Next Article in Journal
Optimal Operation of a Novel Small-Scale Power-to-Ammonia Cycle under Possible Disturbances and Fluctuations in Electricity Prices
Next Article in Special Issue
Estimation of the Values of Electrical Shock Currents during Live-Line Work in Multi-Circuit, Multi-Voltage HVAC Transmission Lines
Previous Article in Journal
Predicting the Remaining Life of Centrifugal Pump Bearings Using the KPCA–LSTM Algorithm
Previous Article in Special Issue
Precision Regulation Strategy for Regional Source, Grid, and Load Friendly Interaction Based on Double-Layer Sensitivity Model
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

The Current Harmonic Impact on Active Power Losses and Temperature Distribution in Power Cables

by
Natalia Radwan-Pragłowska
,
Dominik Mamcarz
,
Paweł Albrechtowicz
* and
Bartosz Rozegnał
Department of Electrical Engineering, Cracow University of Technology, Warszawska 24 St., 31-155 Cracow, Poland
*
Author to whom correspondence should be addressed.
Energies 2024, 17(16), 4170; https://doi.org/10.3390/en17164170
Submission received: 16 July 2024 / Revised: 10 August 2024 / Accepted: 15 August 2024 / Published: 21 August 2024
(This article belongs to the Special Issue Energy, Electrical and Power Engineering 2024)

Abstract

:
The active power losses are dependent on the flowing electric power value through overhead and cable lines. The current flow through the conductor causes negative phenomena to occur, such as released heat. The source of the current harmonics is the non-linear loads. Hence, the skin effect occurs, and the current carrying capacity of cables is reduced. This results in the increase in and uneven distribution of the temperature inside the conductor. This paper presents a comparison of the temperature distribution inside a power cable for an ideal 50 Hz sine wave and highly distorted current ( T H D I = 41 % ) . The calculated active power losses for the IEC 60287-1-1:2006+A1:2014 standard and the method described in the literature were used as a basis for further calculations. The obtained results revealed the problem of the uneven distribution of the conductor temperature. Considering the skin effect, increasing the temperature in the outer layers leads to severe damage and faster insulation aging. The abovementioned phenomenon is a decrease in the permissible load capacity of the conductor. The table given in the IEC 60364-5-52 standard summarizes the percentage contribution of the third harmonic to the current waveform. For percentages between 15% and 33%, the current carrying capacity is reduced by up to 86% of the full-load current rating. In addition, consideration of thermal conditions forces the use of cables with larger cross-sections. This leads to their non-optimal use and makes the investment more expensive from an economic point of view.

1. Introduction

The requirements of modern electricity systems include minimalizing energy losses by increasing efficiency, especially in times of rising electricity prices and the associated C O 2 emission certificates. In transmission lines (cable or overhead lines), the flowing current causes power losses connected with various physical phenomena. The primary source of power loss in conductors is the conductor heating during current flow, and then the energy is released as Joule heat [1,2].
For this reason, the power value and load character supplied by the transmission line must be considered at the design stage. This helps avoid overloading the cables and subsequently damaging the insulation due to an excessive temperature rise. In particular, one should pay attention to non-linear loads that generate higher harmonics of the current in the mains. These loads have a negative effect on the transmission line because the higher harmonics have a significant impact on the power losses and cable temperature increase [3,4]. Long-term cable operation in these conditions can lead to insulation degradation and severe damage to power cables. In turn, grid failures affect economic losses in manufacturing companies due to unplanned downtime and shutdowns. It also generates additional costs associated with repairing the installation. The cost and repair time, especially for underground cable lines, is very high. The problem of the impacts of current harmonics on power loss and temperature distribution in power cables is mentioned in [5,6,7,8].
The method described in the IEC 60287-1-1:2006+A1:2014 standard [9] is often used to calculate the approximate value of active power loss. This method operates on factors correlated with the skin effect. It allows obtaining active power losses using the resultant cross-resistance, considering the current penetration depth factor and assuming constant flow over the whole equivalent section for the calculated harmonic order. In the literature, we also find a description by the French researcher Levasseur. He analytically describes the phenomenon, based on observing the skin effect and using frequency changes in the Kelvin effect calculations [10]. The next of the used methods is the method based on Bessel’s function. It allows for finding a solution to the equation in polar coordinate systems associated with wave propagation and spherical potentials. In calculations, the conductor resistance variation caused by the skin effect is considered a correction factor for R D C resistance. The method described by the authors in [1] is based on calculating the equivalent R A C resistance by using the approximation function defined by a fourth-order polynomial (AM method).
The common element for calculating active power losses in power cable methods is determining the resultant resistance R A C ( h ) for a given harmonic order of current ( h ) . In each mentioned method, both skin effect (Figure 1) and conductor proximity can be considered. In addition, a temperature correction factor can be taken into account in order to calculate the new R D C for defined cable operating temperature.
In the methods from [11,12], the resistance increase for the fundamental frequency is taken into account regardless of the cross-sectional area. For small cross-sections (e.g., 25 mm2), the current penetration depth—the skin effect caused—is greater than the radius of the low-voltage cable conductor. Thus, the conclusion is that the skin effect does not occur in this case, and the previously mentioned methods cause an error in the determination of active power losses. However, for the method described in [4], the penetration depth factor is taken into account, including the value of the radius of the cable conductor under consideration (CPD).
The paper presents a comparison of the simplified method proposed by the authors [4] with the standardized method IEC 60287-1-1:2006+A1:2014 [9] for calculating active power losses in power supply lines. The obtained results can provide a starting point for calculating the temperature distribution for different power systems, including those using cable lines in different thermal backfills, e.g., sand–concrete mix (SCM) and geopolymer, for power transmission or for determining the optimal cable conductor diameter and insulation [13,14,15,16].
The main contribution of this work can be summarized as follows:
  • Comparison of the active power loss calculation method based on the current penetration depth coefficient (CPD) with results of the IEC and AM methods;
  • Comparison of R A C / R D C values calculated with different methods;
  • Presentation of temperature distribution inside the cable through which the distorted current flows.
The following paper sections include the following:
  • Section 2: Methods used to determine equivalent cable resistance;
  • Section 3: Current distortion impact on the cable parameters;
  • Section 4: Calculation of the temperature distribution inside cable;
  • Section 5: Research results;
  • Section 6: Conclusions.

2. Methods Used for Calculating Conductor Resistance

Various methods are presented in the literature for calculating the resistance for selected current frequencies, that is, for the influence of skin effect on this parameter. A widely used method to determine the impact of higher harmonics on the conductor resistance is described in the IEC-60287-1-1:2006+A1:2014 standard [9]. This method can be considered the skin effect and the proximity phenomenon (Equation (1)).
R A C I E C = R D C 1 + γ s + γ p
where
γ s = X s 4 192 + 0.8 X s 4
X s 2 = 8 π f R 10 7 · k s
γ p = X p 4 192 + 0.8 X p 4 d c s 2 × 0.312 d c s 2 + 1.18 X p 4 192 + 0.8 X p 4 + 0.27
X p 2 = 8 π f R 10 7 · k p
  • R A C is the AC resistance of the conductor in [ Ω ] ;
  • R D C is the DC resistance of the conductor in [ Ω ] ;
  • γ s is a skin effect factor in ;
  • γ p is a proximity effect factor in ;
  • k s is the coefficient depending on the number of cable cores (for single-core cable k s = 1 ), in [ ] ;
  • d c is the conductor diameter in [mm];
  • s is the distance between conductor axis, [mm];
  • k s is the proximity coefficient depending on the geometrical shape and number of cable cores/sectors and the conductor material in [ ] .
The second method used to determine the resistance dependence of the skin effect is the method using Bessel functions (Equation (7)). The calculated resistance value as a frequency function is obtained as follows:
R A C B = R D C k b
where
k b = R e Z s J 0 Z s 2 J 1 Z s
Z s = e j 3 π 4 · 2 μ 0 μ r γ n f 1 h
  • J 0 , J 1 are Bessel functions of the first kind of the zeroth and first-order, respectively;
  • n is the harmonic order number in [ ] ;
  • f 1 h is the fundamental harmonic frequency in [ H z ] ;
  • μ 0 is the vacuum permeability in [ V s / A m ] ;
  • μ r is the relative permeability in [ ] ;
  • γ is the conductivity of the material in [ m / ( Ω · m m 2 ) ] .
Another case described in the literature allows for the determination of resistance changes based on the approximation method described in [1].
R A C A M = R D C ( 1.344 × 10 15 y A M 4 3.501 × 10 11 y A M 3 + 2.754 × 10 7 y A M 2 2,544 × 10 4 y A M + 1.0459 )
where
y A M = f R D C
According to the article [1], the fourth-order equation allows for an average accuracy of less than 1% compared to solutions based on the method using Bessel functions [1].
The power loss determination method proposed by the authors of this paper uses the current penetration factor (CPD) [4]. The effective resistance R n for selected current harmonics is determined according to the following formula:
R n = l γ · s n
where
  • l is the wire length in [ m ] ;
  • s n is the equivalent of cross-section area, including the skin depth effect, in [ m m 2 ] .
In cases wherein the part of the cross-section area of a conductor for the n-th current harmonic number is described as
s n = π r 2 π r δ n 2
the current penetration depth (expressed by Equation (13)) describes how far (counting from the external edge) flows the current [11]. In this way, it is very easy to notice that a current of a given frequency flows through the effective conductor cross-area, whose dimensions are smaller than the geometric dimensions of the conductor (Figure 2).
δ n = 1 π n f 1 h μ 0 μ r γ
Based on the determined resistance values for each harmonic current, the active power losses are determined with the flow of distorted current:
P = n = 1 R n I n h 2
where
  • I n h is the RMS value of the n-th current harmonic in [A].
Comparing IEC and CPD methods, one can see that CPD refers to each harmonic separately, and therefore, it allows for obtaining more accurate results, while the IEC method uses a kind of empirical equation prepared to verify how the conductor’s resistance changes. The IEC method is developed and applied to each cable type, such as stranded and solid round conductors and sector-shaped ones made from copper or aluminum material.
This paper presents the results of power loss calculations determined by AM, IEC, and CPD methods. The skin effect is considered in the analysis, while the proximity phenomenon ( γ p = 0 ) is neglected.

3. Current Distortion Impact on the Power Cables Parameters

An increasing current distortion is caused by an increase in non-linear loads connected to the power network. This leads to increased line voltage distortion, which in turn causes an increase in current distortion. The level of distortion is described by the THDI (Current Total Harmonic Distortion) factor [17].
T H D I = n = 1 40 I n 2 I 1
where
  • I 1 is the effective value of the signal of the fundamental component;
  • I n is the effective value of the signal of the n-th harmonic.
The Fourier distribution can be used to write the current distribution into individual harmonics:
i 0 t = A 0 + B 1 sin ω t + C 1 cos ω t + n = 2 B n sin ( n ω t ) + n = 2 C n cos ( n ω t )
where
  • A 0 is the DC component of load current;
  • B 1 sin ω t is the active current component;
  • C 1 cos ω t is the reactive current component;
  • n = 2 B n sin ( n ω t ) is the active current component of the higher harmonics;
  • n = 2 C n cos n ω t is the reactive current component of the higher harmonics.
The authors considered requirements from the standard [17] and conducted the power loss analysis according to these guidelines (current harmonics up to 40th order were included).
The impact of non-linear loads installed at individual electricity consumers on the losses resulting from the flow of distorted current is negligibly small. It is caused by the small values of the power transmitted in the LV distribution lines. However, a different approach should be used for the non-linear loads installed in the industrial sector. The power of the installed equipment generating the flow of higher harmonics is of the order from several hundred kW to several MW.
Power cables are widely used in power systems, especially in the industry sector. They have to fulfill many requirements in terms of electrical parameters (current carrying capacity, high insulation resistance, short-circuit durability) and mechanical (cable routing, environmental conditions, non-flammability, special working conditions). In the design stage, therefore, all of the above requirements should be taken into account. Figure 3 shows the possible cable arrangement methods for three single-core cables. The highest working temperature for different types of insulation, according to IEC 60364-5-52:2009 standard [18]:
  • Vulcanized natural rubber (VIR): 60   ;
  • Polyvinyl chloride (PVC): 70   ;
  • Polyethylene (PE): 75   ;
  • Butyl rubber (IIK): 85   ;
  • Cross-linked polyethylene (XLPE) and ethylene propylene rubber (EPR): 90   ;
  • Ethylene–vinyl acetate (EVA): 120   ;
  • Silicone rubber: 180   .
A significant influence on cable heating is the cable construction and the material from which it is made. The conductor material of the cable core determines its conductivity. In turn, the insulation material and its thickness determine the electrical and mechanical strength and heat distribution (cable heating). The proximity effect can be ignored in the single-conductor or multi-conductor shielded cables (when each conductor is shielded). The most commonly used low-voltage cables are non-shielded, so this effect cannot be ignored in these construction types. Increasing the accuracy of the calculations can help to reduce the cost of constructing cable lines.
The cable route routing and the backfilled material significantly impact the temperature distribution and the maximum load current value. The most common thermal backfill used for cables buried in the ground is dry sand, sand–bentonite mixtures (SCMs), sand, and Portland cement (in a 12:1 ratio) [13,14,15].
There are also advantages of new materials, such as geopolymers with better thermal conductivity properties and improved safety for the environment [17]. The better backfill thermal conductivity is important because it allows the conducting of heat efficiently during current flow through the cable. When the cable temperature increases, the electrical conductivity decreases, caused by a reduction in electron mobility in the metal conductor. The used backfill also reduces dry zones around the cables, which have negatively affected heat dissipation.
Cables with aluminum conductors, such as AsXSn, steel–aluminum (AFL), AlMgSi aluminum alloys (BLX-T), are commonly used in power systems. This has a direct effect on the lower conductivity value compared to copper conductors.

4. Calculation of the Temperature Distribution

In Equation (14), for the calculation value of active power losses, by including the temperature coefficient of resistance, the temperature effect on the value of the equivalent resistance is included in the calculation:
R t = R r e f 1 + α r e f T c ( x , y ) T r e f
where
  • R t is the resistance of the conductor at t ;
  • R r e f is the resistance of the conductor at 20   ;
  • T c ( x , y ) is conductor temperature in ;
  • T r e f is references conductor temperature (default value 20   ) in ;
  • α r e f is temperature coefficient of resistance of material at 20   .
In Equation (14), the temperature impact on the equivalent resistance value described by Equation (17) was obtained as follows:
P t = n = 1 R n I n h 2 · 1 + α r e f T c ( x , y ) T r e f
To calculate the temperature distribution inside a low-voltage power cable, the heat source can be represented as
q ν T x , y = Δ P t s n
Based on Equation (19), the temperature of the cable conductor (20), PVC insulation (21), backfill (22), and soil (23) should be determined as
x k c T ( x , y ) x + y k c T ( x , y ) y = q ν , c ( T x , y )
x k i n s T ( x , y ) x + y k i n s T ( x , y ) y = q ν , i n s ( T x , y )
x k b T ( x , y ) x + y k b T ( x , y ) y = 0
x k s T ( x , y ) x + y k s T ( x , y ) y = 0
where
  • x, y is a selected point in the calculation area on Cartesian coordinates;
  • k c is a thermal conductivity of the cable conductor in [ W / ( m · K ) ] ;
  • k i n s is a thermal conductivity of the PVC insulation in [ W / ( m · K ) ] ;
  • k b is a thermal conductivity of the backfill in [ W / ( m · K ) ] ;
  • k s is a thermal conductivity of the soil in [ W / ( m · K ) ] .
To solve Equations (20)–(23), have assumed boundary conditions as follows:
k T x x = 0 = 0
k T x x = w = 0
k T y y = h H = 0
T x , y = h = T g = 20
Figure 4 shows the excavation geometry for the low-voltage cable line used to calculate the temperature distribution.
Thermal conductivity values for different materials were taken as follows:
  • For cable conductor k c = 400   [ W / ( m · K ) ] ;
  • For PVC insulation k i n s = 0.285   [ W / ( m · K ) ] ;
  • For the outer layer of the cable k e x t = 0.285   [ W / ( m · K ) ] ;
  • For backfill (sand) k b = 0.85   [ W / ( m · K ) ] ;
  • For soil k s = 0.85   [ W / ( m · K ) ] .

5. The Research Results

For selected methods used to calculate the impact of the skin effect on the values of equivalent resistance and, consequently, active power losses, calculations were made for a case where a distorted current flows through the conductor. For analysis, the following methods were selected: the method proposed by the authors (based on the current penetration coefficient CPD), the method described in the IEC standard, and the AM method.
Figure 5 presents the active power losses for three different current loads of the first harmonic, equal to 25, 50, and 75% of the long-term current carrying capacity provided by the manufacturer for selected cross-sections of single-core YKY-type cables. The level of current distortion for which the calculations were conducted amounted to THDI = 76% (the current spectrum is presented in Figure 6).
For relatively small cross-sections of 25–120 mm2, the impact of the skin effect is negligible, and the results for all computational methods are similar. With the increase in the conductor cross-section, the IEC method yields lower values compared to the other presented methods. For the largest cross-sections (300 mm2 and 400 mm2), the method presented by the authors results in the highest power loss values (the results are presented for a 1 m length of cable).
The unit active power losses for the analyzed cable cross-sections were compiled as a function of the relative change in reference to the ideal current waveform at a frequency of 50 Hz and an RMS value equal to the specified load-carrying capacity for the given case. Figure 7 illustrates the values of relative power losses. For small cross-sections, both the authors’ method (CPD) and the IEC method yield positive values, meaning the calculated active power losses are higher than for the standard waveform. Conversely, for the AM method, negative values were obtained for cross-sections of 25–35–50–70 mm2. This indicates that according to this method, power losses for a distorted waveform (THDI = 76%) in the given surface area ranges are lower than for the standard current waveform (undeformed 50 Hz sine wave). The highest increases in values occur for the AM method for cross-sections of 185–240 mm2, and for analyzed cross-sections ≥ 300 mm2, the results assume values smaller than those calculated by the CPD method and greater than those calculated by the AM method. The largest relative power loss values are obtained for cross-sections of 25–120 mm2 using the IEC method, whereas for cross-sections ≥ 240 mm2, the results assume the smallest values.
Both methods (AM and IEC) allow for the calculation of power losses, but as can be seen in Figure 7, the obtained values are difficult to interpret. Results obtained by the AM method for small cross-sections take negative values, while the IEC method yields the highest values among all the analyzed methods. Beyond a cross-section of 120 mm2, the values obtained by the AM method are higher than those calculated by the IEC method. Both methods use an approximating function when determining the equivalent resistance for higher harmonics. Comparing the results obtained by both methods reveals that for small cross-sections, the accuracy of the IEC method is higher, while for larger cross-sections, more accurate values are obtained based on the AM method. The method developed by the authors, which is based on an accurate calculation of penetration depth, returns results greater than 0 in every case, which, compared to the AM method, is a definite advantage. Another element indicating the inaccuracy of the AM method compared to the solution proposed by the authors is illustrated in Figure 8 and Figure 9 (20 °C) as well as Figure 10 and Figure 11 (~90 °C), where the relative values of resistance determined for each harmonic are compared in relation to the resistance for the fundamental harmonic. The results are presented for two cross-sections, 35 mm2 and 300 mm2. These values were chosen to show the results obtained for a cross-section where the skin effect is minimal (35 mm2) and for one where the effect is already significant (300 mm2).
For smaller cross-sections (Figure 8 and Figure 10), the resistance values calculated by the AM method are lower than the fundamental harmonic resistance. According to theory, this phenomenon is impossible to achieve. For cross-sections ≤ 25 mm2, the current flows through the entire cross-sectional area of the conductor because the penetration depth for harmonics < 10 is greater than the radius of the conductor (δ10h = 3.035 mm, while r25mm2 = 2.82 mm). The obtained results would imply an increase in cross-section for these harmonics, which is impossible in the considered system. The CPD method (the authors’ method) assumes an increase in the resistance of a given harmonic relative to the fundamental in the case where a penetration depth is smaller than the radius of the conductor. As a result, for a large cross-section (300 mm2Figure 9), values greater than the fundamental harmonic were obtained, while for a small cross-section (35 mm2 Figure 8), for for harmonics less than 12, a constant resistance value equal to the fundamental resistance was obtained—the increase in calculated resistance amounted to 0.
An interesting relationship can be observed in the resistance change curve of a 300 mm2 cable for the IEC method. Starting from approximately the 20th harmonic, the resistance increase values are much smaller than for the other methods, i.e., AM and CPD. However, despite significant differences compared to other methods, these values do not have a significant impact on the final value. This is due to the fact that harmonics of the 12th order and higher take on small values. The major drawback of this method is the observed lack of an increase in losses for harmonics of order > 20. Despite the small amplitudes of harmonics of order > 20, the increase in resistance should not be close to zero. Such a tendency of the IEC method disqualifies it for applications aimed at precisely determining power losses in power cables in cases of distorted current waveforms, but only for cases where the current spectrum includes values > 20.
Figure 12 shows the value of active power losses calculated according to selected methods for a current frequency of 50 Hz. Even for this frequency value, discrepancies are visible, the trend of which is consistent with the analysis of the results of the methods described above.

6. FEM Analysis

The authors performed a comparative analysis of temperature distribution using FEM (Finite Element Method) calculations. Three cases of cable placement were analyzed: in air, in sand, and in two areas (air and sand to illustrate the temperature changes at the interface between the surroundings). Thermal analyses (transient) were carried out using the ASNSY Icepak environment, making it possible to determine the value of power losses.
The simulation time of 24 h was assumed, with the Time Step of 10 min and 20 Iterations per Time Step for each simulation.
The surrounding region had dimensions of 4 m × 4 m × 4 m in the case of a single medium. For the analysis, in which there was a combination of two materials, the sand region and the air region had dimensions of 8.5 m × 4 m × 4 m each. The temperature distribution was performed in the tested cable and surroundings based on pre-set power losses dependent on the conductive wire part temperature. For cases with one area material (air or sand), two cables were placed next to each other, but only one of them was supplied with power.
Table 1 and Table 2 contain the maximum temperature and power losses for 1 m cable for sand and air surrounding.
The following Figure 13 and Figure 14 show the impact of surrounding for neighboring wire. The finite elements number was 553,571. In Figure 13, one can see the temperature distribution for the cable YKY 1 × 150 mm2 surrounded by air. For this case, an initial ambient temperature value of 30 °C was set. The effect of gravity, the radiation phenomenon, and the Opening Model condition with ambient pressure were taken into account. The THD coefficient was 76%, and the selected method was AM. The simulated cable length was 1 m.
Figure 14 shows the temperature distribution for the cable YKY 1 × 150 mm2 surrounded by sand. The thermal analysis for the case of a cable laid in sand also assumed a simulation time of 24 h, with steps of 10 min. The initial value of the sand temperature was set at 20 °C. The effect of gravitational force was taken into account. The THD coefficient was 76%, and the selected method was AM. The simulated cable length was 1 m.
Figure 15 and Figure 16 show the temperature changes according to distance from the cable center (along the radius) for the cable surrounded by sand (Figure 15) and air (Figure 16) for THD coefficients of 76% and 32%.
Figure 17 shows the temperature distribution at the boundary of two media air/sand for YKY 1 × 300 mm2 cable. The surrounded region had dimensions of 17 m × 4 m × 4 m and was divided into two 8.5 m lengths each. The analyzed cable length was 13 m (6.5 m was placed in air and 6.5 m in sand). The finite element number was 6,780,323. The initial value of the sand temperature was set at 20 °C, and the air temperature was set at 30 °C. The effect of gravitational force was taken into account. The THD coefficient was 76%, and the selected method was AM.
Figure 18 presents the comparative analysis of the effect of the selected method (CPD, IEC, and AM) on the maximum temperature value at the hot spot (at the contact of surrounding materials). The analyzed cable length was 10 m (6.5 m was placed in air and 3.5 m in sand). The THD 76% and 32% were taken into account.

7. Conclusions

This article presents an in-depth analysis of power loss in power cables due to current harmonics, specifically focusing on their effect on temperature distribution within the cables. The findings suggest that higher current harmonics significantly impact power losses and necessitate larger cable cross-sections, impacting economic feasibility.
The authors compared the active power loss calculation method based on the current penetration depth coefficient (CPD) with the results of the IEC and AM methods. This comparison highlights the effectiveness and accuracy of the CPD method in representing the losses caused by the flow of higher current harmonics and makes the comparison of the resistance values (RAC/RDC) calculated with different methods. This aspect of the research underscores the variance in the calculation results when different methodologies are applied, as well as the importance of choosing an appropriate method for accurate loss calculation. The CPD method proposed by the authors indicates an upward trend in the resistance of individual harmonics, reflecting the losses caused by the flow of higher-current harmonics most accurately. Regardless of the chosen method of verification (computational/experimental variant in which the compared computational methods were implemented), the computational method proposed by the authors maintained consistency. The results were logically coherent, repeatable, and showed the same trend and tendency.
The paper also presents the detailed temperature distribution inside the cable through which the distorted current flows. This part of the study was crucial to understanding how current harmonics influence the thermal behavior of power cables, which can have significant implications for cable design and safety. The results presented in the article for the cable laid in two different environments are a precursor to further studies aimed at illustrating the change in temperature at the boundary of contact between two different environments. In this location, a dangerous hot spot may occur, which could result in cable damage.
The performed tests, which took into account the presence of two environments, will form the basis for further analysis.

Author Contributions

Conceptualization, D.M., N.R.-P., P.A. and B.R.; methodology, D.M., N.R.-P., P.A. and B.R.; software, D.M. and N.R.-P.; validation, D.M., N.R.-P., P.A. and B.R.; formal analysis, D.M., N.R.-P., P.A. and B.R.; investigation, D.M., N.R.-P., P.A. and B.R.; resources, D.M. and N.R.-P.; data curation, D.M., N.R.-P., P.A. and B.R.; writing—original draft preparation, D.M., N.R.-P., P.A. and B.R.; writing—review and editing, D.M., N.R.-P., P.A. and B.R. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Polish Ministry of Science and Higher Education and performed by the Cracow University of Technology.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available upon request from the corresponding author.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Desmet, J.; Vanalme, G.; Belmans, R.; Van Dommelen, D. Simulation of Losses in LV Cables due to Nonlinear Loads. In Proceedings of the 2008 IEEE Power Electronics Specialists Conference, Rhodes, Greece, 15–19 June 2008; pp. 785–790. [Google Scholar] [CrossRef]
  2. Wu, W.N.; Zhu, S.J.; Luo, J.B.; Chen, X.; Song, C.P.; Qu, X.L.; Wang, Y. Measurement of the AC Resistance of Small Cross Section Power Cables. In Proceedings of the 9th International Conference on Insulated Power Cables, Versailles, France, 21–25 June 2015; pp. 1–5. [Google Scholar]
  3. Novak, B. Investigation of asymmetric power distribution in balanced three-phase systems in planar arrangement. Electr. Electron. Technol. Open Access J. 2018, 2, 335–340. [Google Scholar] [CrossRef]
  4. Rozegnał, B.; Albrechtowicz, P.; Mamcarz, D.; Rerak, M.; Skaza, M. The Power Losses in Cable Lines Supplying Non-linear Loads. Energies 2021, 14, 1374. [Google Scholar] [CrossRef]
  5. O’Connell, K.; Barrett, M.; Blackledge, J.; Sung, A. Cable Heating Effects due to Harmonic Distortion in Electrical Installations. In Proceedings of the World Congress on Engineering, London, UK, 4–6 July 2012. [Google Scholar]
  6. Patil, K.D.; Gandhare, W.Z. Effects of harmonics in distribution systems on temperature rise and life of XLPE power cables. In Proceedings of the Power and Energy Systems (ICPS), 2011 International Conference on Power and Energy Systems, Chennai, India, 22–24 December 2011; pp. 1–6. [Google Scholar] [CrossRef]
  7. Tofoli, F.L.; Sanhueza, S.M.R.; de Oliveira, A. On the study of losses in cables and transformers in nonsinusoidal conditions. IEEE Trans. Power Deliv. 2006, 21, 971–978. [Google Scholar] [CrossRef]
  8. Dong, Y.; Shi, Y. Analysis of Losses in Cables and Transformers with Unbalanced Load and Current Harmonics. J. Electr. Electron. Eng. 2021, 9, 78–86. [Google Scholar] [CrossRef]
  9. IEC 60287-1-1:2006+A1:2014; Electric Cables—Calculation of the Current Rating—Part 1-1: Current Rating Equations (100% Load Factor) and Calculation of Losses—General. International Electrotechnical Commission: Geneva, Switzerland, 2014.
  10. Lavasseur, A. Nouvelles formules, valables a toutes les frequences, pour le calcul rapide de l’effet Kelvin. J. Phys. Radium 1930, 1, 93–98. [Google Scholar] [CrossRef]
  11. Topolski, Ł.; Warecki, J.; Hanzelka, Z. Methods for determining power losses in cable lines with non-linear load. Przegląd Elektrotechniczny 2018, 94, 85–90. [Google Scholar] [CrossRef]
  12. IEC Standard 60287-2-1:1995; Electric Cables–Calculation of the Current Rating–Part 2: Thermal Resistance–Section 1: Calculation of the Thermal Resistance. International Electrotechnical Commission: Geneva, Switzerland, 1995.
  13. Ocłoń, P.; Taler, D.; Cisek, P. Fem-Based Thermal Analysis of Underground Power Cables Located in Backfills Made of Different Materials. Strength Mater. 2015, 47, 770–780. [Google Scholar] [CrossRef]
  14. Ocłoń, P.; Bittelli, M.; Cisek, P.; Kroener, E.; Pilarczyk, M.; Taler, D.; Rao, R.V.; Vallati, A. The performance analysis of a new thermal backfill material for underground power cable system. Appl. Therm. Eng. 2016, 108, 233–250. [Google Scholar] [CrossRef]
  15. Ocłoń, P.; Cisek, P.; Pilarczyk, M.; Taler, D. Numerical simulation of heat dissipation processes in underground power cable system situated in thermal backfill and buried in a multilayered soil. Energy Convers. Manag. 2015, 95, 352–370. [Google Scholar] [CrossRef]
  16. Ocłoń, P.; Cisek, P.; Matysiak, M. Analysis of an application possibility of geopolymer materials as thermal backfill for underground power cable system. Clean Technol. Environ. Policy 2021, 23, 869–878. [Google Scholar] [CrossRef]
  17. IEC 61000-4-7:2002+AMD1:2008; Electromagnetic Compatibility (EMC)—Part 4-7: Testing and Measurement Techniques—General Guide on Harmonics and Interharmonics Measurements and Instrumentation, for Power Supply Systems and Equipment Connected Thereto. International Electrotechnical Commission: Geneva, Switzerland, 2009.
  18. IEC 60364-5-52:2009; Low-Voltage Electrical Installations—Part 5-52: Selection and Erection of Electrical Equipment—Wiring Systems. International Electrotechnical Commission: Geneva, Switzerland, 2009.
Figure 1. The skin effect illustration.
Figure 1. The skin effect illustration.
Energies 17 04170 g001
Figure 2. The frequency-dependent effective conductor cross-area.
Figure 2. The frequency-dependent effective conductor cross-area.
Energies 17 04170 g002
Figure 3. (a) Electrical cable construction; (b,c) cable arrangement: (b) flat formation; (c) trefoil formation.
Figure 3. (a) Electrical cable construction; (b,c) cable arrangement: (b) flat formation; (c) trefoil formation.
Energies 17 04170 g003
Figure 4. The excavation geometry.
Figure 4. The excavation geometry.
Energies 17 04170 g004
Figure 5. Unit active power losses for selected cross-sections of YKY-type cables.
Figure 5. Unit active power losses for selected cross-sections of YKY-type cables.
Energies 17 04170 g005
Figure 6. Current spectrum (THDI = 76%).
Figure 6. Current spectrum (THDI = 76%).
Energies 17 04170 g006
Figure 7. Increases in power losses in relation to the ideal current waveform (THD = 0%).
Figure 7. Increases in power losses in relation to the ideal current waveform (THD = 0%).
Energies 17 04170 g007
Figure 8. Increase in resistance, according to the fundamental harmonic resistance of a 35 mm2 cable, for the analyzed methods (conductor/cable core temperature of 20 °C).
Figure 8. Increase in resistance, according to the fundamental harmonic resistance of a 35 mm2 cable, for the analyzed methods (conductor/cable core temperature of 20 °C).
Energies 17 04170 g008
Figure 9. Increase in resistance, according to the fundamental harmonic resistance of a 300 mm2 cable, for the analyzed methods (conductor/cable core temperature of 20 °C).
Figure 9. Increase in resistance, according to the fundamental harmonic resistance of a 300 mm2 cable, for the analyzed methods (conductor/cable core temperature of 20 °C).
Energies 17 04170 g009
Figure 10. Increase in resistance, according to the fundamental harmonic resistance of a 35 mm2 cable, for the analyzed methods (conductor/cable core temperature of ~90 °C).
Figure 10. Increase in resistance, according to the fundamental harmonic resistance of a 35 mm2 cable, for the analyzed methods (conductor/cable core temperature of ~90 °C).
Energies 17 04170 g010
Figure 11. Increase in resistance, according to the fundamental harmonic resistance of a 300 mm2 cable, for the analyzed methods (conductor/cable core temperature of ~85 °C).
Figure 11. Increase in resistance, according to the fundamental harmonic resistance of a 300 mm2 cable, for the analyzed methods (conductor/cable core temperature of ~85 °C).
Energies 17 04170 g011
Figure 12. Active power losses for the fundamental frequency calculated using different methods.
Figure 12. Active power losses for the fundamental frequency calculated using different methods.
Energies 17 04170 g012
Figure 13. The temperature distribution for the cable YKY 1 × 150 mm2 surrounded by air.
Figure 13. The temperature distribution for the cable YKY 1 × 150 mm2 surrounded by air.
Energies 17 04170 g013
Figure 14. The temperature distribution for the cable YKY 1 × 150 mm2 surrounded by sand.
Figure 14. The temperature distribution for the cable YKY 1 × 150 mm2 surrounded by sand.
Energies 17 04170 g014
Figure 15. The temperature changes along the cable (1 × 150 mm2) radius and for surrounding sand: (a) THD 76%; (b) 32%.
Figure 15. The temperature changes along the cable (1 × 150 mm2) radius and for surrounding sand: (a) THD 76%; (b) 32%.
Energies 17 04170 g015
Figure 16. The temperature changes along the cable (1 × 150 mm2) radius and for surrounding air: (a) THD 76%; (b) 32%.
Figure 16. The temperature changes along the cable (1 × 150 mm2) radius and for surrounding air: (a) THD 76%; (b) 32%.
Energies 17 04170 g016
Figure 17. The temperature distribution at the boundary of two media air/sand for YKY 1 × 300 mm2 cable (the hot-spot temperature was 53.91 °C).
Figure 17. The temperature distribution at the boundary of two media air/sand for YKY 1 × 300 mm2 cable (the hot-spot temperature was 53.91 °C).
Energies 17 04170 g017
Figure 18. The temperature changes along the cable, taking into account two types of environment: A—CPD method, B—IEC method, C—AM method; (a) THD 76%; (b) 32%.
Figure 18. The temperature changes along the cable, taking into account two types of environment: A—CPD method, B—IEC method, C—AM method; (a) THD 76%; (b) 32%.
Energies 17 04170 g018
Table 1. Power losses and temperature for cable buried in sand.
Table 1. Power losses and temperature for cable buried in sand.
YKY 1 × 35 mm2YKY 1 × 150 mm2YKY 1 × 300 mm2
MethodTHD
[%]
Tmax
[°C]
P
[W/m]
Tmax
[°C]
P
[W/m]
Tmax
[°C]
P
[W/m]
CPD3243.6321.721043.4126.099146.7932.7767
IEC43.6721.762643.8326.567746.1532.0006
AM43.6421.733643.7626.489145.4631.1474
CPD7655.1832.368356.4340.658664.0053.6327
IEC55.3132.492256.5140.749062.1351.6157
AM55.2632.445756.0940.273759.5048.3865
Table 2. Power losses and temperature for cable surrounded by air.
Table 2. Power losses and temperature for cable surrounded by air.
YKY 1 × 35 mm2YKY 1 × 150 mm2YKY 1 × 300 mm2
MethodTHD
[%]
Tmax
[°C]
P
[W]
Tmax
[°C]
P
[W]
Tmax
[°C]
P
[W]
CPD3273.5424.095266.1228.266966.5535.1166
IEC73.6024.142766.6628.782765.8334.2812
AM73.4524.101366.5728.696265.0433.3614
CPD7691.5336.494082.2044.316685.0157.4654
IEC91.7636.643382.3044.417083.3355.3615
AM91.5936.577981.7943.891680.5451.9031
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Radwan-Pragłowska, N.; Mamcarz, D.; Albrechtowicz, P.; Rozegnał, B. The Current Harmonic Impact on Active Power Losses and Temperature Distribution in Power Cables. Energies 2024, 17, 4170. https://doi.org/10.3390/en17164170

AMA Style

Radwan-Pragłowska N, Mamcarz D, Albrechtowicz P, Rozegnał B. The Current Harmonic Impact on Active Power Losses and Temperature Distribution in Power Cables. Energies. 2024; 17(16):4170. https://doi.org/10.3390/en17164170

Chicago/Turabian Style

Radwan-Pragłowska, Natalia, Dominik Mamcarz, Paweł Albrechtowicz, and Bartosz Rozegnał. 2024. "The Current Harmonic Impact on Active Power Losses and Temperature Distribution in Power Cables" Energies 17, no. 16: 4170. https://doi.org/10.3390/en17164170

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop