Next Article in Journal
Ethical ChatGPT: Concerns, Challenges, and Commandments
Previous Article in Journal
Multi-Stage Optimal Power Control Method for Distribution Network with Photovoltaic and Energy Storage Considering Grouping Cooperation
Previous Article in Special Issue
Frequency Support Coordinated Control Strategy of Renewable Distributed Energy Resource Based on Digital Twins
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Transient Synchronization Stability Analysis and Enhancement Control for Power Self-Synchronization Control Converters

1
State Grid Sichuan Electric Power Company Electric Power Research Institute, Chengdu 610000, China
2
College of Electrical Engineering, Sichuan University, Chengdu 610000, China
*
Author to whom correspondence should be addressed.
Electronics 2024, 13(17), 3416; https://doi.org/10.3390/electronics13173416 (registering DOI)
Submission received: 19 June 2024 / Revised: 15 August 2024 / Accepted: 20 August 2024 / Published: 28 August 2024
(This article belongs to the Special Issue Power-Electronic-Based Smart Grid and Its Control Technology)

Abstract

:
Conventional grid-forming control often destabilizes voltage source converters (VSCs) in stiff grids, and transient synchronization instability will occur in the grid fault condition. Therefore, power self-synchronization control (PSSC) is first introduced for enhancing the small-signal stability of grid-forming control in the case of a short circuit ratio ranging from 1 to infinity. Meanwhile, the transient synchronization instability for the grid-forming converter with PSSC in the grid fault condition is analyzed by the phase portrait, and a transient stability enhancement control (TSEC) scheme is combined with a PSSC-based VSC, which can efficiently eliminate the risk of losing synchronization in the arbitrary SCR. Finally, experimental results are provided to confirm the theoretical analysis.

1. Introduction

The voltage source converter (VSC) has been wildly used as an interface between renewable energy generation and the grid. The control techniques for VSCs can be categorized as grid-following control and grid-forming control [1,2].
The VSC usually applies grid-following control to synchronize with the grid via a phase-locked loop (PLL), and the VSC is controlled as a current source whose stable operation relies on a stiff grid condition [3]. However, with the large-scale integration of new energy into the grid by VSCs, the proportion of synchronous generators (SGs) in the system gradually decreases, which leads to a decline in grid strength and poses a great challenge to the stability of grid-following converters [4,5,6].
In order to ensure the stable operation of power systems with a high penetration of power electronics, VSCs are requested to participate in the formation of system voltage and frequency, which is achieved by grid-forming control [7,8]. By imitating the physical mechanism of synchronous generators, different grid-forming control schemes follow the same principle, i.e., (1) the inverter is regulated as a voltage source, and (2) the inverter achieves synchronization through the output power (or DC voltage) rather than by sampling the external AC grid voltage [2,9,10].
Grid-forming VSCs behave as voltage sources which can enhance the synchronization performance in weak grids. Refs. [11,12] indicate that a VSC with PSC is more robust in weak grids in accordance with the Nyquist criterion. Nevertheless, the grid-forming VSC is prone to small-signal instability in stiff grids. [13,14] discovered that the stability margin of a grid-forming VSC decreases with an increasing short circuit ratio (SCR), and the VSC has a higher risk of sub-synchronous oscillation. Ref. [15] has derived the impedance model of a droop-controlled VSC in the stationary frame, and according to the impedance-based stability analysis, it can be concluded that the stability problem of the droop-control VSC is more prominent in stiff grids. The small-signal model of the virtual synchronous generator (VSG)-based VSC is derived in reference [16]; it was revealed that a pair of complex conjugate poles, which are close to the imaginary axis in rigid grids, will result in instability. As indicated in [17], the interactive instability problem between the grid-forming converter and the AC grid is notably characterized by sub-synchronous oscillations.
Ref. [18] introduced a dual-mode control strategy incorporating grid impedance adaptation for droop-control VSCs. The inverter functions in current source mode under conditions of low grid impedance, transitioning to voltage source mode when the grid impedance increases. However, this scheme is complicated in application and it changes the major software structure on the grid-forming control. Ref. [19] proposed a universal controller that combines grid-following and grid-forming control strategies. This approach aims to enhance stability against different system conditions by using PSC as a guide to design a robust grid-following controller. When the SCR approaches 1, a low-frequency power resonance may be induced via an improperated coefficient in alternating voltage control [20]. Ref. [21] added an active susceptance loop, which enhances system damping without varying software structure and enables us to use a standard voltage-oriented vector current control. But the proposed control is more complicated and the condition in an extremely large SCR, which is not discussed.
In order to tackle the oscillation challenge faced by grid-forming converters in stiff grids, ref. [22] presents a new and practical control strategy known as power self-synchronization control (PSSC), where the modulating voltage is estimated as the output voltage of the VSC, rather than the Point of Common Coupling (PCC) voltage. Ref. [22] has built an impedance model and small-signal state space model. PSSC can effectively suppress oscillation with an arbitrary SCR and provide positive damping within a broad frequency band. However, there still is the large-signal stability of the PSSC-VSC.
Numerous studies have concentrated on the transient synchronization stability problem of grid-forming VSCs. The phase portrait, the Lyapunov direct method, and the equal area criterion (EAC) are commonly applied for analyzing nonlinear dynamic systems [23,24,25]. Ref. [26] compared the transient synchronization stability of four grid-forming control strategies during symmetrical grid voltage sags using phase portraits. Additionally, [27] analyzed mathematical formulations for the maximum fault clearance duration and angle in PSC-based VSCs under voltage sag conditions.
This article fills the gap in the transient stability synchronization analysis of PSSC-VSCs by using the phase portrait. A transient stability enhancement control (TSEC) strategy is applied in PSSC, which further avoids the inverter losing synchronization with the grid with an arbitrary SCR during the fault. The comparison between different controllers is listed in Table 1, in which the benefits of the proposed method are highlighted.
The PSSC scheme is systematically introduced to enhance the stability of a grid-forming converter in a stiff grid in Section 2. In Section 3, the nonlinear dynamic equation of the power angle for the PSSC-VSC is established, and the mechanism of transient synchronous instability is analyzed by the phase portrait. In Section 4, to solve the issue of transient synchronization instability, mode-adaptive transient stability control is developed for the PSSC-VSC, and the power angle dynamic behaviors with transient stability control are illustrated through the phase portrait. The experimental results in Section 5 validate the theoretical analysis presented. A summary is provided in Section 6.

2. System Description and Dynamic Modeling

2.1. System Description

Figure 1 shows the single-line diagram of a three-phase grid-connected PSSC-VSC. Lf is the filter inductor. The grid impedance of the VSC connected to the PCC is considered a pure inductance Lg. vi, vPCC, and vg are the VSC output voltage, PCC voltage, and grid voltage in the stationary frame, respectively. vdc is the dc voltage. iLabc is the VSC output current after the filter inductor in the stationary frame. The subscript dq denotes the variables in the dq-frame. vdqref, vodqref, and voref represent the input voltage reference of the inner control loop and the modulated voltage in the dq-frame and in the stationary frame, respectively. edq is the output of the integrator in the current control loop, and the high-frequency components of the input thereby can be filtered.
As illustrated in Figure 1, the controller operates within the dq-frame and is divided into two main components. PSSC manages power synchronization in the outer control loop, while the inner control loop employs a dual-loop control scheme, which includes a voltage control loop and a current control loop.

2.2. Control Loop

The external power loop adopts power self-synchronization control. As shown in Figure 2, the voltage, which is regulated in the voltage control loop and used for the power calculation, is the significant difference between PSSC and PSC.
In PSSC, the instantaneous power is calculated by the sampled grid current and the state variable edq rather than the grid voltage. The integrator output of the current control loop is equivalent to vodqref as the system reaches a steady state. Thereby, edq is equal to vodqref in the steady state, and the active power can be transmitted based on the phase difference between vi and vg.
The active power control law of the VSC can be written as
ω = ω 0 + K p ( P ref P e )
where ω0 is the reference frequency, ω is the desired frequency of the reference voltage, Kp is the P-f controller coefficient, and Pe and Pref are the instantaneous active power and the reference value, respectively.
Due to the dynamic difference between the outer loop and inner loop, which is more than ten times slower than the internal voltage and current loop [28], the internal loop of vector voltage and current control can be considered a unity gain with ideal reference tracking as the transient synchronization stability problem caused by the power loop.
In the conventional PSC-VSC, the voltage and current at the PCC should be sampled for voltage control and power calculation, and the capacitor filter in the AC side is necessary for voltage detection. Conversely, the proposed PSSC-VSC can calculate the active power by using edq and the current, while the cost for the filter capacitor and voltage sensor can ignored.

2.3. Stability Analysis of PSSC-VSC in Stiff Grids

It is worth nothing that the grid-forming VSC is prone to instability in the strong grid. When the grid-forming VSC is connected to an ultra-strong grid (SCR = ∞), the steady-state gains of the transfer functions in the active power control loop are close to infinity, and small disturbances in the control loop are amplified, which leads to system instability.
It is evident from [29] that when the PSC-VSC is connected to a stiff grid, the steady-state gains in the power loop approach infinity, which can easily lead to system instability under small disturbances. Ref. [29] has constructed a linearized small-signal model of the PSC-VSC in an active power loop. For PSSC, which does not sample the voltage of the PCC, the line inductance Lg in the original linearized small-signal model is replaced by the equivalent inductance, which is the sum of the filtering inductance Lf and the line inductance Lg. The linearized small-signal model of the PSSC-VSC in an active power loop can be written as
Δ P e s = V g V i cos θ 0 Δ θ ( s ) / ω 0 ( L f + L g ) .
Due to the existence of Lf, the steady-state gains of the transfer functions can be constrained. The frequency response of the power control loop is improved by designing the control parameters, so that the PSSC-VSC is stabilized under stiff grid conditions.
From the analysis above, it can be seen that the PSSC-VSC utilizes filtering inductance and line impedance for power interaction, which shows excellent stability performance even under strong grid conditions. Furthermore, as shown in Figure 2, edq represents the output of the integrator in the current control loop. Therefore, high-frequency components at the input can be filtered out automatically.

3. Transient Synchronization Stability Analysis of PSSC-VSC

3.1. Dynamic Model of PSSC-VSC

It is assumed that the transmission line impedance is purely inductive and the resistive component is ignored, the voltage on the DC side of each VSC is assumed to be constant, and the frequency of the infinite grid is set as ω0.
Figure 3 shows a simplified circuit of the PSSC-VSC connected to the grid, where Xf = ω0Lf and Xg = ω0Lg are the filter reactance and the line reactance, respectively. The phase difference between the PSSC-VSC output voltage vi and the grid voltage vg is defined as the power angle, and the grid voltage and VSC output are expressed as Vgθg and Viθi, as shown in Figure 4. The active power output from the VSC to the infinite grid can be derived as
P e = 3 V i V g 2 ( X g + X f ) sin δ
Considering θ = ωt, the power angle and the frequencies of VSC and the grid satisfy
δ = θ g θ i = ω ω 0 .
For Equation (4), the derivative of δ, i.e., ∆ω, is obtained as
δ ˙ = ω ω 0 .
ω0 is subtracted from both sides of Equation (1), and substituting Equation (3) into Equation (1), it can be derived as
ω ω 0 = K p P ref 3 V i V g 2 ( X g + X f ) sin δ .
Then, substituting Equation (5) into Equation (6), the dynamic behavior of the power angle for the PSSC-VSC can be obtained as
δ ˙ = K p P ref 3 V i V g 2 ( X g + X f ) sin δ .
From Equation (7), if the reference active power exceeds the maximum transmissible active power, i.e., Pref > 3 V i V g / 2 ( X g + X f ) , according to the trigonometry theorem, δ will have no feasible solution and δ ˙ will never equal zero. Similar to the PSC-VSC, the PSSC-VSC still suffers from the transient synchronization instability issue.
In order to maintain PSSC-VSC transient synchronization stability during the fault, the reference active power is not allowed to exceed the maximum transmissible active power. The transient synchronization stable boundary of PSSC-VSC can be derived as
P ref 3 V i V g 2 ( X g + X f ) = P ref P MAX   <   1 .

3.2. Dynamic Response of Power Angle for PSSC-VSC

The mathematical relationship between δ ˙ and δ is explicitly derived by Equation (7), which is critical to the transient stability analysis. However, due to the high nonlinearity, it is difficult to acquire an analytical solution of Equation (7). In contrast, a graphical evaluation can be easily carried out by the δ ˙ δ curve, which is the so-called phase portrait. Based on the phase portrait, the change in δ can be readily predicted, i.e., δ will increase if δ ˙ > 0 and decrease if δ ˙ < 0, and δ ˙ = 0 corresponds to the equilibrium points.
According to the parameters listed in Table 2, the phase portrait under a normal condition (Vg = 1 p.u.) is plotted with the solid line in Figure 4. There are two equilibrium points, where point a (the solid dot) is the stable equilibrium point (SEP), since δ can return to SEP. However, point b (the open circle) is the unstable one, since a small disturbance will force δ to depart from this point. It is known from Equation (3) that a voltage sag of the grid can cause a decrease in the maximum transmissible active power, which may be smaller than Pref, and will lead to the loss of synchronization. Depending on the depth of the voltage sag, there will be two scenarios.
In the first scenario, the equilibrium points still exist after the fault. Vg dropping to 0.7 p.u. leads to a higher phase portrait; it still crosses zero at points d and e which are the two equilibrium points. At the moment of the fault occurring, the operating point jumps from a to c. Then, δ starts to increase due to δ ˙ > 0, which forces the operating point to move from c to d, shown as the red line with arrows. Once the operating point reaches point d, a new steady state is achieved due to δ ˙ = 0, and δ will stop at δ2 and never exceed δ2, as shown in Figure 5 by the green line with arrows. In the second scenario, Vg dropping to 0.2 p.u. causes the loss of equilibrium points and δ will diverge to infinity as δ ˙ > 0 always remains, shown as the blue line with arrows.

4. Transient Stability Enhancement for PSSC-VSC

4.1. Transient Stability Enhancement Control Scheme

To address the transient stability problem of the PSSC-VSC, a mode adaptive scheme for transient stability enhancement control (TSEC) [30] is developed for PSSC. Additionally, the concept of virtual orthogonal power (VOP) is proposed to enhance the transient stability. By utilizing mathematical relations involving trigonometric functions, the VOP Pν of the PSSC-VSC can be precisely defined and calculated by
P ν = 3 V i V g 2 ( X g + X f ) cos δ .
During grid voltage sags, Pref is always larger than the output active power Pe, and the integral link for the active power error in the PSC loop leads to the power angle continuing to increase. Consequently, it is necessary to dynamically adjust Pref when the power angle surpasses the critical threshold of π/2 rads.
From Figure 6, Pe/Pν changes cyclically with δ. According to the tangent property, δ is related to Pe/Pν by Equation (10) in the range from 0 to π.
δ = a r c t a n ( P e / P ν )                         P e / P ν > 0 a r c t a n ( P e / P ν ) + π           P e / P ν < 0
where δ serves as a direct indicator of the power angle of the VSC. As illustrated in Figure 6, the PSSC-VSC operates in mode 1 when 0 < δ < π/2 and mode 2 when π/2 < δ < π. Furthermore, the ratio Pe/Pν undergoes sharp variation when δ approaches π/2.
Based on the correlation between Pe/Pν and the power angle δ, a novel TSEC method is proposed, as shown in Figure 7. In this proposed approach, the transient stability enhancement control scheme is activated when δ approximates π/2 and deactivated when δ significantly deviates from π/2. In this paper, the critical conditions for disabling and enabling the transient synchronization stability control method occur when δ is less than 1.5 rad and greater than 1.6 rad, respectively. Pe/Pν is restricted to the upper or lower limit by the limitation block, as shown in Figure 7.
Pref is continually amended to an appropriate value via adding the limited Pe/Pν to it, which causes δ to slightly change around π/2 rad and avoids δ increasing to infinity, as shown in the dashed-line area of Figure 7. When adopting TSEC, the reference power Pref is adjusted to (1 + Pe/Pν)Pref, which is called the equivalent reference power P ref eq . The original power control loop of PSSC, i.e., Equation (1), is also corrected to Equation (11), corresponding to Figure 7.
ω = ω 0 + K p ( 1 + P e P ν ) P ref P ref eq P e
Figure 8 shows the flowchart of TSEC. Firstly, the power angle, the output active power, and the virtual orthogonal power are obtained in real time. Then, determining whether the startup condition is met, if the faults cause δ > 1.6 rad, the proposed control scheme is activated to maintain VSC synchronizing with the grid. After the faults have been cleared, δ will decrease until it is smaller than 1.5 rad, and the proposed control scheme is switched to regular PSSC.

4.2. Dynamic Response of Power Angle for PSSC-VSC Adopting TSEC

When TSEC is activated, combining Equations (7) and (10) can yield the nonlinear dynamic equation of the power angle:
δ ˙ = K p 1 + P e P ν P ref 3 V i V g 2 ( X g + X f ) sin δ .
The power angle is δ0 (point a) in a normal state, as shown in Figure 9. During the fault, point a will instantly change to a*. Due to the lack of SEP, the power angle will increase as a result of δ ˙ > 0 and move from a* to b due to the phase portrait. While δ exceeds the trigger value (point b), which is smaller than π/2 rad, transient synchronization stability control will be activated and will operate in mode 1, which causes the operating point to move from b to b*. Since Pe/Pν is larger than zero, Pref in mode 1 will rise, which further increases δ from b* to c, shown by the green line in Figure 9. It is noted that Pe/Pν will be restricted to the upper limit KUL.
When the power angle slightly crosses π/2 rad, Pe/Pν immediately jumps from the upper limit KUL to the lower limit KLL, and the PSSC-VSC operates in mode 2, as depicted by the solid blue line in Figure 9. The operating point shifts from c to c*. By appropriately selecting the KLL, δ ˙ can be smaller than zero in c*, and the power angle will reduce to π/2 rad, as shown by the blue line with arrows. Upon the power angle dropping below π/2 radians once more, the PSSC-VSC reverts to mode 1, leading to an instantaneous change in the operating point from d to d*.
It is easy to find that the slope of δ is smaller than zero in dot c*. Thus, the lower limit KLL is crucial and should be set appropriately. In mode 2, the KLL must satisfy
δ ˙ = K p ( 1 + K LL ) P ref 3 V i V g 2 ( X g + X f ) sin δ   <   0 .
δ is regarded as π/2 rad, and the KLL can be derived according to (13) as
K LL < 3 V i V g 2 ( X f + X g ) P ref   1 .

5. Experimental Verification

In this section, the experimental tests are used to verify the correctness of the theoretical analysis. The following cases are verified in the experimental tests: (1) the transient behaviors of the power angle for the PSSC-VSC; (2) the effectiveness of the PSSC with TSEC. The experimental tests are implemented on the real-time digital simulator based on the NovaCor 2.0 hardware simulation platform, as shown in Figure 10.

5.1. Dynamic Response of Power Angle for PSSC-VSC during Fault

First, the transient responses of the PSSC-VSC under different grid voltage sag conditions are tested. The waveforms of the active power Pe, the output voltage Vi, the output current I, and the power angle δ are displayed. Figure 11a shows the experimental results with PSSC, where the controller parameters in Table 2 are adopted. When Vg drops to 0.7 p.u., there still exists an equilibrium point after the fault. In Figure 11a, δ exhibits a gradual increase and attains a new steady state without any overshoot, which confirms the first-order dynamic behavior of the PSSC-VSC. The experimental dynamic behavior of δ corresponds to the theoretical analysis in Figure 4. The active power delivered to the grid immediately decreases due to the grid voltage sag, as shown in Figure 11a. However, when Vg drops to 0.4 p.u., the equilibrium points no longer exist, and the output active power of the PSSC-VSC is smaller than Pref, which leads to constant increases in δ. Figure 11b illustrates the emergence of low-frequency oscillations in the waveforms of P, δ, V, and I, and the results are consistent with the analysis.

5.2. Verification of PSSC-TSEC Inverter during Symmetrical Fault

The experimental results of the PSSC-VSC with TSEC during a symmetrical fault are elaborated in Figure 12.
Figure 12 shows the waveforms of the PSSC-VSC with TSEC when Vg drops to 0.4 p.u. It can be observed in Figure 12 that when δ crosses 1.6 rad, transient stability enhancement control is enabled to adaptively change the equivalent Pref. Pe/Pν jumps continuously between positive and negative values, which also triggers the rapid change in P ref eq , and transient synchronization stability control is switched between mode 1 and mode 2. Since the power angle is fixed at π/2 rad, even if there is no SEP after the voltage droop, the output active power of the PSSC-VSC can be kept constant. After the grid voltage recovers to the normal value, the power angle gradually decreases until it is below 1.50 rad; then, the PSSC-VSC will return from TSEC to conventional PSSC.
In order to demonstrate the benefits and broad application of the proposed controller in arbitrary SCR, the experimental results with an SCR = ∞ and an SCR = 1.2 are elaborated in Figure 13. The power synchronization coefficient Kp = 0.0006 and Pref = 3 kW in both scenarios. And Lg = 0 and Lf = 7 mH when the SCR = ∞.
Figure 13 shows the waveforms of the PSSC-VSC with TSEC when Vg drops to 0.3 p.u. It can be observed in Figure 13 that when δ crosses 1.6 rad, transient stability enhancement control is enabled. The combination of PSSC and TSEC guarantees the synchronization of the inverter with the grid under ultra-strong or ultra-weak grid conditions, which also indicates the widespread application of the proposed controller in engineering.
The scenario of a big load change is also considered in this article. The load is set to a pure resistance and the value is 6 Ω. Figure 14 shows the waveforms as the load switches off and switch on. When the load is connected to the system, the active power and current between the inverter and the grid will both decrease, which corresponds to the reduction in δ. It is obvious from Figure 14 that the load change will not affect the stability of the PSSC-based inverter.

5.3. Verification of PSSC-TSEC Inverter during Asymmetrical Fault

It is confirmed that PSSC-TSEC is still useful in the conditions of an asymmetrical fault, and the waveforms are demonstrated in Figure 15.
Figure 15a,b correspond to the scenario of a single-phase short-circuit fault and a two-phase short-circuit fault which occurred in the transmission line, respectively. When the asymmetric fault occurs, TSEC is activated and the inverter power angle is regulated to stay at 1.6 rad. After the fault disappears, TSEC is cut off and the inverter returns to normal PSSC operation, which illustrates that TSEC has no influence on the system during regular operation. The effectiveness of PSSC-TSEC during an asymmetrical fault can further reflect the value in engineering applications.

6. Conclusions

This article investigates the transient synchronization stability of PSSC-based VSCs. A comprehensive large-signal model is developed to characterize its dynamics; the power angle transient response is evaluated by phase portraits. The main contributions are outlined below:
(1)
Although the PSSC-based VSC can keep the small signal stable in SCR ranges from 1 to ∞, it still faces the problem of the loss of synchronization with the grid during faults.
(2)
A large-signal model is established and it is found that the imbalance between the output active power and the reference active power causes the transient instability of the PSSC-based VSC.
(3)
The dynamic behavior of the power angle is elucidated. Since the large-signal model of the PSSC-based VSC is equipped with a first-order nature, there is no overshot in the power angle response.
(4)
To keep the PSSC-based VSC synchronized with the grid during faults, transient stability enhancement control is adopted which obviously keeps the PSSC-VSC synchronizing with the grid with an arbitrary SCR during the fault.
(5)
The PSSC-based VSC integrating TSEC scheme has a broad application perspective. It is simple to set the software and the structure of essential controller does not need to vary during the fault. Most importantly, the proposed controller is still effective in both ultra-strong and ultra-weak grids.
(6)
The inverter controlled by PSSC-TSEC can maintain synchronization with the grid in both symmetrical and asymmetrical faults.

Author Contributions

Conceptualization, H.S. and J.M.; methodology, P.S.; validation, B.Z.; data curation, X.W.; writing—original draft preparation, H.S.; writing—review and editing, X.W. and X.Z.; project administration, H.S. All authors have read and agreed to the published version of the manuscript.

Funding

This study was funded by the STATE GRID SICHUAN ELECTRIC POWER COMPANY Science and Technology Project: Analysis and improvement methods for the grid-forming capability of high proportion new energy system, grant number 52199723000A.

Data Availability Statement

All of the images are available on request from the corresponding author.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

Lffilter inductor
Lggrid inductor
viVSC output voltage
vPCCPCC voltage
vggrid voltage
vdcdc voltage
iLabcVSC output current
vdqrefvoltage reference of inner control loop
vodqref, vorefmodulated voltage in dq-frame and in stationary frame
edqoutput of integrator in current control loop
ω0grid frequency
KpP-f controller coefficient
Peinstantaneous active power
Prefreference active power
δpower angle
PMAXmaximum transmissible active power
Pνvirtual orthogonal active power
P ref eq equivalent reference power
KULupper limit of Pe/Pv
KLLlower limit of Pe/Pv
VSCvoltage source converter
SGsynchronous generator
PLLphase-locked loop
SCRshort circuit ratio
PSCpower synchronization control
VSGvirtual synchronous generator
PSSCpower self-synchronization control
PCCPoint of Common Coupling
EACequal area criterion
SEPstable equilibrium point
VOPvirtual orthogonal power
TSECtransient stability enhancement control

References

  1. Wang, X.; Taul, M.G.; Wu, H.; Liao, Y.; Blaabjerg, F.; Harnefors, L. Grid-synchronization stability of converter-based resources—An overview. IEEE Open. J. Ind. Appl. 2020, 1, 115–134. [Google Scholar] [CrossRef]
  2. Zhang, H.; Xiang, W.; Lin, W.; Wen, J. Grid Forming Converters in Renewable Energy Sources Dominated Power Grid: Control Strategy, Stability, Application, and Challenges. J. Mod. Power Syst. Clean Energy 2021, 9, 1239–1256. [Google Scholar] [CrossRef]
  3. Zhou, J.Z.; Ding, H.; Fan, S.; Zhang, Y.; Gole, A.M. Impact of short-circuit ratio and phase-locked-loop parameters on the small-signal behavior of a VSC-HVDC converter. IEEE Trans. Power Deliv. 2014, 29, 2287–2296. [Google Scholar] [CrossRef]
  4. Wang, X.; Blaabjerg, F. Harmonic stability in power electronic based power systems: Concept, modeling, and analysis. IEEE Trans. Smart Grid. 2019, 10, 2858–2870. [Google Scholar] [CrossRef]
  5. Wang, X.; Harnefors, L.; Blaabjerg, F. A unified impedance model of grid-connected voltage-source converters. IEEE Trans. Power Electron. 2018, 33, 1775–1787. [Google Scholar] [CrossRef]
  6. Elkhatib, M.E.; Du, W.; Lasseter, R.H. Evaluation of inverter-based grid frequency support using frequency-watt and grid-forming PV inverters. In Proceedings of the 2018 IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, USA, 5–9 August 2018; pp. 1–5. [Google Scholar]
  7. Rodriguez, P.; Citro, C.; Candela, I.; Rocabert, J.; Rodriguez, P. Flexible grid connection and islanding of SPC-based PV power converters. IEEE Trans. Ind. Appl. 2018, 54, 2690–2702. [Google Scholar] [CrossRef]
  8. Zhang, L.; Harnefors, L.; Nee, H.-P. Power-synchronization control of grid-connected voltage-source converters. IEEE Trans. Power Syst. 2010, 25, 809–820. [Google Scholar] [CrossRef]
  9. Rosso, R.; Wang, X.; Liserre, M.; Lu, X.; Engelken, S. Grid-forming converters: Control approaches, grid-synchronization, and future trends—A review. IEEE Open J. Ind. Appl. 2021, 2, 93–109. [Google Scholar] [CrossRef]
  10. Johnson, B.B.; Sinha, M.; Ainsworth, N.G.; Dörfler, F.; Dhople, S.V. Synthesizing virtual oscillators to control islanded inverters. IEEE Trans. Power Electron. 2016, 31, 6002–6015. [Google Scholar] [CrossRef]
  11. Rocabert, J.; Luna, A.; Blaabjerg, F.; Rodriguez, P. Control of power converters in AC microgrids. IEEE Trans. Power Electron. 2012, 27, 4734–4749. [Google Scholar] [CrossRef]
  12. Milano, F.; Dörfler, F.; Hug, G.; Hill, D.J.; Verbić, G. Foundations and challenges of low-inertia systems. In Proceedings of the 2018 Power Systems Computation Conference (PSCC), Dublin, Ireland, 11–15 June 2018; pp. 1–25. [Google Scholar]
  13. De Brabandere, K.; Bolsens, B.; Van Den Keybus, J.; Woyte, A.; Driesen, J.; Belmans, R. A voltage and frequency droop control method for parallel inverters. IEEE Trans. Power Electron. 2007, 22, 1107–1115. [Google Scholar] [CrossRef]
  14. Huang, L.; Xin, H.; Wang, Z. Damping low-frequency oscillations through VSC-HVDC stations operated as virtual synchronous machines. IEEE Trans. Power Electron. 2018, 34, 5803–5818. [Google Scholar] [CrossRef]
  15. Liao, Y.; Wang, X.; Liu, F.; Xin, K.; Liu, Y. Sub-synchronous control interaction in grid-forming VSCs with droop control. In Proceedings of the 2019 4th IEEE Workshop on the Electronic Grid (eGRID), Xiamen, China, 11–14 November 2019; pp. 1–6. [Google Scholar]
  16. Li, X.; Hu, Y.; Shao, Y.; Chen, G. Mechanism analysis and suppression strategies of power oscillation for virtual synchronous generator. In Proceedings of the IECON 2017-43rd Annual Conference of the IEEE Industrial Electronics Society, Beijing, China, 29 October–1 November 2017; pp. 4955–4960. [Google Scholar]
  17. Denis, G.; Prevost, T.; Panciatici, P.; Kestelyn, X.; Colas, F.; Guillaud, X. Improving robustness against grid stiffness, with internal control of an AC voltage controlled VSC. In Proceedings of the 2016 IEEE Power and Energy Society General Meeting (PESGM), Boston, MA, USA, 17–21 July 2016; pp. 1–5. [Google Scholar]
  18. Li, M.; Zhang, X.; Yang, Y.; Cao, P. The grid impedance adaptation dual mode control strategy in weak grid. In Proceedings of the 2018 International Power Electronics Conference (IPEC-Niigata 2018-ECCE Asia), Niigata, Japan, 20–24 May 2018. [Google Scholar]
  19. Harnefors, L.; Kukkola, J.; Routimo, M.; Hinkkanen, M.; Wang, X. A universal controller for grid-connected voltage-source converters. IEEE J. Emerg. Sel. Topics Power Electron. 2021, 9, 5661–5670. [Google Scholar] [CrossRef]
  20. Harnefors, L.; Schweizer, M.; Kukkola, J.; Routimo, M.; Hinkkanen, M.; Wang, X. Generic PLL-based grid-forming control. IEEE Trans. Power Electron. 2022, 37, 1201–1204. [Google Scholar] [CrossRef]
  21. Zhao, F.; Wang, X.; Zhou, Z.; Sun, Y.; Harnefors, L.; Zhu, T. Robust grid-forming control with active susceptance. IEEE Trans. Power Electron. 2022, 38, 2872–2877. [Google Scholar] [CrossRef]
  22. Wang, P.; Ma, J.; Zhang, R.; Wang, S.; Liu, T.; Wu, Z.; Wang, R. Power Self-Synchronization Control of Grid-Forming Voltage-Source Converters Against a Wide Range of Short-Circuit Ratio. IEEE Trans. Power Electron. 2023, 38, 15419–15432. [Google Scholar] [CrossRef]
  23. Strogatz, S.H. Nonlinear Dynamics and Chaos with Student Solutions Manual: With Applications to Physics, Biology, Chemistry, and Engineering; CRC Press: Boca Raton, FL, USA, 2018. [Google Scholar]
  24. Shuai, Z.; Shen, C.; Liu, X.; Li, Z.; Shen, Z.J. Transient Angle Stability of Virtual Synchronous Generators Using Lyapunov’s Direct Method. IEEE Trans. Smart Grid 2018, 10, 4648–4661. [Google Scholar] [CrossRef]
  25. Li, X.; Tian, Z.; Zha, X.; Sun, P.; Hu, Y.; Huang, M.; Sun, J. Nonlinear Modeling and Stability Analysis of Grid-Tied Paralleled-Converters Systems Based on the Proposed Dual-Iterative Equal Area Criterion. IEEE Trans. Power Electron. 2023, 38, 7746–7759. [Google Scholar] [CrossRef]
  26. Pan, D.; Wang, X.; Liu, F.; Shi, R. Transient stability of voltage-source converters with grid-forming control: A design-oriented study. IEEE J. Emerg. Sel. Topics Power Electron. 2020, 8, 1019–1033. [Google Scholar] [CrossRef]
  27. Wu, H.; Wang, X. Design-Oriented Transient Stability Analysis of Grid-Connected Converters With Power Synchronization Control. IEEE Trans. Ind. Electron. 2019, 66, 6473–6482. [Google Scholar] [CrossRef]
  28. Yuan, H.; Yuan, X.; Hu, J. Modeling of grid-connected VSCs for power system small-signal stability analysis in DC-link voltage control timescale. IEEE Trans. Power Syst. 2017, 32, 3981–3991. [Google Scholar] [CrossRef]
  29. Yang, D.; Wang, X.; Blaabjerg, F. Fast power control for VSCs to enhance the synchronization stability in ultra-weak grid. In Proceedings of the 2018 IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, USA, 5–9 August 2018; pp. 1–6. [Google Scholar]
  30. Sun, R.; Ma, J.; Yang, W.; Wang, S.; Liu, T. Transient synchronization stability control for LVRT with power angle estimation. IEEE Trans. Power Electron. 2021, 36, 10981–10985. [Google Scholar] [CrossRef]
Figure 1. Topology and control diagram of grid-connected PSSC-VSC.
Figure 1. Topology and control diagram of grid-connected PSSC-VSC.
Electronics 13 03416 g001
Figure 2. The controller structure of the PSSC-VSC.
Figure 2. The controller structure of the PSSC-VSC.
Electronics 13 03416 g002
Figure 3. Simplified circuit of PSSC-VSC connected to grid.
Figure 3. Simplified circuit of PSSC-VSC connected to grid.
Electronics 13 03416 g003
Figure 4. Equivalent vector diagram of PSSC-VSC.
Figure 4. Equivalent vector diagram of PSSC-VSC.
Electronics 13 03416 g004
Figure 5. Phase portrait of PSSC−VSC before and after grid voltage sag.
Figure 5. Phase portrait of PSSC−VSC before and after grid voltage sag.
Electronics 13 03416 g005
Figure 6. Relation between Pe/Pν and power angle δ.
Figure 6. Relation between Pe/Pν and power angle δ.
Electronics 13 03416 g006
Figure 7. Control diagram of PSSC with transient synchronization stability control.
Figure 7. Control diagram of PSSC with transient synchronization stability control.
Electronics 13 03416 g007
Figure 8. The flowchart of TSEC.
Figure 8. The flowchart of TSEC.
Electronics 13 03416 g008
Figure 9. Phase portraits of PSSC−VSC adopting transient synchronization stability control.
Figure 9. Phase portraits of PSSC−VSC adopting transient synchronization stability control.
Electronics 13 03416 g009
Figure 10. The NovaCor 2.0 hardware simulation platform.
Figure 10. The NovaCor 2.0 hardware simulation platform.
Electronics 13 03416 g010
Figure 11. Measured current, voltage, active power, and power angle of PSSC-VSC: (a) Vg = 0.7 p.u.; (b) Vg = 0.4 p.u.
Figure 11. Measured current, voltage, active power, and power angle of PSSC-VSC: (a) Vg = 0.7 p.u.; (b) Vg = 0.4 p.u.
Electronics 13 03416 g011
Figure 12. Measured current, voltage, active power, and power angle of PSSC-VSC adopting transient synchronization stability control: (a) Vg = 0.4 p.u.; (b) partial amplification waveform.
Figure 12. Measured current, voltage, active power, and power angle of PSSC-VSC adopting transient synchronization stability control: (a) Vg = 0.4 p.u.; (b) partial amplification waveform.
Electronics 13 03416 g012
Figure 13. Measured current, voltage, active power, and power angle of PSSC-VSC adopting transient synchronization stability control: (a) SCR = ∞; (b) SCR = 1.2.
Figure 13. Measured current, voltage, active power, and power angle of PSSC-VSC adopting transient synchronization stability control: (a) SCR = ∞; (b) SCR = 1.2.
Electronics 13 03416 g013
Figure 14. Measured current, voltage, active power, and power angle of PSSC-VSC during load change.
Figure 14. Measured current, voltage, active power, and power angle of PSSC-VSC during load change.
Electronics 13 03416 g014
Figure 15. Measured current, voltage, active power, and power angle of PSSC-VSC adopting TSEC: (a) single-phase short-circuit fault; (b) two-phase short-circuit fault.
Figure 15. Measured current, voltage, active power, and power angle of PSSC-VSC adopting TSEC: (a) single-phase short-circuit fault; (b) two-phase short-circuit fault.
Electronics 13 03416 g015
Table 1. Controller comparison.
Table 1. Controller comparison.
ControllerStrategyFeatures
The dual-mode controllerCurrent source mode in the stiff grid; voltage source mode in the weak grid
(1)
Complicated to realize
(2)
Change in software structure
The universal controllerUsing PSC as a guide to design a grid-following controller
(1)
Small-signal instability may happen with an SCR ≈ 1
The robust grid-forming controllerAn active susceptance loop is added
(1)
Case with a large SCR is unclear
(2)
Complex structure
The PSSC controller + TSEC controllerThe modulation voltage approximates the VSC output voltage
(1)
Keep VSC small signal and synchronization stable with an arbitrary SCR
(2)
Simple to realize
(3)
Without voltage sensor
Table 2. System parameters.
Table 2. System parameters.
SymbolValueSymbolValueSymbolValue
f050 HzLf4 mHPref10 kW
Vdc750 VVg311 VKp0.0002
Lg20 mHVi311 VKLL−0.75
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Shi, H.; Shi, P.; Zhou, B.; Wang, X.; Zeng, X.; Ma, J. Transient Synchronization Stability Analysis and Enhancement Control for Power Self-Synchronization Control Converters. Electronics 2024, 13, 3416. https://doi.org/10.3390/electronics13173416

AMA Style

Shi H, Shi P, Zhou B, Wang X, Zeng X, Ma J. Transient Synchronization Stability Analysis and Enhancement Control for Power Self-Synchronization Control Converters. Electronics. 2024; 13(17):3416. https://doi.org/10.3390/electronics13173416

Chicago/Turabian Style

Shi, Huabo, Peng Shi, Bo Zhou, Xi Wang, Xueyang Zeng, and Junpeng Ma. 2024. "Transient Synchronization Stability Analysis and Enhancement Control for Power Self-Synchronization Control Converters" Electronics 13, no. 17: 3416. https://doi.org/10.3390/electronics13173416

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Article metric data becomes available approximately 24 hours after publication online.
Back to TopTop