energy efficiency advantages of mass timber and hybrid construction systems, despite the current scarcity of specific design codes and standards for these innovative building methods. They particularly emphasize the potential of Cross-Laminated Timber (CLT) to outperform traditional construction materials like concrete and light steel frames, with possible energy savings reaching up to 40%. A notable advantage of CLT lies in its ability to minimize thermal bridging, thereby facilitating achieving stringent energy performance benchmarks. Moreover, the inherent airtightness of CLT structures contributes to further energy conservation by reducing uncontrolled ventilation and enhancing the operational energy efficiency of buildings. Salonvaara et al. [3] studied the benefits of mass timber in buildings, demonstrating notable reductions in annual energy use and peak demand, alongside improved thermal comfort, compared to conventional lightweight wall systems. The laboratory tests and simulation research revealed mass timber’s ability to shift heating and cooling energy demand away from peak hours, resulting in a 30–50% reduction in peak demand and enhancing thermal comfort by reducing uncomfortable hours by up to 46%. The thermal mass of CLT contributes to energy efficiency, maintaining stable indoor temperatures and reducing the need for mechanical heating and cooling. Setter et al. [4] showed a 38% reduction in annual heating energy in Minneapolis, MN, and a 17% reduction in annual cooling energy in Phoenix, AZ, with simulations. These findings advocate for integrating mass timber as an effective energy efficiency and thermal management strategy in various climate zones. In their comprehensive review within the context of Cross-Laminated Timber (CLT) development and application, Ren et al. [5] assert that CLT emerges as a superior building material when evaluated against criteria such as energy consumption, environmental impact, and structural integrity as corroborated by the majority of sources referenced in their study. They forecast that future research in CLT could pivot around several areas, such as the innovation of non-adhesive CLT solutions to eliminate reliance on chemical binders, enhancements in CLT logistics aimed at optimizing energy efficiency, advancements in the design and functionality of edge connections, mass CLT elements, and the investigation into the airtightness of CLT structures and their energy performance.
Past research on combining insulation with CLT panels is available. Santos et al. [6] focused on a sandwich wall-panel solution based on CLT, aiming to improve thermal insulation and reduce weight by combining wood with a low-density core layer. They presented a Life-Cycle Analysis (LCA) study about the product’s environmental impact. The layout of the new panel is like that of a five-layer CLT panel, but they replaced the inner layer with rigid polyurethane foam. In a follow-up paper [7], they explored the new panel layout named Cross-Insulated Timber (CIT), which uses polyurethane (PUR) rigid foam instead of timber for the inner layer to improve thermal insulation and reduce weight for acoustic and thermal behavior. The CIT panel included four layers of solid wood lamellae with one solid rigid insulation layer in the middle.
Reducing wood content inside the CLT panels impacts its acoustical and structural performance and fire rating. Huang et al. [8] showed that the hollow cores have little effect on the static bending stiffness of the CLT panels. However, there were indications that the hollow cores could degrade the floor dynamic bending stiffness.
This manuscript’s investigation exclusively concentrates on thermal performance aspects. The novel method, replacing pieces of wood boards inside the CLT panel in a staggered fashion, provides a compact, readily insulated CLT panel. The paper constitutes a preliminary analysis, emphasizing the steady-state thermal behavior and the thermal delay characteristics of heat flow through the assembly. Should this foundational examination prove satisfactory, subsequent investigations will encompass fire safety, structural integrity, and other pertinent parameters.

2. Materials and Methods

In this study, we enhanced the thermal performance of Cross-Laminated Timber (CLT) by integrating insulation within its structure and devising an innovative insulated CLT panel. Traditional CLT comprises multiple layers of lumber, with each layer’s wood grain oriented perpendicularly to adjacent ones. Our modification involved substituting a portion of the wood with insulation material in two or three layers, thereby creating partially insulated lamellae within the CLT matrix.
The standard configuration of the CLT used in our experiments was a five-ply structure, with each ply measuring 34.9 mm in thickness, culminating in a total panel thickness of 174.6 mm. To assess the impact of varying insulation properties, we experimented with insulation materials offering a range of thermal conductivity, including 0.0036 W/m·K (vacuum insulation panel) and extending up to 0.11 W/m·K (typical of wood), representing a broad spectrum of thermal conductivity.
A key variable in our study was the ‘insulation ratio’, which refers to the proportion of insulation substituted for wood in the partially insulated layers. Values range from 30% to 70%. This parameter allowed us to explore the structural integrity and thermal performance balance.
We compared the thermal efficiency of our modified CLT panels against a conventional insulation strategy, termed the ‘1D-assembly’. This conventional model consists of a solid wood panel paired with a continuous layer of insulation, maintaining the same overall thickness but lacking the integrated approach of the insulated CLT. The volumes of the wood and insulation materials are identical in the 1D assembly and the insulated CLT.
Our analysis included two configurations: (1) one with insulation replacing wood in two CLT layers and (2) another with three middle layers substituted with insulation. We employed the COMSOL Multiphysics® software v6.2 [9] for our simulations, enabling detailed modeling and calculating the effective surface-to-surface R-value, thereby quantifying the thermal performance enhancements achieved through our insulated CLT design.

3. Results

The simulations for heat transfer through the CLT panels with varying degrees of insulation were carried out for a panel size mimicking one that would be used in a heat flow meter apparatus. The panel size was 0.61 m × 0.61 m with an overall thickness of 175 mm for a five-ply CLT with 35 mm layers.
The thermal properties of the wood used in the simulations for the CLT were
  • Density 500 kg/m3
  • Specific heat capacity 1880 J/kg·K
  • Thermal conductivity 0.11 W/m·K
Staggering the insulation layers in the CLT was created in the test sample by placing the insulation layers at 0.61 m on-center distance from each other, creating a symmetric boundary condition on the sides.

3.1. Staggered Insulation in Two Lamellae of CLT

An insulated CLT assembly was created by replacing some pieces of wood in two layers of a CLT assembly with insulation (Figure 1). Both layers had the same percentage of insulation in the total area.
The assembly is a five-ply CLT with the layers listed in Table 1.
The resulting effective R-values as a function of insulation’s R-value and area coverage are shown in Table 2. The insulation ratio is the same for each partially insulated layer (2 and 4).
Figure 2 and Figure 3 demonstrate that the overall R-value of the partially insulated CLT panel depends linearly on the insulation ratio in the two-layer staggered system. The impact of thermal bridging between the insulation layers is less than 12% when the insulation’s thermal conductivity is higher or equal to 0.018 W/m·K. The thermal bypasses in the system with vacuum insulation, 0.0036 W/m·K, reduce the overall R-value to half that of a system with continuous insulation when the insulation ratio is 0.3 and the volume of the insulation material is the same. The higher the insulation ratio, the smaller the impact of thermal bridging on the overall R-value.

3.2. Staggered Insulation in Three Lamellae of CLT

The insulated CLT system with insulation in two lamellas of CLT was further improved by adding insulation in the third lamellae (Figure 4). This layer runs perpendicular to the other two layers with insulation. All three layers had the same percentage of insulation in the total area.
The assembly is a five-ply CLT with the lamellae listed in Table 3.
The resulting effective R-values as a function of the insulation’s R-value and area coverage are shown in Table 4. The insulation ratio is the same for each partially insulated layer (2, 3, and 4).
Figure 5 and Figure 6 demonstrate that the overall R-value of the partially insulated CLT panel depends linearly on the insulation ratio in the two-layer staggered system.
In a two-layer insulated system, the impact of thermal bridging between the insulation layers is less than 17% when the insulation’s thermal conductivity is equal to or higher than 0.018 W/m·K. The thermal bypasses in the system with vacuum insulation, 0.0036 W/m·K, reduce the overall R-value by 64% of that of a system with continuous insulation when the insulation ratio is 0.3 and the volume of the insulation material is the same. Comparing these results to the three-layer insulation system, we notice that the impact of thermal bridges is higher in the three-layer system, up to 21% with k = 0.018 W/m·K insulation and 68% with k = 0.0036 W/m·K. The higher the insulation ratio, the smaller the impact of thermal bridging on the overall R-value.

3.3. Comparing the Two- and Three-Layer Staggered Insulation CLTs

Figure 7 compares the two- and three-layer staggered insulated systems with thermal conductivity values of 0.0036 and 0.024 for the insulation. The three-layer staggered system provides a better R-value than the two-layer system with the same insulation ratio. However, the three-layer insulation system uses more insulation at the same ratio. Table 5 shows the volume percentage of insulation when the insulation is placed in two or three layers of the CLT. Comparing the two systems at the same volume of insulation used, we can take, for example, an insulation ratio of 0.5 for the two-layer system and 0.33 for the three-layer system. In this case, both systems have one full layer of insulation out of five in the CLT. The two-layer system with R-40 per inch insulation (k = 0.0036 W/m·K) achieves an R-value of 5.1 m2K/W, whereas the three-layer system achieves only 3.8 m2/K/W. Therefore, the arrangement in the two-layer system is more efficient in recovering the R-value of a continuous insulation layer.

3.4. Validating Simulations with an Experimental Test

Simulations can provide theoretical values that are not necessarily replicated in real assemblies due to imperfections such as gaps between components. To validate that the simulations mimic reality, we tested one assembly with insulation in three lamellae of a five-ply CLT in a heat flow meter apparatus for a sample size of 610 mm × 610 mm. The assembly had three solid 203 mm wide wood layers of 16.7 mm thick on top and bottom. Out of the three 19.1 mm middle layers, the top and middle layers had 33% insulation in a staggered fashion (insulation ratio = 0.33) (Figure 8). The bottom 19.1 mm layer has 2/3 insulation of the total area. The total thickness of the assembly was 90.5 mm.
The insulation’s thermal conductivity was measured in the heat flow meter and was found to be 0.033 W/m·K. The thermal conductivity of the wood was not measured but assumed to be 0.11 W/m·K. The materials and assembly were tested using a FOX 600 heat flow meter with an absolute thermal conductivity accuracy of ±1% and reproducibility of ±0.5%. The heat flow meter measures the heat flow in the center of the surfaces in an area of 254 mm × 254 mm (Figure 8). The tested and simulated steady-state results are shown in Table 6 for a temperature difference of 22.2 K at an average temperature of 23.9 °C. The difference between the simulated and tested results is small, less than 2%, indicating that the simulations provide accurate predictions.

3.5. Dynamic Calculations

The thermal mass inherent in construction materials facilitates the absorption and storage of heat, adapting to fluctuating environmental conditions. The integration of heat capacity and thermal conductivity modulates the heat transfer rate through the material, thereby attenuating the intensity of peak thermal fluxes. The effect of thermal mass is well characterized in homogeneous material layers. The insulated CLT panels have staggered internal layers, and the dynamic performance is not as easy to estimate without advanced modeling. We simulated the transient response of the uninsulated and insulated CLT panels of the same thickness to show the impact of the insulation on the time delay and magnitude of the heat flux on the interior side when the panel was exposed to sine wave temperature on the exterior side. The sine wave had a 24 h cycle, which could be expected in natural weather exposure in buildings. The exterior and interior surface had a convection heat transfer coefficient of 10 W/m2K.
The simulations were conducted for the staggered two-layer insulation system with an insulation ratio of 0.5 and a thermal conductivity of insulation 0.024 W/m·K. Five systems were simulated with the same overall thickness of 175 mm:
  • Solid CLT panel
  • Staggered two-layer insulated CLT panel
  • CLT panel with continuous insulation on the exterior side
  • CLT panel with continuous insulation in the middle of the panel
  • CLT panel with continuous insulation on the interior side
Figure 9 shows how the insulation layers in the CLT panel lower the heat flux through the panel while still providing the same long time delay for the peak (~12 h). Shifting the peak heat flux from the daytime to night reduces energy use during peak demand hours, typically in the afternoon and evening hours for cooling climates.

3.6. Targeted Thermal Performance

The integration of insulation within Cross-Laminated Timber (CLT) panels represents a significant advancement in construction technology. It aligns with rigorous building codes for thermal performance without necessitating additional insulation applications on-site. Our study evaluates the compatibility of these innovative hybrid CLT panels with the 2021 International Residential Code (IRC) [10], focusing on the mandated insulation R-value and U-value requirements across diverse International Energy Conservation Code (IECC) climate zones (Table 7).
According to the IRC, walls possessing a thermal mass exceeding 123 kJ/m2·K are classified as mass walls within the thermal envelope of a building. The IECC standards for commercial buildings set this threshold at 103 kJ/m2·K for materials weighing under 1900 kg/m3. Our analysis indicates that 175 mm thick CLT panels, comprised of solid wood, have a thermal mass of 164 kJ/m2·K, qualifying them as mass walls. Notably, embedding insulation up to 25% by volume within these panels does not affect their classification as mass walls in residential constructions. However, this percentage might vary depending on the wood used in the CLT panels.
From a thermal performance standpoint, a 175 mm thick uninsulated CLT panel, with a thermal conductivity of 0.11 W/m·K, achieves an R-value of 1.6 m2·K/W. This results in a U-value of 0.63 W/m2·K, meeting the IECC requirements for climate zones 0 to 2. Thus, the superior thermal efficiency of wood is underscored.
Further analysis of insulated CLT configurations, such as a two-layer staggered arrangement with 20% insulation volume of k = 0.024 W/m·K insulation, revealed an R-value of 2.5 m2·K/W. A similar three-layer configuration yielded an R-value of 2.4 m2·K/W, with the two-layer system’s improved thermal efficiency mainly due to reduced thermal bridging. The U-value for the two-layer insulated system was calculated at 0.40 W/m2·K, demonstrating that hybrid CLT panels can meet building code requirements across a broad range of climate zones.
Including additional layers, such as gypsum boards and exterior sidings, along with surface resistances, can further enhance thermal resistance by at least R-0.35 m2·K/W, leading to a U-value of 0.34 W/m2·K. This is adequate for meeting the thermal requirements of climate zone 6 for mass walls and zones 0 to 3 for frame walls. Increasing the insulation ratio to 28% of the total volume, with an insulation thermal conductivity of 0.024 W/m·K, results in a U-value of approximately 0.30 W/m2·K, fulfilling the insulation criteria for all climate zones for mass walls.
While traditional rigid foam insulations provide thermal conductivity down to 0.024 W/m·K, advanced materials like vacuum insulation panels offer higher insulation properties. However, these materials require protection from mechanical damage to maintain their insulating effectiveness. Embedding such panels within CLT structures can safeguard them, ensuring the durability and performance of the insulation.

3.7. Impact of CLT on Peak Demand

The impact of thermal mass on peak demand and annual energy use for heating and cooling was predicted by using a whole-building simulation model, EnergyPlus [12]. EnergyPlusTM is a comprehensive building energy simulation program developed with contributions from several national labs and organizations under the funding and guidance of the U.S. Department of Energy (DOE). Since its inception in 1997, EnergyPlus has been subject to continuous updates and enhancements, reflecting the latest in building energy modeling research and technology.
DOE has created prototype building models for EnergyPlus for different types of buildings [13]. For the simulations, we chose a three-story multifamily building (Figure 10) with a heat pump for heating and cooling in Knoxville, TN. Of the total building area, 3623 m2, 2007 m2 is conditioned. The base model has features, such as the exterior wall construction, per the International Energy Conservation Code 2021. The base model with the lightweight wall assembly was modified by replacing the wood-frame structure with an insulated CLT assembly while maintaining the U-value of 0.271 W/m2·K. No other changes were made to the model inputs except changing the location and weather file to Knoxville, TN. Thus, all the equipment, internal loads, occupancy schedules, and set points were preserved. The wall layers and their properties are listed in Table 8. Note that EnergyPlus treats wall assemblies as one-dimensional components. The two-dimensional staggered system must be simplified to a three-layer setup with half the thickness of CLT on each side of an insulation layer. Columns LW and CLT show which layers are part of the lightweight and CLT wall assemblies.
The annual energy consumption for heating and cooling exhibited a reduction of 2.4% when employing the Cross-Laminated Timber (CLT) wall assembly, compared to the lightweight construction. Specifically, the building outfitted with CLT walls recorded an electricity usage of 53,215 kWh, whereas the structure with lightweight walls accounted for 54,500 kWh. Figure 11 delineates the diurnal heating demand, identifying a morning peak where the CLT wall assembly facilitates a 5.2% decrease in heating requirements compared to its lightweight counterpart. Figure 12 illustrates the cooling demand patterns during August, pinpointing the peak cooling load. Notably, in August, the CLT wall assembly demonstrated a 7.1% reduction in peak cooling demand relative to the lightweight construction, underscoring its efficiency in thermal management.
The results show that the CLT wall assembly dampens the heat flows through the exterior wall and flattens the heating and cooling demand between night and day. For example, the CLT building has higher cooling demand at night but lower in the afternoon and evening.

3.8. Carbon Benefits of the Insulated CLT

Considering sequestered carbon in the embodied carbon calculations for mass timber and Cross-Laminated Timber (CLT) is a topic of ongoing debate within the sustainability and construction communities. Trees absorb carbon dioxide from the atmosphere as they grow, known as carbon sequestration. When trees are harvested and used in building materials like mass timber and CLT, that carbon is effectively stored in the built environment, potentially for decades or centuries. Including sequestered carbon in embodied carbon calculations acknowledges this benefit and can show mass timber and CLT as more sustainable options than materials like steel or concrete, which have higher embodied carbon and do not sequester carbon.
Accounting for sequestered carbon adds complexity to embodied carbon calculations due to the need to consider factors like the source of the timber, forest management practices, and the likelihood of the carbon being released back into the atmosphere at the end of the product’s life (e.g., through decay or combustion). These factors can vary widely and introduce uncertainty into the calculations. There is a risk that the same sequestered carbon could be counted multiple times in different products or accounting systems, leading to overestimating the actual carbon benefits. For example, if the carbon sequestered by a forest is counted in national carbon inventories, counting it again in the embodied carbon of timber products could lead to double counting. The carbon stored in mass timber and CLT will eventually be released back into the atmosphere when the material decomposes or is burned at the end of its life. Unless there are guarantees that the material will be reused, recycled, or permanently sequestered, including sequestered carbon in embodied calculations could give a misleading impression of the material’s long-term environmental impact.
The impact of internally insulated CLT on carbon released to the atmosphere is multifaceted, involving considerations of operational and embodied carbon, carbon sequestration, construction efficiency, and end-of-life scenarios. The overall impact will depend on factors such as the choice of insulation materials, the energy sources used during the building’s operation, and the practices for managing the building materials at the end of their life. Substituting some wood layers with insulation material will alter the embodied carbon of the CLT panels. The net effect on embodied carbon will depend on the type of insulation material used. If the insulation is made from materials with low embodied carbon, the overall embodied carbon of the insulated CLT panels may be lower than standard CLT panels. Conversely, if the insulation material has high embodied carbon (e.g., certain foams or plastics), it could increase the total embodied carbon of the panels. The pre-installation of water-resistive barriers and the integration of insulation can streamline the construction process, reducing the time and potentially the energy required on-site. This efficiency can lead to lower carbon emissions associated with construction activities.
Improved energy efficiency in buildings can reduce the overall energy demand, potentially leading to decreased carbon emissions at a larger scale within the energy grid, assuming a mix of fossil fuels and renewable energy sources.
On a negative note, non-wood materials (like insulation and water-resistive barriers) within the CLT panels could complicate recycling or reuse at the end of the building’s life, potentially leading to higher carbon emissions associated with waste processing or disposal. However, the impact could be mitigated if these materials are selected for recyclability or systems are in place for recovery.

4. Discussion

This paper presents a novel method for enhancing the thermal efficiency of Cross-Laminated Timber (CLT) panels, which are traditionally characterized by their low thermal resistance. By embedding high-performance insulation within the CLT framework in a staggered arrangement, this approach not only preserves the structural integrity of the CLT panels but also significantly boosts their thermal insulation capabilities. This innovative technique streamlines the construction process by diminishing the need for additional insulation and water-resistive barriers to be applied on-site. The research assesses the impact of this integrated CLT-insulation system on the building’s energy performance and carbon footprint, juxtaposing it with conventional construction materials. The findings underscore the dual benefits of this system in enhancing energy efficiency during the building’s operational phase and reducing embodied carbon, thereby underscoring its potential to advance more ecologically responsible construction methodologies.
This study highlights the potential of hybrid CLT panels with integrated insulation to streamline construction processes and enhance thermal performance, aligning with energy conservation goals outlined in building codes. Future work will involve detailed species-specific analysis to further optimize this innovative building solution. Additionally, the structural and fire performance requirements must be evaluated to comply with the code referenced ANSI/APA PRG 320: Standard for Performance-Rated Cross-Laminated Timber to allow the use of novel products in buildings [14].

5. Conclusions

This paper explored the development and performance evaluation of partially insulated Cross-Laminated Timber (CLT) panels, integrating high-performance insulation within the panel structure to enhance thermal efficiency without compromising structural integrity. Through a comprehensive literature review, we identified a gap in existing research regarding the thermal optimization of CLT panels. We addressed this by proposing an innovative configuration incorporating hollow or insulated core layers. Experimental results demonstrated that these modified CLT panels meet and exceed current thermal performance standards, offering a viable solution for energy-efficient, sustainable construction. The discussion highlighted the broader implications of our findings for the construction industry, particularly in terms of meeting stringent energy codes and sustainability goals. Our conclusions underline the potential of insulated CLT panels to revolutionize building practices, emphasizing the need for further research into long-term performance, cost analysis, and adaptability to various climatic conditions. This study contributes to the growing body of knowledge on sustainable building materials and paves the way for future innovations in green construction.

Author Contributions

Conceptualization, M.S. and A.D.; methodology, M.S.; validation, M.S.; formal analysis, M.S.; investigation, M.S. and A.D.; resources, M.S. and A.D.; data curation, M.S.; writing—original draft preparation, M.S.; supervision, A.D. All authors have read and agreed to the published version of the manuscript.

Funding

This manuscript has been authored in part by UT-Battelle, LLC, under contract DE-AC05-00OR22725 with the US Department of Energy (DOE). The publisher acknowledges the US government license to provide public access under the DOE Public Access Plan (http://energy.gov/downloads/doe-public-access-plan, accessed on 12 April 2024).

Data Availability Statement

Data are contained within the article.

Acknowledgments

Jonathan Cole’s efforts to do the testing are greatly appreciated.

Conflicts of Interest

The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

References

  1. U.S. Department of Energy. Decarbonizing the U.S. Economy by 2050. Office of Energy Efficiency & Renewable Energy. Available online: https://www.energy.gov/eere/articles/decarbonizing-us-economy-2050 (accessed on 4 April 2024).
  2. Cabral, M.R.; Blanchet, P. A state of the Art of the Overall Energy Efficiency of Wood Buildings—An Overview and Future Possibilities. Materials 2021, 14, 1848. [Google Scholar] [CrossRef] [PubMed]
  3. Salonvaara, M.; Iffa, E.; Desjarlais, A.O.; Atchley, J. Impact of Mass Wood Walls on Building Energy Use, Peak Demand, and Thermal Comfort; Oak Ridge National Laboratory (ORNL): Oak Ridge, TN, USA, 2022. [Google Scholar]
  4. Setter, L.; Smoorenburg, E.; Wijesuriya, S.; Tabares-Velasco, P.C. Energy and hygrothermal performance of cross laminated timber single-family homes subjected to constant and variable electric rates. J. Build. Eng. 2019, 25, 100784. [Google Scholar] [CrossRef]
  5. Ren, H.; Bahrami, A.; Cehlin, M.; Wallhagen, M. Literature Review on Development and Implementation of Cross-Laminated Timber. In Proceedings of the 5th International Conference on Building Energy and Environment. COBEE 2022. Environmental Science and Engineering, Montreal, QC, Canada, 25–29 July 2022; Wang, L.L., Ge, H., Zhai, Z.J., Qi, D., Ouf, M., Sun, C., Wang, D., Eds.; Springer: Singapore, 2023. [Google Scholar] [CrossRef]
  6. Santos, P.; Correia, J.R.; Godinho, L.; Dias, A.M.P.G.; Dias, A. Life cycle analysis of cross-insulated timber panels. Structures 2021, 31, 1311–1324. [Google Scholar] [CrossRef]
  7. Santos, P.; Sousa, L.; Godinho, L.; João, R.; Correia, A.M.P.G. Dias, Acoustic and thermal behaviour of cross-insulated timber panels. J. Build. Eng. 2021, 44, 103309. [Google Scholar] [CrossRef]
  8. Huang, H.; Lin, X.; Zhang, J.; Wu, Z.; Wang, C.; Wang, B.J. Performance of the hollow-core cross-laminated timber (HC-CLT) floor under human-induced vibration. Structures 2021, 32, 1481–1491. [Google Scholar] [CrossRef]
  9. COMSOL Multiphysics®, version 6.2; COMSOL AB: Stockholm, Sweden, 2023; Available online: www.comsol.com (accessed on 1 December 2023).
  10. International Code Council. 2021 International Residential Code (IRC); International Code Council: Falls Church, VA, USA, 2021. [Google Scholar]
  11. International Code Council. 2021 International Energy Conservation Code (IECC); International Code Council: Falls Church, VA, USA, 2021. [Google Scholar]
  12. National Renewable Energy Laboratory (NREL); Lawrence Berkeley National Laboratory (LBNL); Oak Ridge National Laboratory (ORNL). EnergyPlus, Version 23.1; U.S. Department of Energy: Washington, DC, USA, 2023; Available online: https://energyplus.net/ (accessed on 1 May 2023).
  13. U.S. Department of Energy. Prototype building models. Building Energy Codes Program. Available online: https://www.energycodes.gov/prototype-building-models (accessed on 4 April 2024).
  14. 2018 ANSI/APA PRG 320; Standard for Performance-Rated Cross-Laminated Timber. American National Standard Institute: Washington, DC, USA, 2018. Available online: https://www.apawood.org/ansi-apa-prg-320 (accessed on 15 March 2024).
Figure 1. Staggered insulation layers in two lamellae of CLT.
Figure 1. Staggered insulation layers in two lamellae of CLT.
Buildings 14 01089 g001
Figure 2. Effective R-value of the five-ply CLT with varying degrees of insulation in two layers (layers 2 and 4). Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Figure 2. Effective R-value of the five-ply CLT with varying degrees of insulation in two layers (layers 2 and 4). Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Buildings 14 01089 g002
Figure 3. R-value ratio (%) in the five-ply CLT with varying degrees of insulation in two layers (layers 2 and 4) compared to a solid CLT with a homogeneous insulation layer. Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Figure 3. R-value ratio (%) in the five-ply CLT with varying degrees of insulation in two layers (layers 2 and 4) compared to a solid CLT with a homogeneous insulation layer. Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Buildings 14 01089 g003
Figure 4. Staggered insulation in three lamellae of a five-ply CLT.
Figure 4. Staggered insulation in three lamellae of a five-ply CLT.
Buildings 14 01089 g004
Figure 5. Effective R-value of the five-ply CLT with varying degrees of insulation in three layers (layers 2, 3, and 4). Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Figure 5. Effective R-value of the five-ply CLT with varying degrees of insulation in three layers (layers 2, 3, and 4). Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Buildings 14 01089 g005
Figure 6. R-value ratio (%) in the five-ply CLT with varying degrees of insulation in three layers (layers 2, 3, and 4) compared to a solid CLT with a homogeneous insulation layer. Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Figure 6. R-value ratio (%) in the five-ply CLT with varying degrees of insulation in three layers (layers 2, 3, and 4) compared to a solid CLT with a homogeneous insulation layer. Results for insulation materials with thermal conductivity ranging from 0.0036 to 0.11 W/m·K. The dotted line is for the vacuum-insulated panel (VIP).
Buildings 14 01089 g006
Figure 7. Comparison of the system R-value with k = 0.0036 W/m·K and k = 0.024 W/m·K insulation staggered in CLTs’ two and three insulation lamellae.
Figure 7. Comparison of the system R-value with k = 0.0036 W/m·K and k = 0.024 W/m·K insulation staggered in CLTs’ two and three insulation lamellae.
Buildings 14 01089 g007
Figure 8. The assembly for comparing the effective R-value based on heat flow meter results to simulated performance. The top square area shows where heat flux is measured and outputted in the simulation for comparison.
Figure 8. The assembly for comparing the effective R-value based on heat flow meter results to simulated performance. The top square area shows where heat flux is measured and outputted in the simulation for comparison.
Buildings 14 01089 g008
Figure 9. Heat flux on the interior surface under dynamic conditions for the uninsulated and insulated CLT panels.
Figure 9. Heat flux on the interior surface under dynamic conditions for the uninsulated and insulated CLT panels.
Buildings 14 01089 g009
Figure 10. Multifamily building as modeled in EnergyPlus software.
Figure 10. Multifamily building as modeled in EnergyPlus software.
Buildings 14 01089 g010
Figure 11. Heating demand on average for each hour in January.
Figure 11. Heating demand on average for each hour in January.
Buildings 14 01089 g011
Figure 12. Cooling demand on average for each hour in August.
Figure 12. Cooling demand on average for each hour in August.
Buildings 14 01089 g012
Table 1. The material arrangement in the CLT with two insulated layers.
Table 1. The material arrangement in the CLT with two insulated layers.
LayerMaterials
1Wood only
2Wood (1.0-insulation ratio *), insulation (insulation ratio *)
3Wood only
4Wood (1.0-insulation ratio *), insulation (insulation ratio *)
5Wood only
* Insulation ratio = area of insulation/total area in a layer.
Table 2. Assembly R-values for a staggered two-layer system and a one-dimensional (1D) assembly with average material thicknesses.
Table 2. Assembly R-values for a staggered two-layer system and a one-dimensional (1D) assembly with average material thicknesses.
k, W/m·K0.00360.01800.02400.02880.04000.05000.1100
Insulation ratioR-value (m2, K/W): Staggered two layers
0.32.602.132.021.961.851.781.59
0.43.502.442.252.141.961.861.59
0.55.062.812.512.342.081.941.59
0.66.823.152.742.522.192.011.59
0.78.323.442.942.682.302.081.59
Homogeneous thickness as a single layer
R-value (m2, K/W): 1D-assemblyd-wood, mmd-ins, mm
0.37.222.562.272.121.921.821.59153.721.0
0.49.092.892.502.302.031.891.59146.727.9
0.510.973.212.732.482.141.971.59139.734.9
0.612.853.532.952.662.252.041.59132.741.9
0.714.723.863.182.842.372.121.59125.748.9
R-value ratio (-): Staggered/1D-assembly
0.336%83%89%92%96%98%100%
0.438%84%90%93%97%98%100%
0.546%88%92%94%97%98%100%
0.653%89%93%95%97%98%100%
0.756%89%93%94%97%98%100%
Table 3. Material arrangement in the CLT with staggered insulation in three lamellae.
Table 3. Material arrangement in the CLT with staggered insulation in three lamellae.
LayerMaterials
1Wood only
2Wood (1.0-insulation ratio *), insulation (insulation ratio *)
3Wood (1.0-insulation ratio *), insulation (insulation ratio *)
4Wood (1.0-insulation ratio *), insulation (insulation ratio *)
5Wood only
* Insulation ratio = area of insulation/total area in a layer.
Table 4. Assembly R-values for a staggered three-layer system and 1D assembly with average material thicknesses.
Table 4. Assembly R-values for a staggered three-layer system and 1D assembly with average material thicknesses.
k, W/m K0.00360.01800.02400.02880.04000.05000.1100
Insulation ratioR-value (m2, K/W): Staggered three layers
0.33.262.412.252.151.981.871.59
0.44.842.892.592.412.141.991.59
0.57.633.442.972.712.322.111.59
0.611.013.973.332.992.492.221.59
0.714.314.463.673.252.662.341.59
Homogeneous thickness as a single layer
R-value (m2, K/W): 1D-assemblyd-wood, mmd-ins, mm
0.310.033.052.612.392.091.931.59143.231.4
0.412.853.532.952.662.252.041.59132.741.9
0.515.664.023.292.932.422.161.59122.252.4
0.618.484.513.643.202.592.271.59111.862.9
0.721.295.003.983.472.752.391.59101.373.3
R-value ratio (-): Staggered/1D-assembly
0.332%79%86%90%95%97%100%
0.438%82%88%91%95%97%100%
0.549%86%90%92%96%98%100%
0.660%88%91%93%96%98%100%
0.767%89%92%94%96%98%100%
Table 5. Volume fraction of insulation (%) in the insulated CLTs.
Table 5. Volume fraction of insulation (%) in the insulated CLTs.
Volume Percentage of Insulation, %
Insulation Ratio, -2-Ply3-Ply
0.312%18%
0.416%24%
0.520%30%
0.624%36%
0.728%42%
Table 6. Simulated and tested heat flow meter results for an insulated CLT panel.
Table 6. Simulated and tested heat flow meter results for an insulated CLT panel.
AreaMeasured Heat Flux
W/m2
Simulated Heat Flux
W/m2
Difference between
Simulated and Measured
Top 254 mm × 254 mm14.4214.68+1.8%
Bottom 254 mm × 254 mm15.2715.57+1.9%
Total area 0.61 m × 0.62 m 17.00N/A
Overall R-value for 0.61 m × 0.61 m area 1.31N/A
Table 7. Thermal requirements for mass walls in IRC 2021 [10] (Tables R402.1.3 and R402.1.2) and in IECC 2021 Table C402.1.4 for commercial buildings Group R (residential) [11]. Dual units are given to show original content as written in the building codes. The SI units have been converted from IP.
Table 7. Thermal requirements for mass walls in IRC 2021 [10] (Tables R402.1.3 and R402.1.2) and in IECC 2021 Table C402.1.4 for commercial buildings Group R (residential) [11]. Dual units are given to show original content as written in the building codes. The SI units have been converted from IP.
Climate ZoneMass Wall R-Value *
ft²·°F·h/Btu (m²·K/W)
Mass Wall U-Value
Btu/ft²·°F·h (W/m²·K)
Frame Wall U-Value
Btu/ft²·°F·h (W/m²·K)
Commercial Buildings Mass Wall U-Value, Group R
Btu/ft²·°F·h (W/m²·K)
03/4 (0.53/0.70)0.197 (1.12)0.084 (0.47)0.151 (0.86)
13/4 (0.53/0.70)0.197 (1.12)0.084 (0.47)0.151 (0.86)
24/6 (0.70/1.06)0.165 (0.94)0.084 (0.47)0.123 (0.70)
38/13 (1.41/2.29)0.098 (0.56)0.060 (0.34)0.104 (0.59)
4 except marine8/13 (1.41/2.29)0.098 (0.56)0.045 (0.26)0.104 (0.59)
5 and marine 413/17 (2.29/2.99)0.082 (0.47)0.045 (0.26)0.080 (0.45)
615/20 (2.64/3.52)0.060 (0.34)0.045 (0.26)0.071 (0.04)
719/21 (3.35/3.70)0.057 (0.32)0.045 (0.26)0.071 (0.04)
819/21 (3.35/3.70)0.057 (0.32)0.045 (0.26)0.037 (0.21)
* The second R-value applies when more than 50% of insulation is on the interior of the mass wall.
Table 8. Wall assembly details for the base case (lightweight wall) and the mass wall (insulated CLT) with effective layer properties, including thermal bridges.
Table 8. Wall assembly details for the base case (lightweight wall) and the mass wall (insulated CLT) with effective layer properties, including thermal bridges.
Layer from Outside to InsideLWCLTThickness (mm)Density (kg/m3)Specific Heat Capacity (J/kg·K)Thermal Conductivity (W/m·K)
Synthetic stuccoXX34008790.087
InsulationX 312014650.035
Oriented StrandBoardX 1154512130.116
Half CLT X6750018800.110
Insulation X402012000.018
Half CLT X6750018800.110
Wood Framed CavityX 14012110360.057
Gypsum BoardXX1380110890.16
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Salonvaara, M.; Desjarlais, A. Impact of Insulation Strategies of Cross-Laminated Timber Assemblies on Energy Use, Peak Demand, and Carbon Emissions. Buildings 2024, 14, 1089. https://doi.org/10.3390/buildings14041089

AMA Style

Salonvaara M, Desjarlais A. Impact of Insulation Strategies of Cross-Laminated Timber Assemblies on Energy Use, Peak Demand, and Carbon Emissions. Buildings. 2024; 14(4):1089. https://doi.org/10.3390/buildings14041089

Chicago/Turabian Style

Salonvaara, Mikael, and André Desjarlais. 2024. "Impact of Insulation Strategies of Cross-Laminated Timber Assemblies on Energy Use, Peak Demand, and Carbon Emissions" Buildings 14, no. 4: 1089. https://doi.org/10.3390/buildings14041089

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop